Plan Review Details - Permit 20101122
Plan Review Stops For Permit 20101122 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-11-03 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-11-03 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-11-18 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-11-18 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-11-18 |
Time |
12:29 |
Sent To |
|
|
Notes |
2020-11-18 12:31:48 | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | STATUS: PASSED | | | | PREVIOUS COMMENTS: | | | | 1) SPECIFY MCB SIZE AND BUSBAR RATING TO SHOW | | COMPLIANCE WITH 120% RULE. | | | | CLARIFIED OVER THE PHONE. IT HAS 200 MCB AND 200 AMPS | | BUSBAR RATINGS SO IT COMPLIES. | | | | 2) PROVIDE SPECS FOR ATS. | | | | NOT AN ATS. | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | DEVELOPMENT SERVICES | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6746. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-11-18 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-11-17 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-11-17 |
Time |
11:37 |
Sent To |
|
|
Notes |
2020-11-17 11:39:13 | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | STATUS: FAILED | | | | 1) SPECIFY MCB SIZE AND BUSBAR RATING TO SHOW | | COMPLIANCE WITH 120% RULE. | | 2) PROVIDE SPECS FOR ATS. | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | DEVELOPMENT SERVICES | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6746. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-11-17 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2020-11-18 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-11-02 |
Time |
07:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-11-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-11-03 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-11-03 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-11-05 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-11-05 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2020-11-05 |
Time |
|
Sent To |
I |
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |