Plan Review Details - Permit 20101099
Plan Review Stops For Permit 20101099
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 08:24 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 08:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-30 Cont ID  
Sent By fgiaquin Date 2020-11-30 Time 23:05 Rev Time 0.00
Received By fgiaquin Date 2020-11-30 Time 22:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By fgiaquin Date 2020-11-19 Time 21:08 Rev Time 0.00
Received By fgiaquin Date 2020-11-19 Time 20:16 Sent To  
Notes
2020-11-19 21:08:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION STATES THIS IS A "NEW" SIGN, BUT
 120V CIRCUIT IS SAID TO BE "EXISTING". SEPARATE
 ELECTRICAL PERMIT REQUIRED BY LICENSED ELECTRICIAN FOR
 120V BRANCH CIRCUIT WORK. OUT OF SCOPE FOR ES LICENSE.
 PLEASE REFERENCE ELECTRICAL PERMIT NUMBER OF SAID
 PERMIT WHEN RESUBMITTING. FBC 105.1 .FS. 489.505 (#19)
 AND F.A.C. 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS
 (#2 SIGN SPECIALTY CONTRACTOR)
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW SHOWING POWER
 SUPPLY, DISCONNECTS, ETC. FS 471.003(2)(H); 471.025;
 WPB FBC 107.2.1, 107.3.5
  
 3. ASTRONOMICAL TIME CLOCK REQUIRED FOR SIGN CIRCUIT.
 FBC EC 405.2.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By lmarchan Date 2020-11-20 Time 11:23 Rev Time 0.00
Received By lmarchan Date 2020-11-05 Time 15:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 08:24 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 08:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By eschneid Date 2020-11-20 Time 08:38 Rev Time 0.25
Received By eschneid Date 2020-11-20 Time 08:38 Sent To  
Notes
2020-11-20 08:43:13WALL LENGTH: 186 FEET 7 INCHES
 SIGN LENGTH: 11 FEET 8.5 INCHES
 SIGN PERCENTAGE: 6.3%


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved