Plan Review Details - Permit 20110014
Plan Review Stops For Permit 20110014
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By jleahy Date 2020-11-13 Time 11:39 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 11:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By jleahy Date 2020-11-05 Time 08:43 Rev Time 0.00
Received By jleahy Date 2020-11-05 Time 08:43 Sent To  
Notes
2020-11-05 08:46:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONLY LOW VOLTAGE SHOWN ON PLANS IS THE TVS, ALL OTHERS
 WILL REQUIRE PLANS FOR INSTALLATION.
  
 SUBMIT SIGNED PLANS FOR LOW VOLTAGE SYSTEMS BEING
 INSTALLED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-13 Cont ID  
Sent By jleahy Date 2020-11-13 Time 11:39 Rev Time 0.00
Received By jleahy Date 2020-11-12 Time 14:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By jleahy Date 2020-11-13 Time 11:38 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 11:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By jleahy Date 2020-11-05 Time 08:47 Rev Time 0.00
Received By jleahy Date 2020-11-05 Time 08:47 Sent To  
Notes
2020-11-05 08:47:44NO PLANS SUBMITTED