Plan Review Details - Permit 20101304
Plan Review Stops For Permit 20101304 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-11-03 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-11-03 |
Time |
07:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-11-02 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-11-02 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-10-30 |
Time |
17:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-10-29 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-10-29 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-10-29 |
Time |
09:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-11-03 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-11-03 |
Time |
11:08 |
Sent To |
|
|
Notes |
2020-11-03 11:08:16 | 11/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2020-11-02 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-11-02 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-11-02 |
Time |
09:16 |
Sent To |
|
|
Notes |
2020-11-02 09:16:55 | 11/02/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THIS BACKFLOW DEVICE (PVB) SUBMITTED CAN NOT BE USED | | FOR THE REPLACEMENT OF A REDUCED PRINCIPAL ZONE | | BACKFLOW DEVICE. THIS PROPERTY IS A COMMERCIAL PROPERTY | | AND THE DEGREE OF HAZARD REQUIRES A DEVICE RPZ WHICH IS | | SET BY THE CITY OF WEST PALM BEACH UTILITIES DEPARTMENT | | AND THE CROSS CONNECTION PROGRAM. PLEASE SUMBMIT | | SPECIFICATIONS OF AN RPZ DEVICE THAT COMPLIES WITH THE | | FOLWING; | | | | 2. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE | | WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD. | | | | 3. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS | | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY | | OF SOUTHERN CALIFORNIA (USC). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-10-29 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-10-29 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-10-29 |
Time |
09:23 |
Sent To |
|
|
Notes |
2020-10-29 09:27:50 | 10/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE SUPPLY THE MANUFACTURER?S SPECIFICATIONS FOR | | THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF | | THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE | | WORK SECTION ON THE PERMIT APPLICATION. | | | | 2. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE | | WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD. | | | | 3. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND | | FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING | | OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL | | HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR | | LESS PER THE 2017 FBC SEC. P 605.2.1 LEAD CONTENT OF | | DRINKING WATER PIPE AND FITTINGS. | | | | 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS | | ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY | | OF SOUTHERN CALIFORNIA (USC). | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
|