Plan Review Details - Permit 20101335
Plan Review Stops For Permit 20101335
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-25 Cont ID  
Sent By cpuell Date 2021-01-25 Time 14:28 Rev Time 0.00
Received By cpuell Date 2021-01-25 Time 14:28 Sent To  
Notes
2021-01-25 14:29:24REAR BUILDING IN THE BACK HAS ADDRESS OF 900 20TH ST #
 2, UPDATED ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By cpuell Date 2020-11-04 Time 11:00 Rev Time 0.00
Received By cpuell Date 2020-11-04 Time 11:00 Sent To  
Notes
2020-11-04 11:01:41PLEASE EMAIL [email protected], AN ARIAL/SITE PLAN OR
 DRAWING OF THE BLDGING TO BE DEMOLISHED.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-03-31 Cont ID  
Sent By pvalenti Date 2021-03-31 Time 09:39 Rev Time 0.00
Received By pvalenti Date 2021-03-31 Time 09:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-01-21 Cont ID  
Sent By pvalenti Date 2021-01-21 Time 11:02 Rev Time 0.00
Received By pvalenti Date 2021-01-21 Time 11:01 Sent To  
Notes
2021-01-21 11:11:45PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW DENIED:
  
 FBC B 107.2.1, THE CONTRACTOR NEEDS TO SIGN THE
 ASBESTOS ACKNOWLEDGEMENT LETTER AND RESUBMIT INTO
 PROJECT DOX.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By pvalenti Date 2020-11-04 Time 09:56 Rev Time 0.00
Received By pvalenti Date 2020-11-04 Time 07:03 Sent To  
Notes
2020-11-04 09:57:27PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW DENIED:
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-05-24 Cont ID  
Sent By pvalenti Date 2021-05-24 Time 11:48 Rev Time 0.00
Received By pvalenti Date 2021-05-24 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-04-16 Cont ID  
Sent By pvalenti Date 2021-04-16 Time 13:26 Rev Time 0.00
Received By pvalenti Date 2021-04-16 Time 13:26 Sent To  
Notes
2021-04-16 13:28:33PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 3. WATERING DOWN METHOD IS REQUIRED:
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 IF A WATER TRUCK WILL BE USED THEN YOU WILL NEED TO
 SUBMIT DETAILS INCLUDING :
 THE GALLON CAPACITY OF THE WATER TRUCK TANK,
 A STATEMENT CONFIRMING THAT POTABLE WATER WILL BE USED
 AND A STATEMENT THAT THE WATER TRUCK WILL BE ON-SITE AT
 ALL TIMES DURING WORK.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561?822?2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED, (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
 (3/31/21 STILL PENDING THE PLUMBING FINAL INSPECTION
 FOR PERMIT #21030683)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-31 Cont ID  
Sent By pvalenti Date 2021-03-31 Time 09:12 Rev Time 0.00
Received By pvalenti Date 2021-03-31 Time 09:05 Sent To  
Notes
2021-03-31 09:22:19PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
  
 3. WATERING DOWN METHOD IS REQUIRED:
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 IF A WATER TRUCK WILL BE USED THEN YOU WILL NEED TO
 SUBMIT DETAILS INCLUDING :
 THE GALLON CAPACITY OF THE WATER TRUCK TANK,
 A STATEMENT CONFIRMING THAT POTABLE WATER WILL BE USED
 AND A STATEMENT THAT THE WATER TRUCK WILL BE ON-SITE AT
 ALL TIMES DURING WORK.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561?822?2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED, (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
 (3/31/21 STILL PENDING THE PLUMBING FINAL INSPECTION
 FOR PERMIT #21030683)
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, THE IMAGE SUBMITTED
 IS NOT CLEAR. PLEASE RESUBMIT.
  
 8. FBC 107.8. PROVIDE A STORMWATER POLLUTION PREVENTION
 PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-22 Cont ID  
Sent By pvalenti Date 2021-01-22 Time 06:30 Rev Time 0.00
Received By pvalenti Date 2021-01-21 Time 11:01 Sent To  
Notes
2021-01-22 06:43:03PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
 1. OK
 2. OK
 3. WATERING DOWN METHOD IS REQUIRED:
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561?822?2183.
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED, (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
 5. EXTERMINATION LETTER ? LETTER NEEDS TO SHOW THAT
 TREATMENT INCLUDES RODENTS.
 6. COMPLETE THE DEMO DEBRIS FORM:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, THE IMAGE SUBMITTED
 IS NOT CLEAR. PLEASE RESUBMIT.
 8. FBC 107.8. PROVIDE A STORMWATER POLLUTION PREVENTION
 PLAN.
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By pvalenti Date 2020-11-04 Time 09:58 Rev Time 0.00
Received By pvalenti Date 2020-11-04 Time 07:03 Sent To  
Notes
2020-11-04 10:00:11PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
  
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS.
  
 6. COMPLETE THE DEMO DEBRIS FORM:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
  
 BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-01-20 Cont ID  
Sent By rrossano Date 2021-01-20 Time   Rev Time 0.00
Received By rrossano Date 2021-01-20 Time   Sent To  
Notes
2021-01-20 08:55:20PASSED WITH PROVISOS:
  
 1. ADDRESS ANY OUTSTANDING COMMENTS FROM OTHER
 DISCIPLINES REVIEWS.
  
 2. PLEASE MAINTAIN POLLUTION CONTROL PLAN ONSITE
 SHOWING:
  
 A) WHERE SILT SCREENS WILL BE INSTALLED, INCLUDING A
 DETAIL SHOWING THE SILT FENCE INSTALLATION. THESE BMPS
 ARE TO BE USED AS PER THE FDEP EROSION AND SEDIMENT
 CONTROL MANUAL.
 B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS.
 C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS.
 D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON
 THE CATCH BASINS.
 E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS.
 F) SHOW HOW DUST CONTROL WILL BE PROVIDED.
  
 HTTP://WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/DOCS/
 CONST_ACTIVITY.PDF
  
 HTTP://WWW.PBCO-NPDES.ORG/CONSTRUN.ASP?MENU=SWMPMENU
  
 3. THERE ARE WATER AND SEWER LINES IN THE VICINITY OF
 THIS PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE
 STATUTES, YOU MUST CALL 811 FOR UTILITY LOCATES AT
 LEAST TWO FULL BUSINESS DAYS IN ADVANCE OF ANY
 CONSTRUCTION OR DEMOLITION WORK. INFORMATION CAN BE
 FOUND HERE: HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By rrossano Date 2020-11-05 Time   Rev Time  
Received By rrossano Date 2020-11-05 Time   Sent To  
Notes
2020-11-05 07:47:34PLEASE ADDRESS BUILDING COMMENTS.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-11-04 Cont ID  
Sent By aborngra Date 2020-11-04 Time 10:26 Rev Time 0.00
Received By aborngra Date 2020-11-04 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-24 Cont ID  
Sent By pvalenti Date 2021-05-24 Time 11:48 Rev Time 0.00
Received By pvalenti Date 2021-05-21 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-31 Cont ID  
Sent By pvalenti Date 2021-03-31 Time 09:39 Rev Time 0.00
Received By pvalenti Date 2021-03-29 Time 15:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-25 Cont ID  
Sent By cpuell Date 2021-01-25 Time 14:29 Rev Time 0.00
Received By cpuell Date 2021-01-13 Time 07:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By ccarvaja Date 2020-11-19 Time 13:54 Rev Time 0.00
Received By ccarvaja Date 2020-10-29 Time 09:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-11-04 Cont ID  
Sent By pvalenti Date 2020-11-04 Time 09:58 Rev Time 0.00
Received By pvalenti Date 2020-11-04 Time 07:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By jroach Date 2020-11-19 Time 11:50 Rev Time 0.00
Received By jroach Date 2020-11-19 Time 11:50 Sent To  
Notes
2020-11-19 11:51:00ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 11.19.2020
 PERMIT NO.: 20101335
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE DEMOLITION IS APPROVED FOR THE REAR STRUCTURE
 ONLY?AND WITH THE CONDITION THAT THE SINGLE FAMILY
 RESIDENCE AT THE FRONT OF THE PROPERTY SHALL REMAIN.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  