Plan Review Details - Permit 20101212
Plan Review Stops For Permit 20101212
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jgomez Date 2020-11-19 Time 11:18 Rev Time 0.00
Received By jgomez Date 2020-11-18 Time 16:25 Sent To  
Notes
2020-11-12 18:21:28RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ADDITION NEEDS TO COMPLY WITH SEC. 507 AND SEC.
 1101.1 FBC-EXISTING BUILDING.
  
 1-THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH THE BASE FLOOD ELEVATION (BFE) OF 6
 FEET BASED ON NAVD 88. DURING THE PERMITTING OF THIS
 STRUCTURE THREE DIFFERENT FLOOD ELEVATION CERTIFICATES
 WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 NOTE: NEED TO PROVIDE THE CONSTRUCTION DRAWINGS
 ELEVATION CERTIFICATE NOW FOR REVIEW.
  
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 SEC. 107.3.5.1.1 CITY AMENDMENTS.
  
  
 2- THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THEREFORE, THE ADDITION AND THE EXISTING
 HOUSE NEED TO COMPLY WITH THE CITY TECHNICAL AMENDMENTS
 FOR STRUCTURES LOCATED IN A FLOOD ZONE AE.
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET OR
 THE DESIGN FLOOD ELEVATION
 THIS HOUSE IS LOCATED IN AE FLOOD ZONE WITH THE BASE
 FLOOD ELEVATION OF 6 FEET BASED ON NAVD 88. THEREFORE,
 THE FINAL FINISH FLOOR ELEVATION NEEDS TO BE AT LEAST
 AT 8 FEET. CONSTRUCTION DRAWINGS AND ELEVATION
 CERTIFICATE ARE REQUIRED TO SHOW THE PROPOSED FINISH
 FLOOR ELEVATION.
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 SEC. 107.3.5.1.1 CITY AMENDMENTS.
  
 SUBSTANTIAL IMPROVEMENT:
 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIR, RECONSTRUCTION, REHABILITATION, ALTERATION,
 ADDITION, OR OTHER IMPROVEMENT OF A BUILDING OR
 STRUCTURE, FOR WHICH THE CUMULATIVE COST IN ANY FIVE
 YEAR PERIOD EQUALS OR EXCEEDS 50 PERCENT OF THE MARKET
 VALUE OF THE BUILDING OR STRUCTURE AT THE END OF THE
 FIVE YEAR PERIOD AND BEFORE THE IMPROVEMENT OR REPAIR
 IS STARTED. IF THE STRUCTURE HAS INCURRED "SUBSTANTIAL
 DAMAGE," ANY REPAIRS ARE CONSIDERED SUBSTANTIAL
 IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR WORK
 PERFORMED.
  
 3-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 4-PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. 1101.1
 FBC-EXISTING BUILDING AND SEC. R401.4 FBC-RESIDENTIAL.
  
 5- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR DOORS.
 B)WINDOWS.
 C)ROOFING FINISH.
 (NOTE: NO SURE IF SHINGLES, TILE OR FLAT ROOF. PLANS
 ARE NOT CLEAR).
 D)SHUTTERS IF DOOR AND WINDOWS DON'T HAVE IMPACT
 GLAZING. AND, NEED SHUTTERS COMPLETE INSTALLATION
 SCHEDULE.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- SHEET A.3:
 A)WINDOW TYPE MARK "A" NEED TO BE SAFETY GLASS AS
 REQUIRED BY SEC. R308.4.3 FBC-RESIDENTIAL. SPECIFY ON
 PLANS.
  
 B)DOOR AND WINDOW SCHEDULES DON'T SPECIFY IF GLAZING IS
 IMPACT OR NOT. NEED TO SPECIFY HOW COMPLYING WITH THE
 PROTECTION OF OPENINGS (IMPACT GLAZING OR SHUTTERS)AS
 REQUIRED BY SEC. R301.2.1.2 FBC-RESIDENTIAL.
  
 C)DOOR AND WINDOW SCHEDULES ARE INCOMPLETE. SPECIFY THE
 CALCULATED DESIGN PRESSURES. SEC. R301.2.1
 FBC-RESIDENTIAL. (NOTE: CLEARLY SPECIFY IF NOMINAL OR
 ULTIMATE DESIGN PRESSURES).
  
 D)PROVIDE SPECIFICATIONS FOR THE DOOR LEADING FROM THE
 GARAGE TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL.
  
 9- REVISE DESIGN CRITERIA AND LOADS INFORMATION ON
 SHEET S-1:
 A)MEAN ROOF HEIGHT IS INCORRECT. 9'-0" IS THE TOP OF
 THE NEW BEAM NOT THE MEAN ROOF HEIGHT. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)IT IS NOT CLEAR IF THE ROOF IS DESIGNED AS FLAT OR
 PITCHED. SCOPE OF WORK ON SHEET A.1 SPECIFIES "NEW
 SLOPED ROOF". ROOF PLAN ON SHEET A.4 SPECIFIES "NEW
 SLOPED ROOF". ROOF FRAMING PLAN, ELEVATIONS AND
 SECTIONS SUGGEST PITCHED ROOF (2:12 PITCH), WHILE
 DESIGN CRITERIA SPECIFY "ORDINARY FLAT ROOF". ALSO, IS
 NOT CLEAR WHAT IS THE ROOFING FINISH. IS IT FLAT ROOF
 ASSEMBLY OR SHINGLES OR ROOF TILE. CLEARLY SPECIFY THE
 ROOF LOADS DEPENDING ON THE ROOF FINISH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 10- ASPHALT SHINGLES ROOF PITCH OF 2:12 TO LESS THAN
 4:12 REQUIRES TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY
 SEC. R905.2.2 FBC-RESIDENTIAL. SPECIFY ON PLANS.
  
 11-SHEET S-3:
 ZONE 3 ROOF PRESSURES SHOWN ON THE ROOF PRESSURE
 DIAGRAM SEEM TO BE LOW BASED SEE AERIAL VIEW OF
 BUILDING LOCATION AND REVISE DESIGN PRESSURES OR
 PROVIDE CALCULATIONS. SEC. R301.2.1.4 FBC-RESIDENTIAL,
 TABLE R301.2(2) FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 12- SHEET S-4:
 A)SECTION D/S-4 SHOWS NEW 2X6 WOOD STEM WALL. DETAIL IS
 MISSING SPECIFICATIONS OF HOW THE 2X6 ARE FASTENED TO
 THE TOP AND BOTTOM PLATES FOR CONTINUITY OF THE LOADS.
 SPECIFY CONNECTION. SEC. R601.2 FBC-RESIDENTIAL.
  
 B)PROVIDE DETAIL/SPECIFICATIONS FOR THE CONSTRUCTION OF
 THE CRICKET THAT IS RUNNING ON THE ENTIRE NORTH WALL OF
 THE ADDITION. SEC. R301.2.1 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBER AND CONNECTORS.
  
 13-PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH SEC.
 R703.1.2.1 FBC-RESIDENTIAL. SPECIFY FRAMING MEMBER AND
 CONNECTORS, SHEATHING, METAL LATH, STUCCO THICKNESS,
 ETC. NEW ENTRANCE SOFFIT AND NEW SOFFIT AROUND NEW
 ROOF.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FLASHING AROUND THE WINDOWS AND DOORS OPENINGS SHOWING
 COMPLIANCE WITH SEC. R703.4 FBC-RESIDENTIAL.
  
 15-VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $85,579. THE PERMIT FEE BALANCE IS $979.72.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-10 Cont ID  
Sent By equinone Date 2020-11-10 Time 09:47 Rev Time 0.00
Received By equinone Date 2020-11-10 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By jgomez Date 2020-11-19 Time 11:24 Rev Time 0.00
Received By jgomez Date 2020-10-27 Time 08:05 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jgomez Date 2020-11-19 Time 11:21 Rev Time 0.00
Received By jgomez Date 2020-11-19 Time 11:21 Sent To  
Notes
2020-11-19 11:22:05IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS SHOW A GARAGE WITH A GUEST SUITE. PLANS NEED TO
 BE REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEE
 ASSESSMENT.
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By medwards Date 2020-11-03 Time 14:32 Rev Time 0.00
Received By medwards Date 2020-11-03 Time 14:07 Sent To  
Notes
2020-11-03 14:32:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20101212
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS NEW
 ADDITION. FBC EC 101.5.1.1.2
  
 2) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE
 NEW EDITION AND THE EXISTING HOME. VERIFY THE EXISTING
 UNIT IS LARGE ENOUGH TO CONDITION THE NEW EDITION. FBC
 EC R403.7; FBC RES M1401.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2020-11-12 Cont ID  
Sent By jgomez Date 2020-11-12 Time 16:48 Rev Time 0.00
Received By jgomez Date 2020-11-12 Time 16:48 Sent To  
Notes
2020-11-12 16:53:071-THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH THE BASE FLOOD ELEVATION (BFE) OF 6
 FEET BASED ON NAVD 88. DURING THE PERMITTING OF THIS
 STRUCTURE THREE DIFFERENT FLOOD ELEVATION CERTIFICATES
 WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 NOTE: NEED TO PROVIDE THE CONSTRUCTION DRAWINGS
 ELEVATION CERTIFICATE NOW FOR REVIEW.
  
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 SEC. 107.3.5.1.1 CITY AMENDMENTS.
  
 2- THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THEREFORE, THE ADDITION AND THE EXISTING
 HOUSE NEED TO COMPLY WITH THE CITY TECHNICAL AMENDMENTS
 FOR STRUCTURES LOCATED IN A FLOOD ZONE AE.
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET OR
 THE DESIGN FLOOD ELEVATION
 THIS HOUSE IS LOCATED IN AE FLOOD ZONE WITH THE BASE
 FLOOD ELEVATION OF 6 FEET BASED ON NAVD 88. THEREFORE,
 THE FINAL FINISH FLOOR ELEVATION NEEDS TO BE AT LEAST
 AT 8 FEET. CONSTRUCTION DRAWINGS AND ELEVATION
 CERTIFICATE ARE REQUIRED TO SHOW THE PROPOSED FINISH
 FLOOR ELEVATION.
 SEC. 18-33. - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 SEC. 107.3.5.1.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-03 Cont ID  
Sent By lcrespo Date 2020-11-03 Time 17:50 Rev Time 0.00
Received By lcrespo Date 2020-11-03 Time 17:50 Sent To  
Notes
2020-11-03 17:51:0211/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By jgomez Date 2020-11-19 Time 11:22 Rev Time 0.00
Received By jgomez Date 2020-11-19 Time 11:22 Sent To  
Notes
2020-11-19 11:23:511- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOFING FINISH.
 (NOTE: NO SURE IF SHINGLES, TILE OR FLAT ROOF. PLANS
 ARE NOT CLEAR).
  
 2-- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By equinone Date 2020-10-27 Time 09:45 Rev Time 0.00
Received By equinone Date 2020-10-27 Time 09:44 Sent To  
Notes
2020-10-27 09:46:14PAPER DRAWINGS HAVE ORIGINAL SIGNATURE AND SEAL. ROUTED
 TO STORAGE 10/27/2020. EQ

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-05 Cont ID  
Sent By awooten Date 2020-11-05 Time   Rev Time  
Received By awooten Date 2020-11-05 Time   Sent To  
Notes
2020-11-05 11:24:15*****************ZONING REVIEW******************
  
 PLEASE UPDATE SITE PLAN INFORMATION TABLE TO SHOW THE
 CORRECT INFORMATION.
  
 THE REQUIRED SIDE SETBACKS HAVE TO BE A MINIMUM OF 5
 FEET AND TOTAL 15 FEET AND NOT JUST FIVE FEET.
  
 FRONT: 25 FEET;
 REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER IS
 LESS;
 SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 DIMENSION THE OVERHANG ON THE ELEVEATION DRAWINGS.
  
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-14449
 [email protected]