Plan Review Details - Permit 20101341
Plan Review Stops For Permit 20101341
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 07:55 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 07:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 15:13 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 13:08 Sent To  
Notes
2020-11-02 15:13:421ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101341
 11/2/2020
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED GAS RISER DRAWING DOES NOT APPEAR TO
 MATCH THE APPROVED GAS RISER UNDER PERMIT 13080706. THE
 APPROVED RISER SHOWS TWO 199,000 BTUH WATER HEATERS AND
 SIX 24,0000 BTUH DRYERS- TOTAL LOAD OF 542,000 BTUH AT
 154 FT. TOTAL DEVELOPED LENGTH. THE APPROVED RISER ALSO
 SHOWS A 2 IN. GALVANIZED METALLIC BRANCH PIPE TO THE
 WATER HEATERS- THE SUBMITTED RISER SHOWS A 1 IN. PIPE.
 PLEASE CORRECT THE DRAWING TO MATCH THE EXISTING-
 SECTION 402.1 FBC FG, AND SECTION 107.2.1 WPB.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 WATER HEATER HIGHLIGHTED TO SHOW THE BTUH LOAD AND THE
 GAS INPUT PRESSURE- SECTION 624.1 FBC FG. SHOW A NEW
 REGULATOR AT THE WATER HEATER IF PRESSURE IS REQUIRED
 TO BE DROPPED PER THE SPECS- SECTIONS 410.1 & 410.2 FBC
 FG.
  
 3) PLEASE CLARIFY IF THE EXISTING VENT SYSTEM IS TO BE
 RE-USED OR IF A NEW SYSTEM IS TO BE INSTALLED- SECTION
 107.2.1 WPB. NEW VENT SYSTEMS SHALL BE IN ACCORDANCE
 WITH THE MANUFACTURER'S SPECIFICATIONS, AND SECTIONS
 502.1 & 503.1 FBC FG.
  
 4) THE $700.00 VALUE ON THE GAS PERMIT APPLICATION
 APPEARS LOW. PLEASE NOTE THAT PERMIT VALUE IS BASED ON
 LABOR, MATERIAL, EQUIPMENT, APPLIANCES ETC. INCLUDING
 THE WATER HEATER- SECTION 109.3 WPB.
  
 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-11-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-12 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-11-02 Time   Rev Time 0.00
Received By cpuell Date 2020-10-30 Time 10:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 07:56 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 15:19 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 13:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 07:56 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 07:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 15:15 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 13:08 Sent To  
Notes
2020-11-02 15:16:11SIGNATURE REVIEW
 11/2/2020
  
 THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  