Plan Review Stops For Permit 20101267 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-03-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-22 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-22 |
Time |
11:56 |
Sent To |
|
|
Notes |
2021-03-22 12:06:59 | COOLER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | 3RD REVIEW | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) EXTERIOR COOLER IS SUBJECT TO WIND LOADS- PROVIDE | | SIGNED AND SEALED DRAWINGS FROM AN ARCHITECT OR | | ENGINEER FOR THE COOLER, COOLER FOUNDATION AND COOLER | | TIEDOWNS OR PROVIDE A MIAMI DADE OR FLORIDA STATE | | PRODUCT APPROVAL. FBC 1609 | | 2) DRAWINGS NEED TO SHOW THE WIND DESIGN DATA USED FOR | | DESIGN FBC 1603.1.4 | | 3) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS | | BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE | | 2017 FBC. | | 4) SEE NOTE NUMBER 5 ON THE PROVIDED PRODUCT APPROVAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-12-07 |
Time |
13:06 |
Sent To |
|
|
Notes |
2020-12-07 13:07:30 | COOLER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | 2ND REVIEW | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEED MORE INFORMATION FOR A COMPLETE REVIEW - | | OUTSIDE COOLER = NEED A SITE PLAN/SURVEY SHOWING | | EASEMENTS, WATER DRAINAGE/ RETENTION ON PROPERTY, | | COOLER LOCATION AND SETBACKS FROM PROPERTY LINES AND | | EXISTING BUILDINGS. EXTERIOR COOLER IS SUBJECT TO WIND | | LOADS- PROVIDE STRUCTURAL CALCULATIONS OR SIGNED AND | | SEALED DRAWINGS FROM AN ARCHITECT OR ENGINEER FOR THE | | COOLER, COOLER FOUNDATION AND COOLER TIEDOWNS OR | | PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL. | | FBC 1609 | | INSIDE COOLER = NEED A LIFE SAFETY PLAN - SHOWING | | LOCATION AND BUILDING MEANS OF EGRESS, BLDG | | CONSTRUCTION TYPE FBC CHAPTER 6, OCCUPANCY | | CLASSIFICATION FBC CHAPTER 10 ETC. | | 2) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS | | BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE | | 2017 FBC. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-04 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-04 |
Time |
11:26 |
Sent To |
|
|
Notes |
2020-11-04 12:26:40 | COOLER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) NEED MORE INFORMATION FOR A COMPLETE REVIEW - | | OUTSIDE COOLER = NEED A SITE PLAN/SURVEY SHOWING | | EASEMENTS, WATER DRAINAGE/ RETENTION ON PROPERTY, | | COOLER LOCATION AND SETBACKS FROM PROPERTY LINES AND | | EXISTING BUILDINGS. EXTERIOR COOLER IS SUBJECT TO WIND | | LOADS- PROVIDE STRUCTURAL CALCULATIONS OR SIGNED AND | | SEALED DRAWINGS FROM AN ARCHITECT OR ENGINEER FOR THE | | COOLER, COOLER FOUNDATION AND COOLER TIEDOWNS OR | | PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL. | | FBC 1609 | | INSIDE COOLER = NEED A LIFE SAFETY PLAN - SHOWING | | LOCATION AND BUILDING MEANS OF EGRESS, BLDG | | CONSTRUCTION TYPE FBC CHAPTER 6, OCCUPANCY | | CLASSIFICATION FBC CHAPTER 10 ETC. | | 2) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS | | BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE | | 2017 FBC. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-10-28 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-10-28 |
Time |
09:07 |
Sent To |
|
|
Notes |
2020-10-28 09:29:06 | ELECTRICAL SUB PERMIT AND ELECTRICAL REVIEW WILL BE | | REQUIRED. EQ |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2021-03-12 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-03-12 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-03-12 |
Time |
13:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2020-12-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-12-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-12-03 |
Time |
16:07 |
Sent To |
|
|
Notes |
2020-12-03 16:17:14 | PREVIOUS FIRE COMMENTS HAVE NOT BEEN ADDRESSED. | | | | PLEASE PROVIDE RESPONSE TO EACH OF THE FAILED COMMENTS. | | | | THE PREVIOUS COMENTS ARE POSTED BELOW: | | | | SOME OF THESE ITEMS MAY BE EXISTING BUT ARE NOT | | INDICATED, PLEASE INDICATE OR CORRECT. | | | | | | 1) I AM CONFUSED OF WHAT THE PROPOSED PROJECT IS OR | | CONSIST OF. | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK | | | | | | | | 1A) WHAT DOES SHEET 2 OF 4 INDICATE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 1B) WHAT DOES SHEET 3 OF 4 INDICATE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 1C) PLEASE PROVIDE A DETAILED SITE PLAN THAT MAY ASSIST | | WITH THE ABOVE QUESTIONS. | | | | | | | | 2) SHEET 2 OF 4 APPEARS TO INDICATE A NEW DOOR. IS THIS | | CORRECT? | | | | PLEASE PROVIDE THE DOOR HANDLE INFO SHOWING THAT A | | PERSON CAN'T BE LOCKED INSIDE. | | | | | | | | 3) THERE IS NO INDICATION OF AN EXIT SIGN IF # 2 | | CREATES A NEW ROOM. | | | | PLEASE PROVIDE DETAILS. | | | | | | 4) THERE IS NOT INCIATION OF LIGHTING OR EMERGENCY | | LIGHTING SHOULD THE ROOM GO DARK. | | | | THE EXIT SIGN OF AN EMERGENCY LIGHT MAY NEED TO BE | | INSTALLED IF NOT CONNECTED TO EMERGENCY POWER. | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-11-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-11-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-11-06 |
Time |
14:15 |
Sent To |
|
|
Notes |
2020-11-06 14:34:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | SOME OF THESE ITEMS MAY BE EXISTING BUT ARE NOT | | INDICATED, PLEASE INDICATE OR CORRECT. | | | | | | 1) I AM CONFUSED OF WHAT THE PROPOSED PROJECT IS OR | | CONSIST OF. | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK | | | | | | | | 1A) WHAT DOES SHEET 2 OF 4 INDICATE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 1B) WHAT DOES SHEET 3 OF 4 INDICATE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 1C) PLEASE PROVIDE A DETAILED SITE PLAN THAT MAY ASSIST | | WITH THE ABOVE QUESTIONS. | | | | | | | | 2) SHEET 2 OF 4 APPEARS TO INDICATE A NEW DOOR. IS THIS | | CORRECT? | | | | PLEASE PROVIDE THE DOOR HANDLE INFO SHOWING THAT A | | PERSON CAN'T BE LOCKED INSIDE. | | | | | | | | 3) THERE IS NO INDICATION OF AN EXIT SIGN IF # 2 | | CREATES A NEW ROOM. | | | | PLEASE PROVIDE DETAILS. | | | | | | 4) THERE IS NOT INCIATION OF LIGHTING OR EMERGENCY | | LIGHTING SHOULD THE ROOM GO DARK. | | | | THE EXIT SIGN OF AN EMERGENCY LIGHT MAY NEED TO BE | | INSTALLED IF NOT CONNECTED TO EMERGENCY POWER. | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-03-30 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-03-30 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-03-11 |
Time |
13:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-12-15 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-12-15 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-12-01 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-11-23 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-11-23 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-10-27 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-15 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-15 |
Time |
09:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2020-12-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-12-04 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-12-04 |
Time |
08:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-11-03 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-11-03 |
Time |
07:48 |
Sent To |
|
|
Notes |
2020-11-03 07:56:40 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20101267 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE SPECIFICATIONS FOR THE REFRIGERATION | | UNITS USED FOR THIS PROJECT. I SEE THAT THE EXISTING | | COOLER IS BEING ENLARGED, PLEASE SHOW THAT THE EXISTING | | REFRIGERATION FOR THIS UNIT WILL BE SUFFICIENT FOR THE | | LARGER SPACE. FBC M 1102 | | | | 2) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THIS | | ADDITION ON THE PROPERTY. FBC 107.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2021-03-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-03-22 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-22 |
Time |
12:07 |
Sent To |
|
|
Notes |
2021-03-22 12:07:42 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-12-07 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-12-07 |
Time |
13:07 |
Sent To |
|
|
Notes |
2020-12-07 13:08:19 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-11-04 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-11-04 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-11-04 |
Time |
12:26 |
Sent To |
|
|
Notes |
2020-11-04 12:27:28 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-03-30 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2021-03-30 |
Time |
15:04 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2021-03-30 |
Time |
14:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2020-12-15 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2020-12-15 |
Time |
10:39 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2020-12-15 |
Time |
10:37 |
Sent To |
|
|
Notes |
2020-12-15 10:40:06 | FAILED | | | | 1) REPEAT COMMENT: PROVIDE A SURVEY SHOWING THE | | LOCATION OF THE PROPOSED COOLER EXPANSION. | | | | 2) REPEAT COMMENT: PROVIDE ELEVATION DRAWINGS OF THE | | PROPOSED COOLER EXPANSION. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-11-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2020-11-23 |
Time |
09:35 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2020-11-23 |
Time |
09:35 |
Sent To |
|
|
Notes |
2020-11-23 09:37:07 | FAILED | | | | 1) PROVIDE A SURVEY SHOWING THE LOCATION OF THE | | PROPOSED COOLER EXPANSION. | | | | 2) PROVIDE ELEVATION DRAWINGS OF THE PROPOSED COOLER | | EXPANSION. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|
|