Plan Review Details - Permit 20101493
Plan Review Stops For Permit 20101493
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-24 Cont ID  
Sent By pvalenti Date 2020-11-24 Time 17:33 Rev Time 0.00
Received By pvalenti Date 2020-11-24 Time 17:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By pvalenti Date 2020-11-19 Time 06:12 Rev Time 0.00
Received By pvalenti Date 2020-11-19 Time 05:55 Sent To  
Notes
2020-11-19 06:22:58PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 PLEASE PROVIDE MORE INFORMATION ON THIS PRODUCT. THE
 TEST REPORTS THAT WERE SENT ARE NOT APPLICABLE TO THIS
 LOCATION. THIS APPLICATION IS NOT FOR A DROP CEILING.
  
 PLEASE PROVIDE THE MANUFACTURER'S INFORMATION FROM THIS
 PRODUCT AND THE FOLLOWING TEST REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-24 Cont ID  
Sent By pvalenti Date 2020-11-24 Time 17:34 Rev Time 0.00
Received By pvalenti Date 2020-11-19 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By pvalenti Date 2020-11-19 Time 06:12 Rev Time 0.00
Received By pvalenti Date 2020-11-05 Time 15:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By pvalenti Date 2020-11-19 Time 06:12 Rev Time 0.00
Received By pvalenti Date 2020-11-19 Time 05:55 Sent To  
Notes
***NONE***