2020-11-12 15:23:47 | 11/12/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. DOCUMENTATION SUBMITTED IN NOT DEVICE THAT IS |
| LEAD-FREE WHICH SHOULD CONTAIN NOT MORE THAN |
| 0.25-PERCENT LEAD. |
| |
| 2. THE THIS AUTO-FILL PVB ALSO REQUIRES TO HAVE A |
| REDUCED PRESSURE ZONE VACUUM BREAKER AT THE METER WHICH |
| IT UNIT HAS TO BE CERTIFIED BY THE CITY OF WEST PALM |
| BEACH UNDER THE CROSS CONNECTION PROGRAM AS THIS IS A |
| CONTAINMENT BACKFLOW DEVICE. THE PVB IS AN ISOLATION |
| DEVICE THAT CAN BE CERTIFIED BY THE PLUMBING CONTRACTOR |
| BEFORE A FINAL INSPECTION. PLEASE SUBMIT A DOCUMATATION |
| FOR THE DEVICE THAT SHOWS MANUFACTURER?S SPECIFICATIONS |
| FOR THE BACKFLOW PREVENTERS. THE MAKE, MODEL, AND SIZE |
| OF THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE |
| WORK SECTION ON THE PERMIT APPLICATION. THESE DEVICES |
| REQUIRE A DOCUMENT THAT NEEDS TO SHOW THE DEVICE IS |
| LEAD-FREE WHICH CONTAINS NOT MORE THAN 0.25-PERCENT |
| LEAD AND APPROVED DEVICES LISTED AND PUBLISHED BY THE |
| UNIVERSITY OF SOUTHERN CALIFORNIA (USC). |
| |
| 3. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND |
| FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING |
| OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL |
| HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR |
| LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF |
| DRINKING WATER PIPE AND FITTINGS. |
| |
| 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS |
| ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY |
| OF SOUTHERN CALIFORNIA (USC). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |