2020-11-10 13:43:43 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC B 107.1. THE CONSTRUCTION DOCUMENTS SHALL BE |
| PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE |
| REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 |
| FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA |
| STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. |
| 2. FBC B 1609. PROVIDE A COMPLETE SET OF SIGNED AND |
| SEALED DESIGN PRESSURE CALCULATIONS FOR HIGH |
| RISE/COMMERCIAL BUILDINGS BY A FLORIDA REGISTERED |
| DESIGN PROFESSIONAL. DESIGN PRESSURE CALCULATIONS MUST |
| BE SPECIFIC FOR EACH OPENING. |
| 3. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| HEADING ?WALL PRESSURE?; PROVIDE THE ACTUAL [PSF] FROM |
| THE REVISED DESIGN PRESSURE CALCULATIONS. PLEASE |
| CORRECT COLUMN HEADING ?ANCHOR SPACING?; USE CORRECT |
| DESIGN PRESSURE CALCULATIONS TO DETERMINE CORRECT |
| SPACING. |
| |