Plan Review Details - Permit 20101101
Plan Review Stops For Permit 20101101
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 08:32 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 08:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-01 Cont ID  
Sent By fgiaquin Date 2020-12-01 Time 00:00 Rev Time 0.00
Received By fgiaquin Date 2020-11-30 Time 23:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By fgiaquin Date 2020-11-19 Time 22:33 Rev Time 0.00
Received By fgiaquin Date 2020-11-19 Time 21:52 Sent To  
Notes
2020-11-19 22:33:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEPARATE ELECTRICAL PERMIT REQUIRED BY LICENSED
 ELECTRICIAN FOR 120V BRANCH CIRCUIT WORK. OUT OF SCOPE
 FOR ES LICENSE. PLEASE REFERENCE ELECTRICAL PERMIT
 NUMBER OF SAID PERMIT WHEN RESUBMITTING. FBC 105.1 .FS.
 489.505 (#19) AND F.A.C. 61G6-7.001 SPECIALTY
 ELECTRICAL CONTRACTORS (#2 SIGN SPECIALTY CONTRACTOR)
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW SHOWING POWER
 SUPPLY, DISCONNECTS, ETC. FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By lmarchan Date 2020-11-20 Time 11:24 Rev Time 0.00
Received By lmarchan Date 2020-11-05 Time 15:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 08:32 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 08:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By eschneid Date 2020-11-20 Time 09:08 Rev Time 0.25
Received By eschneid Date 2020-11-20 Time 09:07 Sent To  
Notes
2020-11-20 09:16:53WALL LENGTH: 186 FEET 7 INCHES
 EXISTING KRAVIS CENTER SIGN LENGTH (PERMIT 19080077):
 60 FEET 6 INCHES
 PROPOSED MEYER VALET SIGN LENGTH: 20 FEET 5 INCHES
  
 TOTAL LENGTHS: 80 FEET 11 INCHES
  
 TOTAL SIGN PERCENTAGE: 43.4%