Plan Review Details - Permit 20101267
Plan Review Stops For Permit 20101267
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-22 Cont ID  
Sent By rmcphers Date 2021-03-22 Time 12:07 Rev Time 0.00
Received By rmcphers Date 2021-03-22 Time 11:56 Sent To  
Notes
2021-03-22 12:06:59COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 3RD REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) EXTERIOR COOLER IS SUBJECT TO WIND LOADS- PROVIDE
 SIGNED AND SEALED DRAWINGS FROM AN ARCHITECT OR
 ENGINEER FOR THE COOLER, COOLER FOUNDATION AND COOLER
 TIEDOWNS OR PROVIDE A MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL. FBC 1609
 2) DRAWINGS NEED TO SHOW THE WIND DESIGN DATA USED FOR
 DESIGN FBC 1603.1.4
 3) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS
 BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE
 2017 FBC.
 4) SEE NOTE NUMBER 5 ON THE PROVIDED PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-07 Cont ID  
Sent By rmcphers Date 2020-12-07 Time 13:06 Rev Time 0.00
Received By rmcphers Date 2020-12-07 Time 13:06 Sent To  
Notes
2020-12-07 13:07:30COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEED MORE INFORMATION FOR A COMPLETE REVIEW -
 OUTSIDE COOLER = NEED A SITE PLAN/SURVEY SHOWING
 EASEMENTS, WATER DRAINAGE/ RETENTION ON PROPERTY,
 COOLER LOCATION AND SETBACKS FROM PROPERTY LINES AND
 EXISTING BUILDINGS. EXTERIOR COOLER IS SUBJECT TO WIND
 LOADS- PROVIDE STRUCTURAL CALCULATIONS OR SIGNED AND
 SEALED DRAWINGS FROM AN ARCHITECT OR ENGINEER FOR THE
 COOLER, COOLER FOUNDATION AND COOLER TIEDOWNS OR
 PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL.
 FBC 1609
 INSIDE COOLER = NEED A LIFE SAFETY PLAN - SHOWING
 LOCATION AND BUILDING MEANS OF EGRESS, BLDG
 CONSTRUCTION TYPE FBC CHAPTER 6, OCCUPANCY
 CLASSIFICATION FBC CHAPTER 10 ETC.
 2) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS
 BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE
 2017 FBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By rmcphers Date 2020-11-04 Time 12:26 Rev Time 0.00
Received By rmcphers Date 2020-11-04 Time 11:26 Sent To  
Notes
2020-11-04 12:26:40COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEED MORE INFORMATION FOR A COMPLETE REVIEW -
 OUTSIDE COOLER = NEED A SITE PLAN/SURVEY SHOWING
 EASEMENTS, WATER DRAINAGE/ RETENTION ON PROPERTY,
 COOLER LOCATION AND SETBACKS FROM PROPERTY LINES AND
 EXISTING BUILDINGS. EXTERIOR COOLER IS SUBJECT TO WIND
 LOADS- PROVIDE STRUCTURAL CALCULATIONS OR SIGNED AND
 SEALED DRAWINGS FROM AN ARCHITECT OR ENGINEER FOR THE
 COOLER, COOLER FOUNDATION AND COOLER TIEDOWNS OR
 PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL.
 FBC 1609
 INSIDE COOLER = NEED A LIFE SAFETY PLAN - SHOWING
 LOCATION AND BUILDING MEANS OF EGRESS, BLDG
 CONSTRUCTION TYPE FBC CHAPTER 6, OCCUPANCY
 CLASSIFICATION FBC CHAPTER 10 ETC.
 2) FLORIDA PRODUCT APPROVAL PROVIDED HAS EXPIRED AND IS
 BASED ON THE 2004 FBC - WILL NEED TO BE BASED ON THE
 2017 FBC.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2020-10-28 Cont ID  
Sent By equinone Date 2020-10-28 Time 09:21 Rev Time 0.00
Received By equinone Date 2020-10-28 Time 09:07 Sent To  
Notes
2020-10-28 09:29:06ELECTRICAL SUB PERMIT AND ELECTRICAL REVIEW WILL BE
 REQUIRED. EQ

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-03-12 Cont ID  
Sent By pleduc Date 2021-03-12 Time   Rev Time 0.00
Received By pleduc Date 2021-03-12 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-12-03 Cont ID  
Sent By pleduc Date 2020-12-03 Time   Rev Time 0.00
Received By pleduc Date 2020-12-03 Time 16:07 Sent To  
Notes
2020-12-03 16:17:14PREVIOUS FIRE COMMENTS HAVE NOT BEEN ADDRESSED.
  
 PLEASE PROVIDE RESPONSE TO EACH OF THE FAILED COMMENTS.
  
 THE PREVIOUS COMENTS ARE POSTED BELOW:
  
 SOME OF THESE ITEMS MAY BE EXISTING BUT ARE NOT
 INDICATED, PLEASE INDICATE OR CORRECT.
  
  
 1) I AM CONFUSED OF WHAT THE PROPOSED PROJECT IS OR
 CONSIST OF.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK
  
  
  
 1A) WHAT DOES SHEET 2 OF 4 INDICATE?
  
 PLEASE PROVIDE DETAILS
  
  
  
 1B) WHAT DOES SHEET 3 OF 4 INDICATE?
  
 PLEASE PROVIDE DETAILS
  
  
  
 1C) PLEASE PROVIDE A DETAILED SITE PLAN THAT MAY ASSIST
 WITH THE ABOVE QUESTIONS.
  
  
  
 2) SHEET 2 OF 4 APPEARS TO INDICATE A NEW DOOR. IS THIS
 CORRECT?
  
 PLEASE PROVIDE THE DOOR HANDLE INFO SHOWING THAT A
 PERSON CAN'T BE LOCKED INSIDE.
  
  
  
 3) THERE IS NO INDICATION OF AN EXIT SIGN IF # 2
 CREATES A NEW ROOM.
  
 PLEASE PROVIDE DETAILS.
  
  
 4) THERE IS NOT INCIATION OF LIGHTING OR EMERGENCY
 LIGHTING SHOULD THE ROOM GO DARK.
  
 THE EXIT SIGN OF AN EMERGENCY LIGHT MAY NEED TO BE
 INSTALLED IF NOT CONNECTED TO EMERGENCY POWER.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-06 Cont ID  
Sent By pleduc Date 2020-11-06 Time   Rev Time 0.00
Received By pleduc Date 2020-11-06 Time 14:15 Sent To  
Notes
2020-11-06 14:34:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SOME OF THESE ITEMS MAY BE EXISTING BUT ARE NOT
 INDICATED, PLEASE INDICATE OR CORRECT.
  
  
 1) I AM CONFUSED OF WHAT THE PROPOSED PROJECT IS OR
 CONSIST OF.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK
  
  
  
 1A) WHAT DOES SHEET 2 OF 4 INDICATE?
  
 PLEASE PROVIDE DETAILS
  
  
  
 1B) WHAT DOES SHEET 3 OF 4 INDICATE?
  
 PLEASE PROVIDE DETAILS
  
  
  
 1C) PLEASE PROVIDE A DETAILED SITE PLAN THAT MAY ASSIST
 WITH THE ABOVE QUESTIONS.
  
  
  
 2) SHEET 2 OF 4 APPEARS TO INDICATE A NEW DOOR. IS THIS
 CORRECT?
  
 PLEASE PROVIDE THE DOOR HANDLE INFO SHOWING THAT A
 PERSON CAN'T BE LOCKED INSIDE.
  
  
  
 3) THERE IS NO INDICATION OF AN EXIT SIGN IF # 2
 CREATES A NEW ROOM.
  
 PLEASE PROVIDE DETAILS.
  
  
 4) THERE IS NOT INCIATION OF LIGHTING OR EMERGENCY
 LIGHTING SHOULD THE ROOM GO DARK.
  
 THE EXIT SIGN OF AN EMERGENCY LIGHT MAY NEED TO BE
 INSTALLED IF NOT CONNECTED TO EMERGENCY POWER.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-30 Cont ID  
Sent By lmarchan Date 2021-03-30 Time 16:59 Rev Time 0.00
Received By lmarchan Date 2021-03-11 Time 13:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-15 Cont ID  
Sent By lmarchan Date 2020-12-15 Time 14:04 Rev Time 0.00
Received By lmarchan Date 2020-12-01 Time 10:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-23 Cont ID  
Sent By lmarchan Date 2020-11-23 Time 09:57 Rev Time 0.00
Received By lmarchan Date 2020-10-27 Time 08:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-15 Cont ID  
Sent By medwards Date 2021-03-15 Time 09:48 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By medwards Date 2020-12-04 Time 09:02 Rev Time 0.00
Received By medwards Date 2020-12-04 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By medwards Date 2020-11-03 Time 07:56 Rev Time 0.00
Received By medwards Date 2020-11-03 Time 07:48 Sent To  
Notes
2020-11-03 07:56:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20101267
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE REFRIGERATION
 UNITS USED FOR THIS PROJECT. I SEE THAT THE EXISTING
 COOLER IS BEING ENLARGED, PLEASE SHOW THAT THE EXISTING
 REFRIGERATION FOR THIS UNIT WILL BE SUFFICIENT FOR THE
 LARGER SPACE. FBC M 1102
  
 2) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THIS
 ADDITION ON THE PROPERTY. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-03-22 Cont ID  
Sent By rmcphers Date 2021-03-22 Time 12:07 Rev Time 0.00
Received By rmcphers Date 2021-03-22 Time 12:07 Sent To  
Notes
2021-03-22 12:07:42SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-07 Cont ID  
Sent By rmcphers Date 2020-12-07 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2020-12-07 Time 13:07 Sent To  
Notes
2020-12-07 13:08:19SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By rmcphers Date 2020-11-04 Time 12:26 Rev Time 0.00
Received By rmcphers Date 2020-11-04 Time 12:26 Sent To  
Notes
2020-11-04 12:27:28SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2021-03-30 Cont ID  
Sent By eschneid Date 2021-03-30 Time 15:04 Rev Time 0.25
Received By eschneid Date 2021-03-30 Time 14:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-12-15 Cont ID  
Sent By eschneid Date 2020-12-15 Time 10:39 Rev Time 0.25
Received By eschneid Date 2020-12-15 Time 10:37 Sent To  
Notes
2020-12-15 10:40:06FAILED
  
 1) REPEAT COMMENT: PROVIDE A SURVEY SHOWING THE
 LOCATION OF THE PROPOSED COOLER EXPANSION.
  
 2) REPEAT COMMENT: PROVIDE ELEVATION DRAWINGS OF THE
 PROPOSED COOLER EXPANSION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-23 Cont ID  
Sent By eschneid Date 2020-11-23 Time 09:35 Rev Time 0.25
Received By eschneid Date 2020-11-23 Time 09:35 Sent To  
Notes
2020-11-23 09:37:07FAILED
  
 1) PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 PROPOSED COOLER EXPANSION.
  
 2) PROVIDE ELEVATION DRAWINGS OF THE PROPOSED COOLER
 EXPANSION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]