Plan Review Details - Permit 20101251
Plan Review Stops For Permit 20101251
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-11-17 Cont ID  
Sent By pvalenti Date 2020-11-17 Time 10:58 Rev Time 0.00
Received By pvalenti Date 2020-11-17 Time 10:55 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By rmcdouga Date 2020-10-28 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2020-10-28 Time 11:34 Sent To  
Notes
2020-10-28 11:35:22PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-17 Cont ID  
Sent By pvalenti Date 2020-11-17 Time 10:58 Rev Time 0.00
Received By pvalenti Date 2020-11-17 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By rmcdouga Date 2020-10-28 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2020-10-28 Time 11:33 Sent To  
Notes
2020-10-28 11:34:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A COPY OF THE CONTRACT WITH THE SCOPE OF WORK
 SPECIFIED. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) THE DRYWALL THAT IS BEING REPLACED ON THE CORRIDOR
 WALLS, TENANT SEPARATION WALLS AND CEILINGS ARE PART OF
 FIRE RATED ASSEMBLIES. PROVIDE SIGNED AND SEALED
 DRAWINGS AND DETAILS FROM A FLORIDA LICENSED DESIGN
 PROFESSIONAL. PROVIDE WALL AND CEILING SECTIONS WITH
 THE LISTING DETAILS FOR THE FIRE RATED ASSEMBLY. FBC
 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By pleduc Date 2020-11-16 Time   Rev Time 0.00
Received By pleduc Date 2020-11-16 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-04 Cont ID  
Sent By pleduc Date 2020-11-04 Time   Rev Time 0.00
Received By pleduc Date 2020-11-04 Time 13:13 Sent To  
Notes
2020-11-04 13:13:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE EXISTING FIRE RATED WALLS THAT ARE BEING
 REPLACED, HOWEVER, THERE ARE NO INDICATIONS OF A LISTED
 RATED WALL CALL-OUT TO ENSURE PROPER CONSTRUCTION.
  
 PER NFPA 1 CH 8
  
 8.3.1.3 WALLS USED AS FIRE BARRIERS SHALL COMPLY WITH
 CHAPTER 7 OF
 NFPA 221, STANDARD FOR HIGH CHALLENGE FIRE WALLS, FIRE
 WALLS, AND
 FIRE BARRIER WALLS. THE NFPA 221 LIMITATION ON
 PERCENTAGE WIDTH OF
 OPENINGS SHALL NOT APPLY.
  
 8.3.2 WALLS.
 8.3.2.1 THE FIRE-RESISTIVE MATERIALS, ASSEMBLIES, AND
 SYSTEMS USED SHALL
 BE LIMITED TO THOSE PERMITTED IN THIS CODE AND THIS
 CHAPTER.
  
 8.3.2.2 THE CONSTRUCTION MATERIALS AND DETAILS FOR
 FIRE-RESISTIVE
 ASSEMBLIES AND SYSTEMS FOR WALLS DESCRIBED SHALL COMPLY
 WITH ALL
 OTHER PROVISIONS OF THIS CODE, EXCEPT AS MODIFIED
 HEREIN.
  
 NFPA 221
  
 4.3 FIRE RESISTANCE RATINGS
 4.3.1 THE FIRE RESISTANCE RATING OF ASSEMBLIES SHALL BE
 DETERMINED
 IN ACCORDANCE, ASTM E 119, STANDARD TEST METHODS FOR
 FIRE
 TESTS OF BUILDING CONSTRUCTION AND MATERIALS, OR
 ANSI/UL 263, STANDARD
 FOR FIRE TESTS OF BUILDING CONSTRUCTION AND MATERIALS,
 OR OTHER
 APPROVED TEST METHODS OR ANALYTICAL METHODS IN
 ACCORDANCE WITH
 4.3.2.
  
 PLEASE PROVIDE A DETAILED LISTED FIRE RATED WALL
 CALL-OUT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-17 Cont ID  
Sent By pvalenti Date 2020-11-17 Time 10:58 Rev Time 0.00
Received By pvalenti Date 2020-11-10 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-05 Cont ID  
Sent By ccarvaja Date 2020-11-04 Time 09:15 Rev Time 0.00
Received By ccarvaja Date 2020-10-28 Time 08:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-17 Cont ID  
Sent By pvalenti Date 2020-11-17 Time 10:58 Rev Time 0.00
Received By pvalenti Date 2020-11-17 Time 10:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By rmcdouga Date 2020-10-28 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2020-10-28 Time 11:35 Sent To  
Notes
2020-10-28 11:36:09ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE PAPER VERSION OF DRAWINGS WITH
 THE ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  
  