Plan Review Details - Permit 20101143
Plan Review Stops For Permit 20101143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-25 Cont ID  
Sent By rmcphers Date 2020-11-25 Time 13:32 Rev Time 0.00
Received By rmcphers Date 2020-11-25 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By rmcphers Date 2020-11-17 Time 13:28 Rev Time 0.00
Received By rmcphers Date 2020-11-17 Time 13:12 Sent To  
Notes
2020-11-17 13:27:45GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW CONCRETE GENERATOR PAD THICKNESS AND ANY
 REQUIRED REINFORCEMENT. FBC 1901.2
 2) PLEASE PROVIDE SIGNED AND SEALED GENERATOR TIEDOWN
 REQUIREMENTS SHOWING THE WIND DESIGN DATA USED FROM AN
 ARCHITECT OR ENGINEER PER FBC 1603.1 TO COMPLY WITH THE
 REQUIRED WIND LOADS PER FBC 1609
 3) PLEASE SHOW THE CONCRETE PAD SETBACKS FROM THE
 PROPERTY LINES AND THE WATER RUN OFF TO BE MAINTAINED
 ON THIS PROPERTY.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-02 Cont ID  
Sent By equinone Date 2020-12-02 Time 10:29 Rev Time 0.00
Received By equinone Date 2020-12-02 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By equinone Date 2020-11-16 Time 14:40 Rev Time 0.00
Received By equinone Date 2020-11-16 Time 13:10 Sent To  
Notes
2020-11-16 16:00:16CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SHEET NUMBER E-3.0 KEYNOTE NUMBER 2 STATES THAT
 GENERATOR IS NOT A SEPARATELY DERIVED SYSTEM. RISER
 DIAGRAMS SHOWS A #6 GROUND AT THE GENERATOR. FOR
 GENERATORS INSTALLED AS NOT SEPARATELY DERIVED SYSTEM
 NORMALLY THE EQUIPMENT GROUNDING CONDUCTOR THAT IS PART
 OF THE FIVE WIRE FEEDER FROM THE GENERATOR TO THE
 TRANSFER EQUIPMENT WILL GROUND AND BOND ALL OF THE
 NON-CURRENT CARRYING METAL PARTS OF THE GENERATOR
 THROUGH THE TRANSFER EQUIPMENT TO THE GROUNDING
 ELECTRODE SYSTEM BACK AT THE SERVICE. NEC 250.35. ONLY
 ONE FAULT RETURN PATH SHOULD EXIST.
 2) PROVIDE NOTE REQUIRING WARNING LABEL TO COMPLY WITH
 NEC 702.7
 3) SEE SIGNATURE COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-25 Cont ID  
Sent By pleduc Date 2020-11-25 Time   Rev Time 0.00
Received By pleduc Date 2020-11-25 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By pleduc Date 2020-11-19 Time   Rev Time 0.00
Received By pleduc Date 2020-11-19 Time 10:53 Sent To  
Notes
2020-11-19 11:17:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET # 3.0 INDICATES THE FUEL TYPE AS NATURAL GAS;
 HOWEVER, THERE IS NO INDICATIONS OF A FUEL LINE TO THE
 GENERATOR.
  
 PLEASE PROVIDE DETAILS OF THE LOCATION AND SIZE OF THE
 FUEL LINE IN COMPLAINCE WITH THE REQUIRMENTS OF NFPA
 54.
  
 5.1 PIPING PLAN.
 5.1.1 INSTALLATION OF PIPING SYSTEM. WHERE REQUIRED BY
 THE
 AUTHORITY HAVING JURISDICTION, A PIPING SKETCH OR PLAN
 SHALL BE
 PREPARED BEFORE PROCEEDING WITH THE INSTALLATION. THE
 PLAN
 SHALL SHOW THE PROPOSED LOCATION OF PIPING, THE SIZE OF
 DIFFERENT
 BRANCHES, THE VARIOUS LOAD DEMANDS, AND THE LOCATION OF
 THE POINT OF DELIVERY.
  
 CHAPTER 7 GAS PIPING INSTALLATION
 7.1 PIPING UNDERGROUND.
 7.1.1 CLEARANCES. UNDERGROUND GAS PIPING SHALL BE
 INSTALLED
 WITH SUFFICIENT CLEARANCE FROM ANY OTHER UNDERGROUND
 STRUCTURE
 TO AVOID CONTACT THEREWITH, TO ALLOW MAINTENANCE, AND
 TO PROTECT
 AGAINST DAMAGE FROM PROXIMITY TO OTHER STRUCTURES. IN
 ADDITION,
 UNDERGROUND PLASTIC PIPING SHALL BE INSTALLED WITH
 SUFFICIENT
 CLEARANCE OR SHALL BE INSULATED FROM ANY SOURCE OF HEAT
 SO AS TO
 PREVENT THE HEAT FROM IMPAIRING THE SERVICEABILITY OF
 THE PIPE.
 7.1.2 PROTECTION AGAINST DAMAGE. MEANS SHALL BE
 PROVIDED TO
 PREVENT EXCESSIVE STRESSING OF THE PIPING WHERE
 VEHICULAR TRAFFIC IS
 HEAVY OR SOIL CONDITIONS ARE UNSTABLE AND SETTLING OF
 PIPING OR
 FOUNDATION WALLS COULD OCCUR. PIPING SHALL BE BURIED OR
 COVERED
 IN A MANNER SO AS TO PROTECT THE PIPING FROM PHYSICAL
 DAMAGE.
 PIPING SHALL BE PROTECTED FROM PHYSICAL DAMAGE WHERE IT
 PASSES
 THROUGH FLOWER BEDS, SHRUB BEDS, AND OTHER SUCH
 CULTIVATED AREAS
 WHERE SUCH DAMAGE IS REASONABLY EXPECTED.
 7.1.2.1 COVER REQUIREMENTS. UNDERGROUND PIPING SYSTEMS
 SHALL BE INSTALLED WITH A MINIMUM OF 12 IN. (300 MM) OF
 COVER.
  
 (A) THE MINIMUM COVER SHALL BE INCREASED TO 18 IN.
 (460MM)IF
 EXTERNAL DAMAGE TO THE PIPE OR TUBING FROM EXTERNAL
 FORCES IS
 LIKELY TO RESULT.*******LIKE A UNDER A PARKING
 LOT********
  
  
  
 2) SHEET E 1.0 - THERE ARE NO DIMENSIONS INDICATED
 AROUND THE LOCATION OF THE GENERATOR.
  
 7.2.6 THE EPS EQUIPMENT SHALL BE INSTALLED IN A
 LOCATION THAT
 PERMITS READY ACCESSIBILITY AND A MINIMUM OF 0.9M(36
 IN.) FROM
 THE SKID RAILS? OUTERMOST POINT IN THE DIRECTION OF
 ACCESS FOR INSPECTION,
 REPAIR, MAINTENANCE, CLEANING, OR REPLACEMENT. THIS
 REQUIREMENT
 SHALL NOT APPLY TO UNITS IN OUTDOOR HOUSINGS.
  
  
 PLEASE PROVIDE DETAILED DIMENSION FROM PROPERTY LINES,
 PAVEMENT EDGES AND BUIDLINGS OR PROVIDE THE SPECIFIC
 MANUFACTURES SPEC SHEETS INDICATING OUTDOOR HOUSING.
  
  
  
 3) SHEET E 1.0 & E 2.0 - THERE ARE NO ELEVATION
 DIMENSIONS OF THE FOUNDATION.
  
 PER NFPA 110
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE
 ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE FLOOR OR GRADE
 LEVEL
 AND BE OF SUFFICIENT ELEVATION TO FACILITATE
 LUBRICATING-OIL DRAINAGE
 AND EASE OF MAINTENANCE.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 17:17 Rev Time 0.00
Received By medwards Date 2020-12-09 Time 17:17 Sent To  
Notes
2020-12-09 17:18:01SEE PERMIT #20120401 ME

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-12-01 Cont ID  
Sent By ccole Date 2020-12-01 Time 08:55 Rev Time 0.00
Received By ccole Date 2020-12-01 Time 07:20 Sent To  
Notes
2020-12-01 08:55:452ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101143
 12/1/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS #6- 14 FROM THE 1ST REVIEW WERE NOT ADDRESSED.
 PLEASE COMPLY.
  
 6) P3.0: CORRECT THE NOTE SPECIFYING THE ASPHALT PAINT
 ON THE UG GAS LINE- SECTION 404.17 FBC FG.
  
 7) P3.0: CORRECT OR REMOVE NOTE #4 AT THE GENERATOR
 RISER. IT APPEARS NOTE #5 SHOULD BE PROVIDED TO
 INDICATE 2ND STAGE REGULATOR. SHOW THE REQUIRED PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR-
 SECTIONS 410.1 & 410.2(7) FBC FG, AND SECTION 107.2.1
 WPB. PLEASE SHOW OR NOTE THE REQUIRED PIPE UNIONS AT
 THE REGULATOR LOCATED ON THE EXTERIOR WALL.
  
 8) P3.0: INDICATE A FLEXIBLE GAS SUPPLY LINE WILL BE
 INSTALLED AT THE GENERATOR AND PROVIDE THE LENGTH AND
 SIZE- SECTION 411.1 FBC FG.
  
 9) P1.0 & P3.0: SINGLE DEDICATED AND ACCESSIBLE SHUT
 OFF VALVES FOR THE EQUIPMENT IN THE MAIN LAB ROOM AND
 IN THE EQUIPMENT/COMPRESSOR ROOM SHALL BE PROVIDED. THE
 VALVES SHALL SERVE AS MAIN SHUTOFFS FOR ALL EQUIPMENT
 IN EACH ROOM AND SHALL BE LOCATED ADJACENT TO THE
 EGRESS DOOR FROM THE ROOM OR SPACE, AND SHALL BE
 IDENTIFIED BY APPROVED SIGNAGE STATING "GAS SHUTOFF"-
 SECTION 409.6 FBC FG.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND INTERIOR GAS-FIRED EQUIPMENT. THE SPECS
 SHALL BE HIGHLIGHTED OR MARKED UP TO SHOW THE MBTU/H
 LOADS, INPUT PRESSURES, AND LISTING STANDARDS- SECTIONS
 301.3, 301.5, & 305.1 FBC FG.
  
 11) CLARIFY IF THE INTERIOR EQUIPMENT WILL BE DIRECTLY
 CONNECTED VIA THE RIGID PIPING OR IF APPLIANCE
 CONNECTORS OR QUICK DISCONNECT DEVICES WILL BE
 INSTALLED. SUBMIT SPECS FOR ALL MANUFACTURED CONNECTORS
 HIGHLIGHTED OR MARKED UP TO SHOW LISTINGS- SECTION
 411.1 FBC FG.
  
 12) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 INTERIOR GAS-FIRED EQUIPMENT AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SECTION 304.1 & 305.1 FBC FG.
  
 13) PLEASE REFER TO SECTION 501.8 ITEMS #10 & 11 FBC
 FG: VENTING SYSTEMS APPEAR NOT TO BE REQUIRED FOR THE
 GAS BURNERS BECAUSE THE TOTAL GAS LOAD IN EACH ROOM
 DOES NOT EXCEED 20 MBTU/H, HOWEVER PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR THE EQUIPMENT TO CONFIRM COMPLIANCE- SECTION 305.1
 FBC FG.
  
 14) REFER TO SECTION 307.2 FBC FG AND PROVIDE
 CONDENSATE DISPOSAL PLANS FOR EQUIPMENT PRODUCING
 LIQUID COMBUSTION BY PRODUCTS.
  
 NEW COMMENT:
  
 15) INDICATE HOW THE GENERATOR IN THE PARKING LOT WILL
 BE PROTECTED FROM DAMAGE BY VEHICULAR IMPACT- SECTION
 303.4 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 11:12 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 07:59 Sent To  
Notes
2020-11-19 11:13:071ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20101143
 11/19/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.0: KEY NOTES AND GAS LOADS MISSING AT SHUT
 OFF VALVE LOCATIONS IN THE EQUIPMENT ROOM AND MODEL
 ROOM- SECTION 107.2.1 WPB.
  
 2) P1.0 & P3.0: CORRECT THE TOTAL LOAD IN THE FUEL/GAS
 SCHEDULE ON P1.0 TO INDICATE 2424.2 MBTU/H TO MATCH THE
 RISER DRAWING- SECTION 107.2.1 WPB.
  
 3) P1.0, P2.0, P3.0: CORRECT THE TOTAL LOADS INDICATED
 IN FUEL/GAS/SCHEDULE ON P2.0 TO MATCH THE TOTAL LOADS
 SPECIFIED IN THE OTHER DRAWINGS AND LOAD SUMMARIES-
 SECTION 107.2.1 WPB.
  
 4) P3.0: SHOW THE TOTAL MBTU/H LOAD AT THE METER AND
 THE LOAD AT THE GENERATOR. CORRECT THE TOTAL LOAD IN
 THE FUEL/GAS SCHEDULE- SECTION 107.2.1 WPB.
  
 5) P3.0: CORRECT THE NFPA 58 REFERENCE IN THE GAS
 NOTES. NFPA 58 IS THE LIQUIFIED PETROLEUM GAS CODE- SEE
 FBC FG REFERENCED STANDARDS.
  
 6) P3.0: CORRECT THE NOTE SPECIFYING THE ASPHALT PAINT
 ON THE UG GAS LINE- SECTION 404.17 FBC FG.
  
 7) P3.0: CORRECT OR REMOVE NOTE #4 AT THE GENERATOR
 RISER. IT APPEARS NOTE #5 SHOULD BE PROVIDED TO
 INDICATE 2ND STAGE REGULATOR. SHOW THE REQUIRED PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR-
 SECTIONS 410.1 & 410.2(7) FBC FG, AND SECTION 107.2.1
 WPB. PLEASE SHOW OR NOTE THE REQUIRED PIPE UNIONS AT
 THE REGULATOR LOCATED ON THE EXTERIOR WALL.
  
 8) P3.0: INDICATE A FLEXIBLE GAS SUPPLY LINE WILL BE
 INSTALLED AT THE GENERATOR AND PROVIDE THE LENGTH AND
 SIZE- SECTION 411.1 FBC FG.
  
 9) P1.0 & P3.0: SINGLE DEDICATED AND ACCESSIBLE SHUT
 OFF VALVES FOR THE EQUIPMENT IN THE MAIN LAB ROOM AND
 IN THE EQUIPMENT/COMPRESSOR ROOM SHALL BE PROVIDED. THE
 VALVES SHALL SERVE AS MAIN SHUTOFFS FOR ALL EQUIPMENT
 IN EACH ROOM AND SHALL BE LOCATED ADJACENT TO THE
 EGRESS DOOR FROM THE ROOM OR SPACE, AND SHALL BE
 IDENTIFIED BY APPROVED SIGNAGE STATING "GAS SHUTOFF"-
 SECTION 409.6 FBC FG.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND INTERIOR GAS-FIRED EQUIPMENT. THE SPECS
 SHALL BE HIGHLIGHTED OR MARKED UP TO SHOW THE MBTU/H
 LOADS, INPUT PRESSURES, AND LISTING STANDARDS- SECTIONS
 301.3, 301.5, & 305.1 FBC FG.
  
 11) CLARIFY IF THE INTERIOR EQUIPMENT WILL BE DIRECTLY
 CONNECTED VIA THE RIGID PIPING OR IF APPLIANCE
 CONNECTORS OR QUICK DISCONNECT DEVICES WILL BE
 INSTALLED. SUBMIT SPECS FOR ALL MANUFACTURED CONNECTORS
 HIGHLIGHTED OR MARKED UP TO SHOW LISTINGS- SECTION
 411.1 FBC FG.
  
 12) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 INTERIOR GAS-FIRED EQUIPMENT AND INDICATE HOW THE AIR
 WILL BE PROVIDED- SECTION 304.1 & 305.1 FBC FG.
  
 13) PLEASE REFER TO SECTION 501.8 ITEMS #10 & 11 FBC
 FG: VENTING SYSTEMS APPEAR NOT TO BE REQUIRED FOR THE
 GAS BURNERS BECAUSE THE TOTAL GAS LOAD IN EACH ROOM
 DOES NOT EXCEED 20 MBTU/H, HOWEVER PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS
 FOR THE EQUIPMENT TO CONFIRM COMPLIANCE- SECTION 305.1
 FBC FG.
  
 14) REFER TO SECTION 307.2 FBC FG AND PROVIDE
 CONDENSATE DISPOSAL PLANS FOR EQUIPMENT PRODUCING
 LIQUID COMBUSTION BY PRODUCTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-15 Cont ID  
Sent By lmarchan Date 2020-12-15 Time 09:11 Rev Time 0.00
Received By lmarchan Date 2020-12-09 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-03 Cont ID  
Sent By shill Date 2020-12-03 Time 18:32 Rev Time 0.00
Received By shill Date 2020-11-24 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By shill Date 2020-11-19 Time 16:03 Rev Time 0.00
Received By shill Date 2020-11-12 Time 21:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 17:19 Rev Time 0.00
Received By medwards Date 2020-12-09 Time 17:19 Sent To  
Notes
2020-12-09 17:19:50SEE PERMIT #20120511 FOR THE AIR COMPRESSOR. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-12-09 Cont ID  
Sent By shill Date 2020-12-09 Time 10:18 Rev Time 0.00
Received By shill Date 2020-12-09 Time 10:18 Sent To  
Notes
2020-12-09 10:18:42SEPARATE PERMIT REQUIRED (AIR COMPRESSOR LINES CANNOT
 BE ON A GENERATOR PERMIT)
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By ccole Date 2020-12-07 Time 09:31 Rev Time 0.00
Received By ccole Date 2020-12-07 Time 09:31 Sent To  
Notes
2020-12-07 09:32:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20101143
 11/19/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P4.0 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE COMPRESSORS, COMPRESSED AIR PIPING, AND PIPE
 CONNECTORS TO EQUIPMENT- SECTION 1003.1 AND 1003.2 FBC
 M. THE SPECS SHALL SHOW THE MAXIMUM PRESSURE RATINGS OF
 THE COMPRESSORS, PIPING, AND CONNECTORS.
  
 2) P4.0: INDICATE ON THE PLAN THE TYPE OF COMPRESSED
 AIR PIPING AND PIPE SLEEVES TO BE INSTALLED- SECTION
 1003.2 FBC M. PROVIDE PIPE SUPPORT AND HANGING DETAILS-
 TYPES, SIZES, AND SPACINGS OF HANGERS.
  
 3) P4.0: SUBMIT SPECS FOR THE AIR INTAKES AT THE
 EXTERIOR WALL AND PROVIDE A DETAIL SHOWING HOW THE AIR
 WILL BE DUCTED TO THE CEILING AIR INTAKE. CLARIFY HOW
 THE AMOUNT OF REQUIRED AIR FOR THE COMPRESSOR ROOM WAS
 DETERMINED OR CALCULATED- SECTION 107.2.1 WPB.
  
 4) P4.0: SHOW HOW CONDENSATION FROM THE COMPRESSORS
 WILL BE DRAINED AND DISPOSED OF- SECTION 307.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 17:20 Rev Time 0.00
Received By medwards Date 2020-12-09 Time 17:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-12-01 Cont ID  
Sent By ccole Date 2020-12-01 Time 09:18 Rev Time 0.00
Received By ccole Date 2020-12-01 Time 07:20 Sent To  
Notes
2020-12-01 09:19:06THE PLUMBING REVIEW COMMENTS FOR THE AIR COMPRESSOR AND
 PIPING WERE MOVED TO THE MECHANICAL REVIEW.
 CCOLE- 12/7/20
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By ccole Date 2020-11-19 Time 11:50 Rev Time 0.00
Received By ccole Date 2020-11-19 Time 07:59 Sent To  
Notes
2020-12-07 09:34:53THE PLUMBING REVIEW COMMENTS FOR THE AIR COMPRESSOR AND
 PIPING WERE MOVED TO THE MECHANICAL REVIEW.
 CCOLE- 12/7/20
  
2020-11-19 11:50:36 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-12-11 Cont ID  
Sent By pvalenti Date 2020-12-11 Time 17:31 Rev Time 0.00
Received By pvalenti Date 2020-12-11 Time 17:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-12-09 Cont ID  
Sent By medwards Date 2020-12-09 Time 17:20 Rev Time 0.00
Received By medwards Date 2020-12-09 Time 17:20 Sent To  
Notes
2020-12-09 17:21:11PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-25 Cont ID  
Sent By rmcphers Date 2020-11-25 Time 13:32 Rev Time 0.00
Received By rmcphers Date 2020-11-25 Time 13:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-17 Cont ID  
Sent By rmcphers Date 2020-11-17 Time 13:29 Rev Time 0.00
Received By rmcphers Date 2020-11-17 Time 13:29 Sent To  
Notes
2020-11-17 13:29:31SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By equinone Date 2020-11-16 Time 14:41 Rev Time 0.00
Received By equinone Date 2020-11-16 Time 14:41 Sent To  
Notes
2020-11-16 14:44:17ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 ELECTRICAL PLANS AND GAR AND AIR LINES PLANS: DOCUMENTS
 PREPARED BY AN ARCHITECT OR ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL. FS471, FS481,
  
 EITHER UPLOAD DIGITALLY OR ELECTRONICALLY SIGNED PLANS
 OR YOU CAN SUBMIT SIGNED AND SEALED PAPER ORIGINALS
 WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-12-14 Cont ID  
Sent By kalexand Date 2020-12-14 Time 17:00 Rev Time 0.00
Received By kalexand Date 2020-12-14 Time 17:00 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-12-02 Cont ID  
Sent By kalexand Date 2020-12-02 Time 15:01 Rev Time 0.00
Received By kalexand Date 2020-12-02 Time 15:01 Sent To I
Notes
2020-12-02 15:26:46ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO SETBACK.
 PURSUANT TO ZLDR SEC. 94-305 MECHANICAL EQUIPMENT MAY
 NO PROJECT MORE THAN 4FT INTO ANY REQUIRED SETBACK. THE
 REQUIRED SETBACK FOR THIS PARCEL IS 15FT.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By ajones Date 2020-11-19 Time 15:15 Rev Time 0.00
Received By ajones Date 2020-11-19 Time 15:15 Sent To  
Notes
2020-11-19 15:17:4611/19/20- FAILED- PLEASE SHOW SETBACKS OF GENERATOR AND
 AC UNIT FROM THE PROPERTY LINES.
  
 ANGELLA VANN, AICP
 551-822-1441
 [email protected]