Plan Review Details - Permit 20101304
Plan Review Stops For Permit 20101304
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 11:08 Rev Time 0.00
Received By lcrespo Date 2020-11-03 Time 07:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-02 Cont ID  
Sent By lcrespo Date 2020-11-02 Time 09:16 Rev Time 0.00
Received By lcrespo Date 2020-10-30 Time 17:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By lcrespo Date 2020-10-29 Time 09:23 Rev Time 0.00
Received By lcrespo Date 2020-10-29 Time 09:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 11:08 Rev Time 0.00
Received By lcrespo Date 2020-11-03 Time 11:08 Sent To  
Notes
2020-11-03 11:08:1611/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-11-02 Cont ID  
Sent By lcrespo Date 2020-11-02 Time 09:16 Rev Time 0.00
Received By lcrespo Date 2020-11-02 Time 09:16 Sent To  
Notes
2020-11-02 09:16:5511/02/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BACKFLOW DEVICE (PVB) SUBMITTED CAN NOT BE USED
 FOR THE REPLACEMENT OF A REDUCED PRINCIPAL ZONE
 BACKFLOW DEVICE. THIS PROPERTY IS A COMMERCIAL PROPERTY
 AND THE DEGREE OF HAZARD REQUIRES A DEVICE RPZ WHICH IS
 SET BY THE CITY OF WEST PALM BEACH UTILITIES DEPARTMENT
 AND THE CROSS CONNECTION PROGRAM. PLEASE SUMBMIT
 SPECIFICATIONS OF AN RPZ DEVICE THAT COMPLIES WITH THE
 FOLWING;
  
 2. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE
 WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD.
  
 3. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By lcrespo Date 2020-10-29 Time 09:23 Rev Time 0.00
Received By lcrespo Date 2020-10-29 Time 09:23 Sent To  
Notes
2020-10-29 09:27:5010/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUPPLY THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE
 WORK SECTION ON THE PERMIT APPLICATION.
  
 2. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE
 WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD.
  
 3. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND
 FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING
 OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL
 HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR
 LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF
 DRINKING WATER PIPE AND FITTINGS.
  
 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC).
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  