Plan Review Details - Permit 20101369
Plan Review Stops For Permit 20101369
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-02 Cont ID  
Sent By rmcphers Date 2021-02-02 Time 14:20 Rev Time 0.00
Received By rmcphers Date 2021-02-02 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-25 Cont ID  
Sent By rmcphers Date 2021-01-25 Time 12:39 Rev Time 0.00
Received By rmcphers Date 2021-01-25 Time 12:25 Sent To  
Notes
2021-01-25 12:38:37SFR REMODEL AND ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) TRUSS DRAWINGS NEED TO SHOW THE REQUIRED LOCATIONS
 OF THE TRUSS CONNECTORS SHOWN IN THE CONNECTOR
 SCHEDULE.
 2) PLEASE SHOW THAT THE EXISTING DOOR FROM THE GARAGE
 TO THE LIVING SPACE COMPLIES WITH FBC R302.5.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By rmcphers Date 2020-12-01 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2020-11-30 Time 14:13 Sent To  
Notes
2020-12-01 08:09:10SFR REMODEL AND ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE SMOKE AND CARBON MONOXIDE DETECTOR
 LOCATIONS THROUGHOUT THE HOUSE PER FBC R314.2.2
 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. AND FBC R315.1
 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
 2) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO
 COMPLY WITH FBC R807.1
 3) PRODUCT APPROVALS PROVIDED FOR THE WINDOWS AND DOORS
 = THE PRODUCT APPROVAL NUMBERS DO NOT MATCH THE NUMBERS
 SHOWN ON THE DRAWINGS WINDOW AND DOOR SCHEDULES -PLEASE
 REVISE THE DRAWINGS OR PROVIDE THE PRODUCT APPROVALS
 SHOWN ON THE DRAWINGS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-01 Cont ID  
Sent By fgiaquin Date 2021-02-01 Time 21:13 Rev Time 0.00
Received By fgiaquin Date 2021-02-01 Time 20:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-05 Cont ID  
Sent By fgiaquin Date 2020-12-05 Time 22:22 Rev Time 0.00
Received By fgiaquin Date 2020-12-05 Time 21:08 Sent To  
Notes
2020-12-05 22:22:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO WORKING CLEARANCE FOR SUB-PANEL "B". NEC 110.26
  
 2. NO SMOKE ALARMS SHOWN. FBC-R 314&315
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-02 Cont ID  
Sent By cpuell Date 2021-02-02 Time 13:22 Rev Time 0.00
Received By cpuell Date 2021-01-12 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-05 Cont ID  
Sent By fgiaquin Date 2020-12-05 Time 22:22 Rev Time 0.00
Received By fgiaquin Date 2020-11-17 Time 10:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By lmarchan Date 2021-02-17 Time 11:14 Rev Time 0.00
Received By lmarchan Date 2021-02-02 Time 14:35 Sent To  
Notes
2021-02-04 10:49:59RECEIPT - MU-2021-4872 - $2491.56 - PAID
2021-02-02 14:35:402/2/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By rmcphers Date 2020-12-01 Time 08:09 Rev Time 0.00
Received By rmcphers Date 2020-12-01 Time 08:09 Sent To  
Notes
2020-12-01 08:11:04PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-01-26 Cont ID  
Sent By medwards Date 2021-01-26 Time 10:22 Rev Time 0.00
Received By medwards Date 2021-01-26 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-11-21 Cont ID  
Sent By medwards Date 2020-11-21 Time 11:14 Rev Time 0.00
Received By medwards Date 2020-11-21 Time 10:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-01-26 Cont ID  
Sent By lcrespo Date 2021-01-26 Time 12:37 Rev Time 0.00
Received By lcrespo Date 2021-01-26 Time 12:37 Sent To  
Notes
2021-01-26 12:37:5701/26/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By lcrespo Date 2020-11-19 Time 16:35 Rev Time 0.00
Received By lcrespo Date 2020-11-19 Time 16:34 Sent To  
Notes
2020-11-19 16:35:0911/19/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-12-01 Cont ID  
Sent By rmcphers Date 2020-12-01 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2020-12-01 Time 08:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-25 Cont ID  
Sent By rmcphers Date 2021-01-25 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2021-01-25 Time 12:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-21 Cont ID  
Sent By medwards Date 2020-11-21 Time 11:14 Rev Time 0.00
Received By medwards Date 2020-11-21 Time 11:14 Sent To  
Notes
2020-11-21 11:15:58DESIGNERS OF DIGITALLY SUBMITTED PLANS MUST DIGITALLY
 SIGN AND SEAL THE DOCUMENTS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-02-01 Cont ID  
Sent By kalexand Date 2021-02-01 Time 23:08 Rev Time 0.00
Received By kalexand Date 2021-02-01 Time 23:08 Sent To I
Notes
2021-02-01 23:09:51AS THE TOTAL VALUE OF THE ADDITIONS EXCEEDS 50% OF THE
 IMPROVEMENT VALUE OF THE STRUCTURE, A LANDSCAPE PERMIT
 MUST BE SUBMITTED TO PLANNING AND ZONING DIVISION.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By kalexand Date 2020-11-24 Time 13:55 Rev Time 0.00
Received By kalexand Date 2020-11-24 Time 13:55 Sent To I
Notes
2020-11-24 15:04:18 
 ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 11/24
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1.PROVIDE THE TOTAL HEIGHT OF THE PROPOSED ADDITION ON
 THE ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION
 94-611, THE HEIGHT SHALL BE MEASURED AS THE VERTICAL
 DISTANCE FROM THE AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL BETWEEN
 EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
 3. AS THE TOTAL VALUE OF THE ADDITIONS EXCEEDS 50% OF
 THE IMPROVEMENT VALUE OF THE STRUCTURE A LANDSCAPE
 PERMIT MUST BE SUBMITTED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  