Plan Review Details - Permit 20110081
Plan Review Stops For Permit 20110081
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-03 Cont ID  
Sent By rmcphers Date 2021-03-03 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2021-03-03 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 12:29 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 11:29 Sent To  
Notes
2020-11-19 12:29:20SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC R703.2 WATER-RESISTIVE BARRIER. ONE LAYER OF NO.
 15 ASPHALT FELT, FREE FROM HOLES AND BREAKS, COMPLYING
 WITH ASTM D226 FOR TYPE 1 FELT OR OTHER APPROVED
 WATER-RESISTIVE BARRIER SHALL BE APPLIED OVER STUDS OR
 SHEATHING OF ALL EXTERIOR WALLS.
 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS. (COMPLETE = FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS). ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 10:38 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-03 Cont ID  
Sent By rmcphers Date 2021-03-03 Time 08:37 Rev Time 0.00
Received By rmcphers Date 2021-02-18 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 10:38 Rev Time 0.00
Received By equinone Date 2020-11-18 Time 11:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-03 Cont ID  
Sent By rmcphers Date 2021-03-03 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2021-03-03 Time 08:36 Sent To  
Notes
2021-03-03 08:37:06SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 12:34 Sent To  
Notes
2020-11-18 17:01:57ORIGINAL SEALED AND SIGNED DRAWINGS WERE SENT TO
 STORAGE. ME