Plan Review Stops For Permit 20101457 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-12-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-12-22 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-12-22 |
Time |
14:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-11-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-12 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-12 |
Time |
12:47 |
Sent To |
|
|
Notes |
2020-11-12 15:03:48 | SFR REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) OFFICE AREA IS CONSIDERED LIVING SPACE WHICH IS | | HABITABLE SPACE - PLEASE SHOW THE CEILING HEIGHT TO | | COMPLY WITH FBC R305.1 MINIMUM HEIGHT. | | HABITABLE SPACE, HALLWAYS AND PORTIONS OF BASEMENTS | | CONTAINING THESE SPACES SHALL HAVE A CEILING HEIGHT OF | | NOT LESS THAN 7 FEET (2134 MM). EXCEPTIONS:1.FOR ROOMS | | WITH SLOPED CEILINGS, THE REQUIRED FLOOR AREA OF THE | | ROOM SHALL HAVE A CEILING HEIGHT OF NOT LESS THAN 5 | | FEET (1524 MM) AND NOT LESS THAN 50 PERCENT OF THE | | REQUIRED FLOOR AREA SHALL HAVE A CEILING HEIGHT OF NOT | | LESS THAN 7 FEET (2134 MM). | | 2) DRAWING A3 SHOWS SECTION CUTS A/A1 AND B/A1 - | | DRAWING A1 DOES NOT SHOW THESE SECTIONS. (CEILING | | HEIGHT WOULD BE BEST SHOWN ON THOSE CUT SECTIONS. | | 3) SMOKE ALARM PLACEMENTS NEAR BATHROOM DOOR - FBC | | R314.3 LOCATION (4).SMOKE ALARMS SHALL BE INSTALLED NOT | | LESS THAN 3 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR | | OPENING OF A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER | | UNLESS THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM | | REQUIRED BY SECTION R314.3. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-12-21 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-12-21 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-11-10 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-11-10 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-11-10 |
Time |
14:42 |
Sent To |
|
|
Notes |
2020-11-10 14:56:20 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED | | | | 1) SMOKE ALARM IN MASTER BEDROOM REQUIRED. FBC RE - | | 314.3 | | 2) PLEASE SHOW LOCATION OF MAIN SERVICE DISCONNECT AND | | METER FBC RE - 107 | | 3) RISER DIAGRAM: PLEASE SPECIFY SIZE OF BREAKER | | PROTECTING THE FEEDER TO NEW PANEL A. FBC RE ? E3704, | | E3705 | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2020-12-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-23 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-23 |
Time |
14:15 |
Sent To |
|
|
Notes |
2020-12-23 14:32:33 | 2ND REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20101457 | | 12/23/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: NOT REQUIRED. THE SUBMITTED GAS | | PLAN WAS NOT REVIEWED UNDER THIS MAIN PERMIT. A | | SEPARATE PRIMARY GAS PERMIT AND PLANS SHALL BE | | SUBMITTED FOR REVIEW. SEE COMMENT #1 FROM THE 1ST | | REVIEW PRIUNTED BELOW. | | | | 1) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED | | FOR GAS PIPING- SECTIONS 105.1 & 107.2.1 WPB. A REVIEW | | OF THE GAS HAS NOT BEEN PERFORMED UNDER THIS PERMIT. A | | COMPLETE GAS PLAN, RISER DRAWING, PIPE SIZING TABLES, | | AND PIPING AND APPLIANCE SPECIFICATIONS SHALL BE | | SUBMITTED FOR REVIEW. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2020-11-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-11-05 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-11-05 |
Time |
09:11 |
Sent To |
|
|
Notes |
2020-11-05 09:12:26 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20101457 | | 11/5/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: NOT REQUIRED | | | | 1) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED | | FOR GAS PIPING- SECTIONS 105.1 & 107.2.1 WPB. A REVIEW | | OF THE GAS HAS NOT BEEN PERFORMED UNDER THIS PERMIT. A | | COMPLETE GAS PLAN, RISER DRAWING, PIPE SIZING TABLES, | | AND PIPING AND APPLIANCE SPECIFICATIONS SHALL BE | | SUBMITTED FOR REVIEW. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
3 |
Status |
P |
Date |
2021-01-08 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2021-01-08 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2021-01-08 |
Time |
14:43 |
Sent To |
|
|
Notes |
2021-01-08 14:43:39 | PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | | | 1. THE CEILING FOR THE PORCH AND PORTE COCHERE SHALL BE | | MADE OF WOOD AND HAVE A TONGUE AND GROOVE PROFILE. | | 2. ALL WINDOW INFORMATION REFERENCED ON THIS PERMIT IS | | FOR INFORMATIONAL PURPOSES ONLY. A SEPARATE WINDOW AND | | DOOR PERMIT EXIST. | | 3. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, | | LANDSCAPING. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
F |
Date |
2020-12-23 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-12-23 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-12-23 |
Time |
14:52 |
Sent To |
|
|
Notes |
2020-12-23 14:53:02 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT | | VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO | | COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION | | 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE | | SPEAK WITH RAY CARANCI ? SENIOR LANDSCAPING PLANNER - | | [email protected] TO SHOW COMPLIANCE WITH CURRENT | | LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING | | PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING | | PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR. | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | 1. THE CEILING FOR THE PORCH AND PORTE COCHERE SHALL BE | | MADE OF WOOD AND HAVE A TONGUE AND GROOVE PROFILE. | | 2. ALL WINDOW INFORMATION REFERENCED ON THIS PERMIT IS | | FOR INFORMATIONALLY PURPOSES ONLY. A SEPARATE WINDOW | | AND DOOR PERMIT EXIST. | | 3. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, | | LANDSCAPING. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2020-11-23 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-11-23 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-11-23 |
Time |
14:39 |
Sent To |
|
|
Notes |
2020-11-23 14:39:53 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. NEW MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN | | FOUR FEET INTO A SETBACK. REVISE AS NEEDED. A SEPARATE | | PERMIT IS NEEDED. | | 2. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, | | LANDSCAPING. PLEASE ACKNOWLEDGE THIS. | | 3. ILLUSTRATE REAR PORCH COMPLIES WITH SEC. 94-305 | | (B)(7) - STEPS AND PORCHES. STEPS, OPEN UNCOVERED | | PORCHES OR STOOPS, AND OPEN TERRACES WHICH ARE THREE | | FEET OR LESS ABOVE GRADE MAY ENCROACH INTO ANY REQUIRED | | SETBACK AREA TO A POINT NOT CLOSER THAN TWO FEET TO THE | | PROPERTY LINE. ANY GRADE DIFFERENTIAL BETWEEN THE | | ENCROACHING STEP, PORCH, STOOP, OR TERRACE AND ADJACENT | | PROPERTY SHALL BE STRUCTURALLY RETAINED AND POSITIVELY | | DRAINED IN A MANNER THAT WILL PREVENT ANY DRAINAGE | | DISCHARGE TO ANY PROPERTY CONTIGUOUS TO THE SIDE OR | | REAR PROPERTY LINES. | | 4. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT | | VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO | | COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION | | 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE | | SPEAK WITH RAY CARANCI ? SENIOR LANDSCAPING PLANNER - | | [email protected] TO SHOW COMPLIANCE WITH CURRENT | | LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING | | PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING | | PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR. | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | 1. THE CEILING FOR THE PORCH AND PORTE COCHERE SHALL BE | | MADE OF WOOD AND HAVE A TONGUE AND GROOVE PROFILE. | | 2. ALL WINDOW INFORMATION REFERENCED ON THIS PERMIT IS | | FOR INFORMATIONALLY PURPOSES ONLY. A SEPARATE WINDOW | | AND DOOR PERMIT EXIST. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-01-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-01-22 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-01-06 |
Time |
09:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2020-12-23 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-12-18 |
Time |
16:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-12-03 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-12-03 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-11-03 |
Time |
08:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-12-21 |
Time |
06:51 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-12-21 |
Time |
06:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-11-04 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-11-04 |
Time |
08:19 |
Sent To |
|
|
Notes |
2020-11-04 09:14:58 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20101457 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M-2; THE GOODMAN AHU-1 CFM TOTAL IS 600CFM, | | THE CFM?S AT EACH REGISTER IN THE HOUSE ADD UP TO 1,004 | | CFM. PLEASE SIZE THE AHU TO MATCH THE NEEDED CFM IN | | EACH ROOM OF THE HOUSE. FBC RES M1401.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-12-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-23 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-23 |
Time |
14:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-11-05 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-11-05 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-11-04 |
Time |
11:45 |
Sent To |
|
|
Notes |
2020-11-05 09:08:58 | 1ST REVIEW FBC-2017 RES. PLUMBING | | PERMIT- 20101457 | | 11/5/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED | | FOR GAS PIPING- SECTIONS 105.1 & 107.2.1 WPB. A REVIEW | | OF THE GAS HAS NOT BEEN PERFORMED UNDER THIS PERMIT. A | | COMPLETE GAS PLAN, RISER DRAWING, PIPE SIZING TABLES, | | AND PIPING AND APPLIANCE SPECIFICATIONS SHALL BE | | SUBMITTED FOR REVIEW. | | | | 2) SHEETS A10 & A11: PROVIDE A WATER RISER DRAWING- | | SECTION 107.3.5.3 WPB. | | | | 3) A10 & A11, 1ST FLOOR RISER: THE DOUBLE LAV SINK IN | | THE MASTER BATH REQUIRES A VENT OR THE FIXTURE DRAIN | | MUST CONNECT HORIZONTALLY TO THE WET VENT- SECTION | | P3108.1 FBC RES. | | | | 4) A11: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW | | TANKLESS WATER HEATER INDICATING MAKE AND MODEL AND | | EFFICIENCY RATING- SEE TABLE C404.2 FBC EC. | | | | 5) A11: PLEASE MODIFY NOTE #23 TO INDICATE R-3 HOT | | WATER PIPE INSULATION REQUIRED- SECTION R403.4 FBC EC. | | | | 6) A11: PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & | | P2709.2 FBC RES. | | | | 7) A11: PLEASE NOTE THAT A FL. LICENSED PLUMBING | | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR | | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE | | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF | | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY | | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION | | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB | | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR | | FURTHER INFORMATION. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-12-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-12-22 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-12-22 |
Time |
14:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-11-04 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-11-04 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-01-08 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2021-01-08 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2021-01-08 |
Time |
14:42 |
Sent To |
|
|
Notes |
2021-01-08 14:43:21 | PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITION(S): | | | | 1. THE CEILING FOR THE PORCH AND PORTE COCHERE SHALL BE | | MADE OF WOOD AND HAVE A TONGUE AND GROOVE PROFILE. | | 2. ALL WINDOW INFORMATION REFERENCED ON THIS PERMIT IS | | FOR INFORMATIONAL PURPOSES ONLY. A SEPARATE WINDOW AND | | DOOR PERMIT EXIST. | | 3. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, | | LANDSCAPING. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2020-12-23 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-12-23 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-12-23 |
Time |
14:53 |
Sent To |
|
|
Notes |
2020-12-23 14:53:24 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT | | VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO | | COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION | | 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE | | SPEAK WITH RAY CARANCI ? SENIOR LANDSCAPING PLANNER - | | [email protected] TO SHOW COMPLIANCE WITH CURRENT | | LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING | | PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING | | PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR. | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | 1. THE CEILING FOR THE PORCH AND PORTE COCHERE SHALL BE | | MADE OF WOOD AND HAVE A TONGUE AND GROOVE PROFILE. | | 2. ALL WINDOW INFORMATION REFERENCED ON THIS PERMIT IS | | FOR INFORMATIONALLY PURPOSES ONLY. A SEPARATE WINDOW | | AND DOOR PERMIT EXIST. | | 3. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, | | LANDSCAPING. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-11-23 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-11-23 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-11-23 |
Time |
14:40 |
Sent To |
|
|
Notes |
2020-11-23 14:40:13 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. NEW MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN | | FOUR FEET INTO A SETBACK. REVISE AS NEEDED. A SEPARATE | | PERMIT IS NEEDED. | | 2. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS, | | GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION, | | LANDSCAPING. PLEASE ACKNOWLEDGE THIS. | | 3. ILLUSTRATE REAR PORCH COMPLIES WITH SEC. 94-305 | | (B)(7) - STEPS AND PORCHES. STEPS, OPEN UNCOVERED | | PORCHES OR STOOPS, AND OPEN TERRACES WHICH ARE THREE | | FEET OR LESS ABOVE GRADE MAY ENCROACH INTO ANY REQUIRED | | SETBACK AREA TO A POINT NOT CLOSER THAN TWO FEET TO THE | | PROPERTY LINE. ANY GRADE DIFFERENTIAL BETWEEN THE | | ENCROACHING STEP, PORCH, STOOP, OR TERRACE AND ADJACENT | | PROPERTY SHALL BE STRUCTURALLY RETAINED AND POSITIVELY | | DRAINED IN A MANNER THAT WILL PREVENT ANY DRAINAGE | | DISCHARGE TO ANY PROPERTY CONTIGUOUS TO THE SIDE OR | | REAR PROPERTY LINES. | | 4. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT | | VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO | | COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION | | 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE | | SPEAK WITH RAY CARANCI ? SENIOR LANDSCAPING PLANNER - | | [email protected] TO SHOW COMPLIANCE WITH CURRENT | | LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING | | PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING | | PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR. | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | 1. THE CEILING FOR THE PORCH AND PORTE COCHERE SHALL BE | | MADE OF WOOD AND HAVE A TONGUE AND GROOVE PROFILE. | | 2. ALL WINDOW INFORMATION REFERENCED ON THIS PERMIT IS | | FOR INFORMATIONALLY PURPOSES ONLY. A SEPARATE WINDOW | | AND DOOR PERMIT EXIST. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|