Plan Review Details - Permit 20101043
Plan Review Stops For Permit 20101043
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 13:19 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2020-12-14 Cont ID  
Sent By jgomez Date 2020-12-14 Time 14:24 Rev Time 0.00
Received By jgomez Date 2020-12-14 Time 14:24 Sent To  
Notes
2020-12-14 14:26:41RESIDENTIAL (R3) SEVENTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
  
 COMMENTS TO REVISED DRAWING CVR SUBMITTED:
  
 1) REPEAT COMMENT: PLYWOOD FASTENING SPECIFICATIONS ARE
 INCOMPLETE AGAIN. STILL FAILING TO SPECIFY PLYWOOD
 FASTENER SPACING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2) DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS
 REQUIRED BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: PREVIOUS DRAWING HAD ARCHITECT'S DIGITAL
 SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 15:24 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 15:13 Sent To  
Notes
2020-12-11 15:32:25RESIDENTIAL (R3) SIXTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
  
 COMMENTS TO REVISED DRAWING CVR SUBMITTED:
  
 1) REPEAT COMMENT: PLYWOOD FASTENING SPECIFICATIONS ARE
 INCOMPLETE AGAIN. STILL FAILING TO SPECIFY FASTENER
 SPACING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2) DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS
 REQUIRED BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: PREVIOUS DRAWING HAD ARCHITECT'S DIGITAL
 SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 09:43 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 09:30 Sent To  
Notes
2020-12-11 09:53:27RESIDENTIAL (R3) FIFTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
  
 COMMENTS TO REVISED DRAWING CVR SUBMITTED:
 A) REPEAT COMMENT: PLYWOOD FASTENING SPECIFICATIONS ARE
 INCOMPLETE. OF THE PLYWOOD IS NOT CLEAR. WHERE ARE THE
 3" TAPCONS PLACED. SPECIFY SPACING, ETC. COORDINATE
 WITH ITEM #3. ABOVE.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. PLYWOOD FASTENING SPECIFICATIONS ARE
 INCOMPLETE AGAIN. STILL FAILING TO SPECIFY FASTENER
 SPACING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) ARCHITECT TO SPECIFY METAL LATH FASTENING. SPECIFY
 FASTENER TYPE, SIZE AND SPACING.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-12-09 Cont ID  
Sent By jgomez Date 2020-12-09 Time 16:58 Rev Time 0.00
Received By jgomez Date 2020-12-09 Time 16:09 Sent To  
Notes
2020-12-09 17:00:34RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 COMMENTS TO DRAWING CVR SUBMITTED:
 1)OK
 2)OK
  
 3) CONSTRUCTION DRAWINGS ARE NOT CLEAR AND ARE
 INCOMPLETE:
 A)PROVIDE DETAIL SHOWING HOW ARE THE 2X4 STUDS
 INSTALLED UNDER THE EXISTING PRECAST CONCRETE DOUBLE
 TEE FLOORING AND SPECIFY FASTENER TYPE, SIZE AND
 SPACING.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. DRAWING SUBMITTED STILL NO CLEAR AND
 DOESN'T PROVIDE SPECIFICATIONS FOR FASTENING OF P.T.
 2X4"S TO THE PRECAST DOUBLE TEE FLOORING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)FASTENING OF THE PLYWOOD IS NOT CLEAR. WHERE ARE THE
 (2)3" TAPCONS PLACED. SPECIFY SPACING, ETC. COORDINATE
 WITH ITEM #3. ABOVE.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. FASTENING OF THE PLYWOOD IS NOT CLEAR.
 SPECIFICATIONS SHOWN ON THE CONSTRUCTION PLAN DON'T
 MATCH SPECIFICATIONS SHOWN ON THE CONSTRUCTION
 AXONOMETRIC. CLEARLY SPECIFY FASTENER TYPE, SIZE AND
 SPACING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. THERE ARE NO SPECIFICATIONS FOR 2
 LAYERS OF WATER RESISTIVE BARRIERS. THERE IS A NOTE ON
 THE CONSTRUCTION AXONOMETRIC CALLING FOR "DOUBLE WIRE
 LATH". CLARIFY WHAT IS THIS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 NEW COMMENTS:
 D)CONSTRUCTION AXONOMETRIC SHOWS "EXISTING RAILING TO
 REMAIN" ON THE UPPER ROOF. ACCORDING TO PHOTOS SHOWN ON
 SHEET CVR, THERE IS NOT RAILING ON THE ROOF.
 REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 E)CONSTRUCTION AXONOMETRIC CALLS FOR "INSTALL A 3" PVC
 VENT. ACCORDING TO CONTRACTOR THERE IS NOT WORK ON THE
 SECOND FLOOR ROOF, EXCEPT FOR A MINOR REPAIR/PATCH.
 REVISE/CLARIFY AS REQUIRED. IF INSTALLING VENT , THEN
 CLEARLY SPECIFY SIZE AND LOCATION OF VENTS. SEC.
 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-12-03 Cont ID  
Sent By jgomez Date 2020-12-03 Time 13:14 Rev Time 0.00
Received By jgomez Date 2020-12-03 Time 10:12 Sent To  
Notes
2020-12-03 13:15:07RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1-UNABLE TO PERFORM BUILDING REVIEW. THERE IS NOT
 INFORMATION TO REVIEW. PROVIDE COMPLETE SET OF
 DRAWINGS/SPECIFICATIONS SHOWING ALL THE SCOPE OF WORK
 TO BE PERFORMED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 COMMENTS TO DRAWING CVR SUBMITTED:
 1)DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS REQUIRED
 BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 2) DRAWING HAS A NOTE ACROSS ENTIRE SHEET STATING THAT
 THIS IS NOT FOR CONSTRUCTION. NEED TO PROVIDE DRAWING
 WITHOUT THIS NOTE. DRAWING IS SUBMITTED FOR
 CONSTRUCTION. SEC. 107.2.1 CITY AMENDMENTS.
  
 3) CONSTRUCTION DRAWINGS ARE NOT CLEAR AND ARE
 INCOMPLETE:
 A)PROVIDE DETAIL SHOWING HOW ARE THE 2X4 STUDS
 INSTALLED UNDER THE EXISTING PRECAST CONCRETE DOUBLE
 TEE FLOORING AND SPECIFY FASTENER TYPE, SIZE AND
 SPACING.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
  
 B)FASTENING OF THE PLYWOOD IS NOT CLEAR. WHERE ARE THE
 (2)3" TAPCONS PLACED. SPECIFY SPACING, ETC. COORDINATE
 WITH ITEM #3. ABOVE.
 SEC. R703.1.2.1 FBC-RESIDENTIAL.
  
 C)DRAWINGS DON'T PROVIDE ANY INFORMATION ABOUT THE
 FINISH MATERIALS ON THIS SOFFIT. IS IT STUCCO?. SPECIFY
 THICKNESS ( TABLE R702.1(1). FBC-RESIDENTIAL).
  
 D) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-16 Cont ID  
Sent By jgomez Date 2020-11-16 Time 15:18 Rev Time 0.00
Received By jgomez Date 2020-11-16 Time 14:48 Sent To  
Notes
2020-11-16 15:19:20RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1-UNABLE TO PERFORM BUILDING REVIEW. THERE IS NOT
 INFORMATION TO REVIEW. PROVIDE COMPLETE SET OF
 DRAWINGS/SPECIFICATIONS SHOWING ALL THE SCOPE OF WORK
 TO BE PERFORMED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 INFORMATION SUBMITTED:
 A) IT LOOKS LIKE THE FIRST FLOOR SOFFIT AND THE SECOND
 FLOOR SOFFIT CONSTRUCTION ARE DIFFERENT. INFORMATION
 SUBMITTED IS NOT CLEAR. WHERE ARE THE COLUMNS SPECIFIED
 ON THE INFORMATION SUBMITTED. PROVIDE A COMPLETE
 DRAWING WITH COMPLETE SPECIFICATIONS FOR EACH TYPE OF
 SOFFIT SHOWING THAT THE SOFFIT IS DESIGNED TO RESIST
 THE WIND LOADS AS REQUIRED BY SEC. R703.1.2.1
 FBC-RESIDENTIAL. (NOTE: ACCORDING TO SEC. R301.2.1.4
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "D". HAVE THIS IN CONSIDERATION FOR THE WIND RESISTANCE
 REQUIRED FOR THIS SOFFIT).
  
 B) PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By jgomez Date 2020-10-29 Time 10:15 Rev Time 0.00
Received By jgomez Date 2020-10-29 Time 10:07 Sent To  
Notes
2020-10-29 10:17:23RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-UNABLE TO PERFORM BUILDING REVIEW. THERE IS NOT
 INFORMATION TO REVIEW. PROVIDE COMPLETE SET OF
 DRAWINGS/SPECIFICATIONS SHOWING ALL THE SCOPE OF WORK
 TO BE PERFORMED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By fmittner Date 2020-12-08 Time 10:30 Rev Time 0.00
Received By fmittner Date 2020-12-08 Time 10:30 Sent To  
Notes
2020-12-08 10:30:35CONTRACTOR CONFIRMED VIA E-MAIL RAILING TO REMAIN AND
 STUCCO FINISH TO MATCH EXISTING.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-11-23 Cont ID  
Sent By fmittner Date 2020-11-23 Time 11:52 Rev Time 0.00
Received By fmittner Date 2020-11-23 Time 11:52 Sent To  
Notes
2020-11-23 11:54:13SCOPE IS NOT CLEAR. PROPERTY IS IN HISTORIC DISTRICT.
 BRICK AND SMOOTH STUCCO FINISH MUST REMAIN INCLUDING
 BALCONY. PROVIDE PHOTOS AND CLEAR DESCRIPTION OF WORK.
 QUESTIONS, CONTACT:
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 (561) 822-1457 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 13:20 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 13:08 Sent To I
Notes
2020-12-17 13:08:24CONTRACTOR EMAILED REVISED DRAWING. JG.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-12-14 Cont ID  
Sent By jgomez Date 2020-12-14 Time 14:27 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 12:04 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 15:35 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 15:13 Sent To  
Notes
2020-12-11 15:14:18RECEIVED REVISED CVR PLAN VIA EMAIL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 10:23 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 09:29 Sent To I
Notes
2020-12-11 09:30:22CONTRACTOR EMAILED REVISED DRAWING.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-09 Cont ID  
Sent By jgomez Date 2020-12-09 Time 17:02 Rev Time 0.00
Received By jgomez Date 2020-12-09 Time 16:09 Sent To  
Notes
2020-12-09 16:10:02CONTRACTOR SUBMITTED REVISED DRAWINGS. I UPLOADED IT TO
 PROJECTDOX. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-08 Cont ID  
Sent By jgomez Date 2020-12-08 Time 13:44 Rev Time 0.00
Received By jgomez Date 2020-12-02 Time 15:18 Sent To  
Notes
2020-12-02 15:18:50RECEIVE EMAIL FROM CONTRACTOR WITH DRAWING CVR. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-02 Cont ID  
Sent By jgomez Date 2020-11-23 Time 15:16 Rev Time 0.00
Received By jgomez Date 2020-10-23 Time 06:55 Sent To  
Notes
2020-12-02 15:17:26HISTORIC REVIEW DONE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 13:09 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 13:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-12-14 Cont ID  
Sent By jgomez Date 2020-12-14 Time 14:27 Rev Time 0.00
Received By jgomez Date 2020-12-14 Time 14:26 Sent To  
Notes
2020-12-14 14:27:101)DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS REQUIRED
 BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 15:32 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 15:32 Sent To  
Notes
2020-12-11 15:33:241)DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS REQUIRED
 BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-11 Cont ID  
Sent By jgomez Date 2020-12-11 Time 10:20 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By jgomez Date 2020-12-03 Time 13:18 Rev Time 0.00
Received By jgomez Date 2020-12-03 Time 13:18 Sent To  
Notes
2020-12-03 13:20:241)DRAWING WAS NOT SIGNED AND SEALED BY THE ARCHITECT OF
 RECORD. ARCHITECT TO SIGN AND SEAL DRAWING AS REQUIRED
 BY 61G1-16.001FAC AND CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE: PLANS MAY BE SUBMITTED WITH A DIGITAL SIGNATURE
 OR HARD COPIES WITH LICENSED DESIGN PROFESSIONAL SEAL
 AND SIGNATURE MAY BE DROPPED (OR MAILED) TO CITY HALL
 FOR RECORDS RETENTION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy