Plan Review Details - Permit 20100983
Plan Review Stops For Permit 20100983
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-12-03 Cont ID  
Sent By cpuell Date 2020-12-03 Time 09:26 Rev Time 0.00
Received By cpuell Date 2020-12-03 Time 09:26 Sent To  
Notes
2020-12-03 09:29:47UNITY OF TITLE HAS NOT BEEN COMPLETED AT THIS TIME
 HOWEVER PAPA HAS GIVEN A PRELIMINARY COMBINATION PCN OF
 74424311010150030, AND I HAD AGREED WITH THE APPLICANT
 THAT THE PRIMARY ADDRESS WILL BE 5130 47TH PLACE N.
 UPLOADED COMBINED PARCEL LETTER TO PROJECTDOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-06-28 Cont ID  
Sent By rmcphers Date 2021-06-28 Time 13:27 Rev Time 0.00
Received By rmcphers Date 2021-06-28 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-19 Cont ID  
Sent By rmcphers Date 2021-05-19 Time 09:42 Rev Time 0.00
Received By rmcphers Date 2021-05-17 Time 16:23 Sent To  
Notes
2021-05-19 09:45:20SEE PLANS FOR THE DEFERRED ITEMS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-08 Cont ID  
Sent By mcphers Date 2021-03-08 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2021-03-08 Time 10:03 Sent To  
Notes
2021-03-08 10:12:51NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A7.0.1 HAS NOT BEEN REVISED TO SHOW THE
 GLAZING FOR THE WINDOWS IN THE FIRE RATED WALLS TO BE
 FIRE RATED. PLEASE SHOW FIRE RATED GLAZING IN FIRE
 RATED CORRIDOR WALLS AND DOORS TO COMPLY WITH FBC 716.5
 2) DRAWING A10.0.4 NEEDS TO SHOW THE DIMENSIONS FROM
 THE KITCHEN ISLAND TO THE REFRIGERATOR. PLEASE SHOW THE
 CLEAR SPACE DIMENSION BETWEEN KITCHEN COUNTER AND
 COUNTER OR APPLIANCES TO COMPLY WITH FBC FHA -
 REQUIREMENT 7 - USABLE KITCHENS AND BATHROOMS. (B)
 CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE
 CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST
 40 INCHES.
  
 TO BE DEFERRED - ROOFING SYSTEMS, PRODUCT APPROVALS FOR
 EXTERIOR WINDOWS, DOORS AND LOUVERS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By rmcphers Date 2020-12-02 Time 12:10 Rev Time 0.00
Received By rmcphers Date 2020-12-01 Time 12:42 Sent To  
Notes
2020-12-02 11:29:09NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) EXISTING BUILDING DEMO NEEDS TO BE A SEPARATE
 PERMIT.
 2) PLEASE SHOW THE STC RATING FOR THE WALLS AROUND THE
 SLEEPING AREAS TO COMPLY WITH FBC 1207.2 AIR-BORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90.
 3) PLEASE SHOW THE FIRE RATED CORRIDOR TO CONTINUE TO
 THE EXIT TO COMPLY WITH FBC 1020.6 CORRIDOR CONTINUITY.
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS.
 4) PLEASE SHOW DOORS (137, 138, 139, 130, 143, 146,
 147) OPENING INTO THE FIRE RATED CORRIDOR TO BE FIRE
 RATED PER FBC 716.5
 5) PLEASE SHOW FIRE RATED GLAZING IN FIRE RATED
 CORRIDOR WALLS AND DOORS TO COMPLY WITH FBC 716.5
 6) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO
 COMPLY WITH FBC 1209.2
 7) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS,
 LOUVERS ETC. - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD OR BE LISTED BY PRODUCT APPROVAL NUMBER ON
 THE DRAWINGS.
 8) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEM TO BE USED.
 9) PLEASE SHOW THE LOCATION AND REQUIREMENT FOR GRAB
 BAR BACKING AT THE TOILETS AND ALL WALLS OF THE SHOWERS
 IN THE ROOM TYPE A AND B PER FBC FHA - REQUIREMENT 6 -
 REINFORCED WALLS FOR GRAB BARS. REINFORCED BATHROOM
 WALLS TO ALLOW LATER INSTALLATION OF GRAB BARS AROUND
 THE TOILET, TUB, SHOWER STALL AND SHOWER SEAT, WHERE
 SUCH FACILITIES ARE PROVIDED, WOULD MEET SECTION
 100.205(C)(3)(III) IF REINFORCED AREAS ARE PROVIDED AT
 LEAST AT THOSE POINTS WHERE GRAB BARS WILL BE MOUNTED.
 10) PLEASE SHOW LAUNDRY AREA CLEAR FLOOR SPACE AND
 APPLIANCES TO COMPLY WITH FBC FHA - REQUIREMENT 2.
 ACCESSIBLE AND USABLE PUBLIC AND COMMON USE AREAS.IF
 PROVIDED IN THE FACILITY OR AT THE SITE, AT LEAST ONE
 OR EACH TYPE OF APPLIANCES PROVIDED IN EACH LAUNDRY
 AREA, EXCEPT THAT LAUNDRY ROOMS SERVING COVERED
 MULTIPLE-FAMILY DWELLINGS WOULD NOT BE REQUIRED TO HAVE
 FRONT-LOADING WASHERS IN ORDER TO MEET THE REQUIREMENTS
 OF 100.205(C)(1). (WHERE FRONT-LOADING WASHERS ARE NOT
 PROVIDED, MANAGEMENT WILL BE EXPECTED TO PROVIDE
 ASSISTIVE DEVICES ON REQUEST IF NECESSARY TO PERMIT A
 RESIDENT TO USE A TOP LOADING WASHER.)
 11) PLEASE SHOW THE CLEAR SPACE DIMENSION BETWEEN
 KITCHEN COUNTER AND COUNTER OR APPLIANCES TO COMPLY
 WITH FBC FHA - REQUIREMENT 7 - USABLE KITCHENS AND
 BATHROOMS. (B) CLEARANCE BETWEEN COUNTERS AND ALL
 OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES OR
 WALLS IS AT LEAST 40 INCHES.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-06-28 Cont ID  
Sent By jleahy Date 2021-06-28 Time 09:10 Rev Time 0.00
Received By jleahy Date 2021-06-28 Time 08:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-10 Cont ID  
Sent By jleahy Date 2021-05-10 Time 14:33 Rev Time 0.00
Received By jleahy Date 2021-05-10 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-24 Cont ID  
Sent By jleahy Date 2021-02-24 Time 15:15 Rev Time 0.00
Received By jleahy Date 2021-02-24 Time 13:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By jleahy Date 2020-12-07 Time 17:00 Rev Time 0.00
Received By jleahy Date 2020-12-07 Time 15:31 Sent To  
Notes
2020-12-07 17:08:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.1.1
  
 GAZEBO HAS MORE THAN ONE BRANCH CIRCUIT GOING TO IT. IT
 SHALL MEET THE REQUIREMENTS OF 225.30
  
 A BUILDING OR O THER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT UNLESS PERMITTED IN 225.30(A)
 THROUGH (E). FOR THE PURPOSE OF THIS SECTION, A
 MULTIWIRE BRANCH CIRCUIT SHALL BE CONSIDERED A SINGLE
 CIRCUIT.
  
 PAGE E3.1
  
 DRINKING FOUNTAN SHALL BE GFCI PROTECTED AND GFCI
 DEVICE SHALL BE ACCESSIBLE 422.52
  
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION.
  
 PAGE E5.1
  
 TRANSFER SWITCH DOES NOT SHOW A SIZE OR BREAKER SIZE
 INSIDE. 215.5
  
 GENERATOR SHOW OCP NO SIZE SHOWN. 215.5

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By rrossano Date 2020-11-05 Time   Rev Time  
Received By rrossano Date 2020-11-05 Time   Sent To  
Notes
2020-11-05 08:57:05UNDER REVIEW AS FORMAL ENG SUBMITTAL E20060020.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-06-14 Cont ID  
Sent By pleduc Date 2021-06-11 Time   Rev Time 0.00
Received By pleduc Date 2021-06-11 Time 15:01 Sent To  
Notes
2021-06-11 15:10:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE TWO EXIT SIGNS WITHIN THE MAIN CORRIDOR
 CENTERED OVER A DOUBLE SWING DOOR.
  
 PLEASE RELOCATE THE EXIT SIGNS OVER THE CENTER OF THE
 DOOR IN THE PATH OF TRAVEL; AS INDICATED.
  
  
 2) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED
 & INSPECTED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-04-22 Cont ID  
Sent By pleduc Date 2021-04-22 Time   Rev Time 0.00
Received By pleduc Date 2021-04-22 Time 12:55 Sent To  
Notes
2021-04-22 13:09:48THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE TWO EXIT SIGNS WITHIN THE MAIN CORRIDOR
 CENTERED OVER A DOUBLE SWING DOOR.
  
 PLEASE RELOCATE THE EXIT SIGNS OVER THE CENTER OF THE
 DOOR IN THE PATH OF TRAVEL; AS INDICATED.
  
  
 2) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED
 & INSPECTED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-12 Cont ID  
Sent By pleduc Date 2021-02-12 Time   Rev Time 0.00
Received By pleduc Date 2021-02-10 Time 09:53 Sent To  
Notes
2021-02-10 10:09:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE TWO EXIT SIGNS WITHIN THE MAIN CORRIDOR
 CENTERED OVER A DOUBLE SWING DOOR.
  
 PLEASE RELOCATE THE EXIT SIGNS OVER THE CENTER OF THE
 DOOR IN THE PATH OF TRAVEL; AS INDICATED.
  
  
 2) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED
 & INSPECTED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-23 Cont ID  
Sent By pleduc Date 2020-11-23 Time   Rev Time 0.00
Received By pleduc Date 2020-11-18 Time 13:34 Sent To  
Notes
2020-11-23 13:17:52THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THERE ARE TWO EXIT SIGNS WITHIN THE MAIN CORRIDOR
 CENTERED OVER A DOUBLE SWING DOOR.
  
 PLEASE RELOCATE THE EXIT SIGNS OVER THE CENTER OF THE
 DOOR IN THE PATH OF TRAVEL; AS INDICATED.
  
  
 2) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED, TESTED
 & INSPECTED PER NFPA 24 UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 10:38 Rev Time 0.00
Received By ccole Date 2021-06-25 Time 17:32 Sent To  
Notes
2021-06-28 10:39:30GAS REVIEW COMPLETED. SUB-PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-05-11 Cont ID  
Sent By ccole Date 2021-05-11 Time 09:13 Rev Time 0.00
Received By ccole Date 2021-05-10 Time 08:46 Sent To  
Notes
2021-05-11 09:14:112ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20100983
 5/11/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P0.1, P3.1 & P6.1: THE PLANS DO NOT INDICATE
 HOW COMBUSTION AIR WILL BE PROVIDED FOR THE GAS WATER
 HEATER, OR HOW THE APPLIANCE WILL BE VENTED- SECTIONS
 304.1, 502.1 & 624.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-26 Cont ID  
Sent By ccole Date 2021-02-26 Time 17:38 Rev Time 0.00
Received By ccole Date 2021-02-26 Time 17:38 Sent To  
Notes
2021-02-26 17:40:011ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20100983
 2/26/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P6.1: PROVIDE MANUFACTURER?S SPECIFICATIONS
 FOR THE GENERATOR, RANGE, AND DRYERS- SECTION 107.2.1
 WPB. CONCERNING THE GENERATOR, A SEPARATE PERMIT IS
 REQUIRED FOR THE INSTALLATION, HOWEVER A CUT SHEET
 SHOWING THE BTUH LOAD AND INPUT PRESSURE WOULD BE
 HELPFUL FOR REGULATOR SELECTION- SECTION 410.2 FBC FG.
 PLEASE NOTE THAT THE CURRENT RANGE PRODUCT SUBMITTAL IS
 FOR AN ELECTRIC APPLIANCE, AND THE GAS DRYER SUBMITTAL
 INDICATES 22,000 BTUH DRYERS- THE RISER SHOWS 75,000
 BTUH DRYERS.
  
 2) P6.1: SHOW THE TOTAL LOAD OF THE SYSTEM- 3,377,000
 BTUH- SECTION 402.2 & 402.3 FBC FG.
  
 3) P6.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND DRYERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-28 Cont ID  
Sent By rmcphers Date 2021-06-28 Time 13:27 Rev Time 0.00
Received By rmcphers Date 2021-06-10 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-19 Cont ID  
Sent By rmcphers Date 2021-05-19 Time 09:46 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-08 Cont ID  
Sent By rmcphers Date 2021-03-08 Time 10:15 Rev Time 0.00
Received By rmcphers Date 2021-02-05 Time 22:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-07 Cont ID  
Sent By jleahy Date 2020-12-07 Time 17:08 Rev Time 0.00
Received By jleahy Date 2020-11-03 Time 07:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-07-01 Cont ID  
Sent By lmarchan Date 2021-07-01 Time 09:44 Rev Time 0.00
Received By lmarchan Date 2021-05-29 Time 09:12 Sent To  
Notes
2021-07-01 09:44:01RECEIPT MU-2021-029092 - $1519.95 - PAID
2021-05-29 09:12:415/29/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By rmcphers Date 2020-12-02 Time 12:15 Rev Time 0.00
Received By rmcphers Date 2020-12-02 Time 12:15 Sent To  
Notes
2020-12-02 12:16:38PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-06-24 Cont ID  
Sent By medwards Date 2021-06-24 Time 14:16 Rev Time 0.00
Received By medwards Date 2021-06-24 Time 14:16 Sent To  
Notes
2021-06-24 14:17:45 
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-05-10 Cont ID  
Sent By medwards Date 2021-05-10 Time 09:07 Rev Time 0.00
Received By medwards Date 2021-05-10 Time 09:07 Sent To  
Notes
2021-05-10 09:09:373RD REVIEW FBC-2020 MECHANICAL
 PERMIT-20100983
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET LS-1-1 SHOWS 1-HOUR RATED CORRIDOR WALLS.
 SHEET M2-1: PLEASE SHOW THE REQUIRED PROTECTION WHERE
 ALL CORRIDOR WALLS ARE PENETRATED BY THE MECHANICAL
 DUCTS. I.E. AHU-6 DUCTWORK INTO THE MUSIC ROOM. FBC M
 607
  
 2) SHEET M2-1: PLEASE SHOW PROTECTION AT EACH LOCATION
 THAT THE 12 X14 DUCT FROM OAU-3 PENETRATES THE RATED
 CORRIDOR WALLS. FBC 607
  
 3) SHEET M2-1: PLEASE SHOW PROTECTION AT EACH LOCATION
 THAT THE BATH EXHAUST DUCTS PENETRATE THE FIRE
 PARTITION SEPARATING THE SLEEPING UNITS. FBC 607
  
 4) PLEASE SHOW HOW AHU-3, AHU-6 AND AHU-1 MEET AIR
 MOVEMENT IN EGRESS ELEMENTS FBC M 601.2
  
 5) PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS
 INDICATING THAT THE KITCHEN HOOD WILL BE A SEPARATE
 SUBMITTAL AND REVIEW. IT WILL ALSO NEED TO MEET FBC M
 506, 507 FOR THE HOOD AND GREASE DUCT, SECTION 508 FOR
 MAKE UP AIR, SECTION 509 FOR FIRE SUPPRESSION SYSTEMS.
 THE HOOD EXHAUST MUST MEET FBC M 501.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-02-24 Cont ID  
Sent By medwards Date 2021-02-24 Time 13:32 Rev Time 0.00
Received By medwards Date 2021-02-24 Time 10:05 Sent To  
Notes
2021-02-24 13:32:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20100983
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2-1 DOES SHOW SEVERAL FIRE RATED WALLS.
 PLEASE SHOW THE PROTECTION FOR EACH DUCT PENETRATION AT
 EACH OF THESE WALLS. FBC M 607
  
 2) OAU-2 SHOWS DUCTWORK PENETRATING THE RATED WALLS OF
 THE BEDROOMS IT ALSO SHOWS DUCTS SUPPLYING OUTDOOR AIR
 TO THE CORRIDOR AND OTHER AREAS. PLEASE SHOW THE
 DAMPERS FOR THE PENETRATIONS OF THE RATED WALLS FOR THE
 BEDROOMS. FBC M 607.5.3
  
 3) PLEASE SHOW THE FIRE DAMPER IN THE EXHAUST FANS. FBC
 M 607
  
 4) THE KITCHEN IS CLASSIFIED AS A COMMERCIAL KITCHEN.
 THEREFORE YOU MUST INSTALL A TYPE I HOOD. YOU CAN USE A
 DOMESTIC COOKING APPLIANCE IN A COMMERCIAL KITCHEN. FBC
 M DEFINITIONS: COMMERCIAL COOKING APPLIANCES.
 APPLIANCES USED IN A COMMERCIAL FOOD SERVICE
 ESTABLISHMENT FOR HEATING OR COOKING FOOD AND WHICH
 PRODUCE GREASE VAPORS, STEAM, FUMES, SMOKE OR ODORS
 THAT ARE REQUIRED TO BE REMOVED THROUGH A LOCAL EXHAUST
 VENTILATION SYSTEM. SUCH APPLIANCES INCLUDE DEEP FAT
 FRYERS; UPRIGHT BROILERS; GRIDDLES; BROILERS;
 STEAM-JACKETED KETTLES; HOT-TOP RANGES; UNDER-FIRED
 BROILERS (CHARBROILERS); OVENS; BARBECUES; ROTISSERIES;
 AND SIMILAR APPLIANCES. FOR THE PURPOSE OF THIS
 DEFINITION, A FOOD SERVICE ESTABLISHMENT SHALL INCLUDE
 ANY BUILDING OR A PORTION THEREOF USED FOR THE
 PREPARATION AND SERVING OF FOOD.
 FBC M 507.1 COMMERCIAL KITCHEN HOODS; DOMESTIC COOKING
 APPLIANCES USED FOR COMMERCIAL PURPOSES FBC M 507.1.2,
 GREASE DUCTS SERVING A TYPE I HOOD FBC M 506.3
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-13 Cont ID  
Sent By medwards Date 2020-11-13 Time 13:19 Rev Time 0.00
Received By medwards Date 2020-11-10 Time 15:34 Sent To  
Notes
2020-11-13 13:20:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100983
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LS-1.2 LISTS THE MULTIPURPOSE ROOM OCCUPANCY AS 18.
 SHEET M0.1 OUTSIDE AIR CALCULATIONS HAS THE OCCUPANCY
 FOR THE MULTIPURPOSE ROOM AT 8. PLEASE MAKE THE OUTSIDE
 AIR CALCULATIONS OCCUPANCY COUNT MATCH THE BUILDING
 OCCUPANCY COUNT FOR USE OF SPACE. FBC M TABLE 4.3.3.1.1
  
 2) PLEASE USE THE BUILDING OCCUPANT COUNT FOR USE OF
 SPACE AS THE ?ACTUAL OCCUPANT NO. OF PEOPLE IN THE
 OUTSIDE AIR CALCULATIONS. FBC TABLE 403.3.1.1
  
 3) PLEASE SHOW ON THE MECHANICAL DRAWINGS THAT THE
 AHU?S FOR THE LIVING QUARTERS ARE ACCESSIBLE. FBC M
 306.3 APPLIANCES IN ATTICS
  
 4) SHEET M2.1; THE WALL BETWEEN THE GAME ROOM AND THE
 RECEPTION AREAS APPEARS TO BE A RATED WALL. PLEASE SHOW
 THE PROTECTION AT THE PENETRATIONS OF THESE RATED WALLS
 FOR THE SUPPLY AND RETURN DUCTS FOR THE GAME ROOM. FBC
 M 607
  
 5) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE COOKING
 EQUIPMENT IN THE KITCHEN. PLEASE PROVIDE A DETAIL OF
 THE SPECIFIC USE OF THIS KITCHEN AND TYPES OF FOOD
 BEING PREPARED. FBC 107.2
  
 6) PLEASE PROVIDE SPECIFICATIONS FOR THE KITCHEN HOOD.
 FBC M 507
  
 7) EXHAUST FANS IN THE BATHROOMS IN THE WORKOUT ROOM DO
 NOT HAVE A TAG ASSOCIATED WITH GENERAL FAN SCHEDULE ON
 SHEET M6.2 PLEASE CORRECTLY IDENTIFY THESE EXHAUST
 FANS. FBC 107.2
  
 8) PLEASE PROVIDE A DETAIL DRAWING OF THE BATH EXHAUST
 FANS AND THE FIRE DAMPER LOCATION AND ACCESS. FBC M
 607.4
  
 9) PLEASE SHOW ACCESS FOR EACH FIRE SMOKE DAMPER. FBC
 M607.4
  
 10) PLEASE PROVIDE SPECIFICATION SHEETS FOR THE DRYERS
 IN THE LAUNDRY ROOM. FBC M 504
  
 11) SHEET M7.2 THE DETAIL DRAWING OF THE DRYER ROOF
 TERMINATION HAS A SCREEN AT THE EXHAUST TERMINATION.
 PLEASE REMOVE THE SCREEN AS IT IS NOT ALLOWED. FBC M
 504.4
  
 12) SHEET M7.2 THE CEILING FIRE DAMPER DETAIL INDICATES
 THERE IS A CEILING BELOW THE RATED CEILING, PLEASE
 PROVIDE A SHEET NUMBER THAT SHOWS THE DETAIL OF THE TWO
 CEILINGS. FBC 107.2
  
 13)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 10:38 Rev Time 0.00
Received By ccole Date 2021-06-25 Time 17:32 Sent To  
Notes
2021-06-28 10:40:12PLUMBING REVIEW COMPLETED. PLUMBING SUB-PERMIT
 REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-05-11 Cont ID  
Sent By ccole Date 2021-05-11 Time 08:18 Rev Time 0.00
Received By ccole Date 2021-05-10 Time 08:46 Sent To  
Notes
2021-05-11 08:18:333RD REVIEW FBC-2017 PLUMBING
 PERMIT-20100983
 5/10/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0.1, P2.1 & P5.1: HAND SINK SK-2 SHALL NOT
 DRAIN INTO THE GREASE INTERCEPTOR- SECTION 1003.3.1 FBC
 P. HANDSINKS ARE NOT SIGNIFICANT GREASE CONTRIBUTORS.
  
 2) P0.1, P2.1, & P5.1: THE PLANS SHOW A DIRECT WASTE
 CONNECTION FOR SK-1 HOWEVER AN INDIRECT WASTE
 CONNECTION IS REQUIRED PER SECTIONS 802.1 & 802.1.1 FBC
 P. THE PLANS DO NOT MAKE CLEAR THE USE OF THE SINK BUT
 IT IS ASSUMED TO BE RELATED TO EITHER FOOD PREP OR
 DISHWASHING.
  
 3) P0.1, P2.1, & P6.1: THE NOTES IN THE SCHEDULE FOR
 SK-4 INDICATE COMPLIANCE WITH SECTION 422.6 FBC P.
 PLEASE REFER TO TABLE 604.5 AND CLARIFY IF THE SELECTED
 SINK IS A CLINAL SINK WITH A FLUSHOMETER VALVE BECAUSE
 A 1-INCH WATER LINE IS REQUIRED AND THE PLANS SHOW A
 1/2- INCH LINE.
  
 4) P0.2: PLEASE PROVIDE A SAMPLING PORT DETAIL FOR THE
 GREASE INTERCEPTOR- SECTION 1003.3.4 FBC P.
  
 5) P0.2, P2.1: PLEASE NOTE THAT A LOAD RATED TRAFFIC
 LID SHALL BE PROVIDED FOR THE INTERCEPTOR IF LOCATED IN
 A MOTOR VEHICLE DRIVE OR PARKING AREA- SECTION 1003.3.4
 FBC P.
  
 6) P0.2 & P2.1: PROVIDE SIZING CALCULATIONS FOR THE
 STRIEM SOLIDS INTERCEPTOR TO VERIFY ADEQUATE GALLON
 SIZE SIZE SELECTION. THE SPECS SHOW 2 IN. INLETS AND
 OUTLETS, HOWEVER THE SANITARY RISER INDICATES 4 INCH
 PIPE CONNECTIONS. REFER TO SECTION 1003.6 FBC P- PLEASE
 VERIFY THE INTERCEPTOR IS PROVIDED WITH A WIRE BASKET
 OR SIMILAR DEVICE, REMOVABLE FOR CLEANING, THAT
 PREVENTS PASSAGE INTO THE DRAINAGE SYSTEM OF SOLIDS 1/2
 INCH OR LARGER IN SIZE, STRING, RAGS, BUTTONS OR OTHER
 MATERIALS DETRIMENTAL TO THE PUBLIC SEWAGE SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By ccole Date 2021-02-26 Time 17:34 Rev Time 0.00
Received By ccole Date 2021-02-26 Time 17:34 Sent To  
Notes
2021-02-26 17:34:462ND REVIEW FBC-2017 PLUMBING
 PERMIT-20100983
 2/26/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. REMAINING COMMENTS FROM
 THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 3) SHEET LS.1.1 & LS.1.1, PLUMBING FIXTURE
 REQUIREMENTS: THE SQUARE FOOT AREAS AND OCCUPANT LOADS
 ON LS.1.1 DO NOT MATCH THE AREA AND OCCUPANT LOAD CALCS
 IN THE PLUMBING FIXTURE SCHEDULE ON LS.1.2. PLEASE
 CORRECT. THE NARRATIVE RESPONSE STATES THIS HAS BEEN
 CLEARED UP IN PHONE CALL, HOWEVER THE REVIEWER HAS
 NUMEROUS PHONE CALLS ABOUT PLANS, AND UNFORTUNATELY
 DOES NOT RECALL THE DETAILS OF THE PHONE CALL. PLEASE
 SUBMIT A NARRATIVE IN WRITING CLARIFYING WHAT THE
 DESIGN INTENTION IS REGARDING THE NUMBER OF REQUIRED
 FIXTURES FOR THE OCCUPANCY, AND THE REQUIRED SEPARATION
 OF FACILITIES FOR MALE AND FEMALE USE IN THE BUSINESS
 AND ASSEMBLY AREAS.
  
 B) FAILED. LIST THE REQUIRED AND PROVIDED NUMBERS OF
 MALE AND FEMALE WATER CLOSETS AND LAVATORIES FOR A3, B,
 R4, & S OCCUPANCIES. PLEASE NOTE THAT SEPARATE MALE AND
 FEMALE FIXTURES ARE REQUIRED FOR A3, B AND S
 OCCUPANCIES- SECTION 403.2. UNISEX ARE PERMITTED FOR
 THE R4 OCCUPANCY. SEPARATE MALE AND FEMALE FIXTURES
 REQUIRED.
  
 6) FAILED. P0.1, P2.1 & P5.1: A) SK-1 &SK-2 ARE
 MISLABELED L2 IN THE ISOMETRIC. B) SK-3 IS MISLABELED
 SK-2 IN THE ISOMETRIC. C) SK-3 IS A 3-COMPARTMENT SINK
 PER THE FIXTURE SCHEDULE BUT IS SHOWN AS A
 2-COMPARTMENT SINK ON THE PLAN, AND A SINGLE SINK IN
 THE ISO. INDIRECT WASTE REQUIRED FOR THE 3-BAY SINK-
 SECTIONS 802.1 & 802.1.1 FBC P.
  
 8) FAILED. P0.1: PROVIDE AN ITEMIZED FOOD EQUIPMENT
 PLAN AND CORRELATING EQUIPMENT SCHEDULE- SECTION
 107.2.1 WPB. CLARIFY WHAT EQUIPMENT MAY BE INSTALLED IN
 THE KITCHEN SUCH AS A FOOD WASTE DISPOSER, ICE MAKER,
 BEVERAGE DISPENSER, COFFEE MAKER ETC. THE SCHEDULE ON
 SHEET A10.04 SHOWS AN ELECTRIC RANGE, THE GAS PLAN ON
 SHEET P3.1 SHOWS A GAS RANGE. REFER TO GAS REIVEW
 COMMENTS.
  
 9) FAILED P0.1, P2.1 & P5.1: PROVIDE A GREASE
 INTERCEPTOR AND GREASE INTERCEPTOR CALCULATIONS FOR THE
 DRAINAGE FROM PLUMBING FIXTURES IN THE KITCHEN- REFER
 TO SECTIONS 1003.1 & 1003.3.1 FBC P. REVISE THE
 DRAWINGS AND SPECIFICATIONS TO SHOW THE TYPE OF
 INTERCEPTOR TO BE INSTALLED, MAKE AND MODEL OF THE
 UNIT, THE LOCATION AND THE PLUMBING PIPING
 REQUIREMENTS. SECTION 1003.3.3 DOES NOT REQUIRE GREASE
 INTERCEPTORS FOR INDIVIDUAL DWELLING UNITS AND PRIVATE
 QUARTERS. THIS OCCUPANCY IS A GROUP LIVING FACILITY.
 EXCEPTION DOES NOT APPLY- PROVIDE THE GREASE
 INTERCEPTOR AS REQUIRED.
  
 10) FAILED. P0.1, P2.1 & P5.1: THE DRAINAGE FROM THE
 DISHWASHER AND THE 2 OR 3-COMPARTMENT SINKS SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE RECEPTOR- SECTIONS
 802.1 & 802.7 FBC P. REVISE THE DRAWINGS ACCORDINGLY,
 PROVIDE AN INSTALLATION DETAIL PER SECTION 802.2, AND
 ADD THE RECEPTORS TO THE FIXTURE SCHEDULES- SECTION
 802.3. THE FIXTURE SCHEDULE ON SHEET P0.1 CALLS OUT A
 COMMERCIAL DISHWASHER.
  
 11) FAILED. P0.1, P2.1 & P5.1: PROVIDE INTERCEPTORS FOR
 THE CLOTHES WASHERS PER SECTION 1003.6. REVISE THE
 DRAWINGS AND SPECIFICATIONS TO SHOW MAKES AND MODELS OF
 THE UNITS, LOCATIONS, AND THE PLUMBING PIPING
 REQUIREMENTS. THE EXCEPTIONS UNDER 1003.6 ARE NOT
 APPLICABLE.
  
 13) FAILED. P0.1, P5.1, & P6.1: SK-4 IS MISLABELED AS
 SK-1 IN THE ISOMETRIC DRAWINGS- SECTION 107.2.1 WPB.
 BASED ON THE USE OF THE MEDICATION ROOM, A CLINICAL
 SINK SHALL BE REQUIRED IN ACCORDANCE WITH SECTIONS
 422.1 & 422.6. REVISE THE DRAWINGS AND THE SCHEDULE
 ACCORDINGLY. SK-4 DRAIN NOT SHOWN CORERECTLY IN THE
 ISOMETRIC ON P5.1. SINK HAS AN INTEGRAL TRAP- SEE
 SECTION 713.2 FBC P.
  
 14) FAILED. P3.1 & P6.1: IF APPLICABLE TO THE KITCHEN
 LAYOUT PLEASE SHOW THE WATER SUPPLY LINES TO EQUIPMENT
 SUCH AS ICE MAKERS OR BEVERAGE DISPENSERS AND THE
 REQUIRED WATER HAMMER ARRESTORS AND BACKFLOW
 PREVENTERS- SECTIONS 604.9 AND 608.3 FBC P. SHOW HOW
 THE DISHWASHER WILL BE PROTECTED AGAINST BACKFLOW-
 SECTION 409.2. THE FIXTURE SCHEDULE ON SHEET P0.1 CALLS
 OUT A COMMERCIAL DISHWASHER, HOWEVER ALL DISHWASHING
 MACHINES WHETHER RESIDENTIAL OR COMMERCIAL REQUIRE SOME
 TYPE OGF BACKFLOW PREVENTION- SEE P2717.1 FBC RES.
  
 20) FAILED CORRECT THE ENERGY COMPLIANCE IECC- 2015
 FORM INDICATING THE WATER HEATER IS LESS THAN 75000
 BTUH- THE EQUIPMENT SCHEDULE INDICATES 200,000 BTUH.
 PLEASE CORRECT THE DATA AND PROVIDE THE MISSING PIPING
 SYSTEM COMPLIANCE DATA- SECTION C101.5 FBC EC. THE
 COMPLIANCE DATA IN THE CALCS INDICATES 155,000 BTUH OR
 LESS. EFFICENCY REQUIREMENT IS THE SAME PER THE TABLE,
 HOWEVER THE PLANS AND CALCS MUST MATCH. PLEASE SHOW THE
 GAS PIPING CONNECTION. SEE GAS REVIEW COMMENTS.
  
 21) FAILED. PROVIDE A ROOF DRAINAGE PLAN INCLUDING ROOF
 FLOW RATE CALCULATIONS, AND SIZING OF THE HORIZONTAL
 ROOF GUTTER AND VERTICAL LEADER SIZES PER SECTIONS
 1106.3, 1106.6 AND TABLES 1106.3 & 1106.6 FBC P.
 NARRATIVE REFERECNES SHEET A.2.0.1 WHICH IS NOT A
 COMPLETE ROOF DRAINAGE PLAN. REFER TO SECTIONS AND
 TABLES 1106.3 &1106.6 FBC P. PLEASE PROVIDE GUTTER AND
 DOWNSPOUT ATTACHMENT DETAILS- SECTIONS 1101.2 & 1102.7.
  
 22) SHEETS A10.01- A10.02 FAIR HOUSING ACT DESIGN
 MANUAL GUIDELINES:
  
 A) FAILED. PROVIDE GRAB BAR REINFORCEMENT DETAILS FOR
 ALL BATH FIXTURES- PAGE 7.33 (REQUIREMENT 6). PLEASE
 NOTE SPECIFICATION TYPE B SHOWERS REQUIRE
 REINFORCEMENTS FOR FUTURE SEATS- PAGE 7.5. NOT PROVIDED
 ON A10.01 & A-10.02.
  
 B) FAILED. INDICATE WHICH DESIGN HAS BEEN SELECTED FOR
 THE RESIDENT ROOMS- SPECIFICATION TYPE A OR TYPE B-
 PAGE 7.34. NOT PROVIDED.
  
 F) FAILED. PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE TOILETS- PAGE 7.43- 7.46. DIMENSIONS
 NOT PROVIDED.
  
 G) FAILED. A FRONT APPROACH TO THE LAVATORY SINKS IS
 SHOWN PROVIDE A DETAIL FOR INSTALLATION OF THE
 REMOVABLE LAVATORY CABINET OR BASE- PAGE 7.49. FAIR
 HOUSING SINK DETAIL NOT PROVIDED.
 23) SHEET A10.0.3:
  
 E) FAILED. THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM
 FROM THE CENTERLINE OF THE SEAT TOWARD THE SHOWER
 OPENING. PLEASE CORRECT THE INCORRECT DIMENSION SHOWN
 IN DETAIL 9/A10.03- SECTION 608.5.1. PLEASE INDICATE
 THE CENTER OF THE SHOWER SEAT ACCORDING TO THE CODE
 SECTION.
  
 26) A10.06:
  
 C) FAILED. SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF
 THE LAVATORY SINKS- SECTION 306.3.NOT PROVIDED.
  
 27) A10.0.7:
  
 B) FAILED. SHOW THE REQUIRED 30 X 60 IN. CLEARANCE
 DIAGRAMS AND DIMENSIONS AT THE SHOWERS- SECTION
 608.2.2.1. 30 IN. WIDTH DIMENSION NOT PROVIDED.
  
 C) FAILED. SHOW THE SHOWER GRAB BARS WILL BE INSTALLED
 A MAXIMUM OF 6 IN. FROM THE ADJACENT WALLS- SECTION AND
 FIGURE 608.3.2. NOT PROVIDED.
  
 E) FAILED. PROVIDE A ROLL-IN SHOWER PAN AND THRESHOLD
 DETAIL- SECTION 608.7 FBC P AND SECTION 417.5.2 FBC P.
 NOT PROVIDED.
  
 G) FAILED. SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF
 THE LAVATORY SINKS- SECTION 306.3. MINIMUM 11 IN. WIDE
 KNEE CLEARANCE NOT SHOWN- SEE FIGURE 306.3.
  
 28) FAILED. ACCESSIBLE DRINKING FOUNTAINS: PROVIDE
 DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B)
 KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, SPOUT
 LOCATIONS- SECTIONS 306, 307, & 602.2. C) COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS. SHEET LS.1.2 -
 MINIMUM 11 IN. WIDE KNEE CLEARANCE NOT SHOWN- SEE
 FIGURE 306.3. PLEASE WRITE "SPOUT HEIGHT" ON THE
 DETAIL.
  
 29) NEW COMMENT- SHEET P6.1: THE NEW SK-4 REQUIRES ?
 IN. SUPPLY LINES. PLEASE CORRECT THE ISO- SECTION 422.6
 AND TABLE 604.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-06 Cont ID  
Sent By ccole Date 2020-11-06 Time 14:03 Rev Time 0.00
Received By ccole Date 2020-11-05 Time 12:12 Sent To  
Notes
2020-11-06 14:03:261ST REVIEW FBC-2017 PLUMBING
 PERMIT-20100983
 11/6/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE SEPARATE PERMITS ARE REQUIRED FOR THE
 WATER SERVICE BACKFLOW PREVENTER, IRRIGATION SYSTEM,
 GAS PIPING SYSTEM, EMERGENCY GENERATOR, AND GREASE
 INTERCEPTOR- SECTION 107.2.1 WPB. COMPLETE PLANS AND
 SPECIFICATIONS ARE REQUIRED FOR REVIEW.
 2) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 3) SHEET LS.1.1 PLUMBING FIXTURE REQUIREMENTS SCHEDULE
 CORRECTIONS PER SECTION 403 & TABLE 403.3 FBC P.
  
 A) ROUND UP THE FRACTIONAL NUMBERS- SECTION 403.1.1 FBC
 P.
  
 B) LIST THE REQUIRED AND PROVIDED NUMBERS OF MALE AND
 FEMALE WATER CLOSETS AND LAVATORIES FOR A3, B, R4, & S
 OCCUPANCIES. PLEASE NOTE THAT SEPARATE MALE AND FEMALE
 FIXTURES ARE REQUIRED FOR A3, B AND S OCCUPANCIES-
 SECTION 403.2. UNISEX ARE PERMITTED FOR THE R4
 OCCUPANCY.
  
 C) LIST THE REQUIRED AND PROVIDED NUMBER OF SERVICE
 SINKS AND DRINKING FOUNTAINS- TABLE 403.3 FBC P.
  
 4) SHEET P2.1: PROVIDE A CLEANOUT AT THE JUNCTION OF
 THE BUILDING DRAIN AND SEWER- SECTION 708.1.3 FBC P.
  
 5) SHEETS P2.1 & P5.1: THE PLAN INDICATES ISLAND SINKS
 AND DISHWASHER BUT THE ISOMETRIC DRAWING SHOWS A VENT
 STACK INSTEAD OF AN ISLAND VENT OR AAV- SECTION 916 FBC
 P.
  
 6) P0.1, P2.1 & P5.1: A) SK-1 &SK-2 ARE MISLABELED L2
 IN THE ISOMETRIC. B) SK-3 IS MISLABELED SK-2 IN THE
 ISOMETRIC. C) SK-3 IS A 3-COMPARTMENT SINK PER THE
 FIXTURE SCHEDULE BUT IS SHOWN AS A 2-COMPARTMENT SINK
 ON THE PLAN, AND A SINGLE SINK IN THE ISO.
  
 7) P0.1 PLUMBING FIXTURE SCHEDULE: PLEASE INCLUDE THE
 SHOWER VALVES TO BE INSTALLED IN THE ACCESSIBLE AND
 NON-ACCESSIBLE SHOWERS- SECTION 608.6 FBC ACC AND 424.3
 FBC P.
  
 8) P0.1: PROVIDE AN ITEMIZED FOOD EQUIPMENT PLAN AND
 CORRELATING EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB.
 CLARIFY WHAT EQUIPMENT MAY BE INSTALLED IN THE KITCHEN
 SUCH AS A FOOD WASTE DISPOSER, ICE MAKER, BEVERAGE
 DISPENSER, COFFEE MAKER ETC.
  
 9) P0.1, P2.1 & P5.1: PROVIDE A GREASE INTERCEPTOR AND
 GREASE INTERCEPTOR CALCULATIONS FOR THE DRAINAGE FROM
 PLUMBING FIXTURES IN THE KITCHEN- REFER TO SECTIONS
 1003.1 & 1003.3.1 FBC P. REVISE THE DRAWINGS AND
 SPECIFICATIONS TO SHOW THE TYPE OF INTERCEPTOR TO BE
 INSTALLED, MAKE AND MODEL OF THE UNIT, THE LOCATION AND
 THE PLUMBING PIPING REQUIREMENTS.
  
 10) P0.1, P2.1 & P5.1: THE DRAINAGE FROM THE DISHWASHER
 AND THE 2 OR 3-COMPARTMENT SINKS SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE RECEPTOR- SECTIONS 802.1 &
 802.7 FBC P. REVISE THE DRAWINGS ACCORDINGLY, PROVIDE
 AN INSTALLATION DETAIL PER SECTION 802.2, AND ADD THE
 RECEPTORS TO THE FIXTURE SCHEDULES- SECTION 802.3.
  
 11) P0.1, P2.1 & P5.1: PROVIDE INTERCEPTORS FOR THE
 CLOTHES WASHERS PER SECTION 1003.6. REVISE THE DRAWINGS
 AND SPECIFICATIONS TO SHOW MAKES AND MODELS OF THE
 UNITS, LOCATIONS, AND THE PLUMBING PIPING REQUIREMENTS.
  
 12) P3.1 & P6.1: A) SK-3 IS MISLABELED SK-2 IN THE
 ISOMETRIC. B) SK-3 IS A 3-COMPARTMENT SINK PER THE
 FIXTURE SCHEDULE BUT IS SHOWN AS A 2-COMPARTMENT SINK
 ON THE PLAN, AND A SINGLE SINK IN THE ISO. C) P3.1
 SHOWS SK-1 & SK-2 COUNTER SINKS, P6.1 SHOWS DOUBLE SK-1
 SINKS.
  
 13) P0.1, P5.1, & P6.1: SK-4 IS MISLABELED AS SK-1 IN
 THE ISOMETRIC DRAWINGS- SECTION 107.2.1 WPB. BASED ON
 THE USE OF THE MEDICATION ROOM, A CLINICAL SINK SHALL
 BE REQUIRED IN ACCORDANCE WITH SECTIONS 422.1 & 422.6.
 REVISE THE DRAWINGS AND THE SCHEDULE ACCORDINGLY.
  
 14) P3.1 & P6.1: IF APPLICABLE TO THE KITCHEN LAYOUT
 PLEASE SHOW THE WATER SUPPLY LINES TO EQUIPMENT SUCH AS
 ICE MAKERS OR BEVERAGE DISPENSERS AND THE REQUIRED
 WATER HAMMER ARRESTORS AND BACKFLOW PREVENTERS-
 SECTIONS 604.9 AND 608.3 FBC P. SHOW HOW THE DISHWASHER
 WILL BE PROTECTED AGAINST BACKFLOW- SECTION 409.2.
  
 15) P3.1 & P6.1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SECTIONS 416.5 & 607.1.2.
  
 16) P0.1: PROVIDE A PLUMBING DEVICE SCHEDULE INDICATING
 MAKES AND MODELS AND LISTINGS OF THE RECIRCULATION
 PUMPS, BALANCING VALVES, FULL OPEN SHUTOFF VALVES,
 WATER HAMMER ARRESTORS, TRAP PRIMERS, BACKFLOW
 PREVENTERS, AND MIXING VALVES ETC.- SECTIONS 604.9,
 606, 607.1.2, 607.2.1, 608.3, 613.1 FBC P AND 107.2.1
 WPB.
  
 17) P3.1: INDICATE HOW ACCESS WILL BE PROVIDED TO THE
 BALANCING VALVES- SECTION 606.3.
  
 18) P0.1 & P3.1: SHOW WATER HEATER RELIEF VALVE PIPE,
 DRAIN PAN AND DRAIN PIPE DETAILS- SECTION 504 FBC P.
  
 19) P0.1 & P3.1: INDICATE THE RECIRCULATION PUMP
 CONTROLS SHALL START THE PUMPS BASED ON THE
 IDENTIFICATION OF A DEMAND FOR HOT WATER WITHIN THE
 OCCUPANCY, AND SHALL AUTOMATICALLY TURN OFF THE PUMP
 WHEN THE WATER IN THE CIRCULATION LOOP IS AT THE
 DESIRED TEMPERATURE AND WHEN THERE IS NO DEMAND FOR HOT
 WATER- SECTION 607.2.1 FBC P AND SECTION R403.5.1.1 FBC
 EC.
  
 20) CORRECT THE ENERGY COMPLIANCE IECC- 2015 FORM
 INDICATING THE WATER HEATER IS LESS THAN 75000 BTUH-
 THE EQUIPMENT SCHEDULE INDICATES 200,000 BTUH. PLEASE
 CORRECT THE DATA, AND PROVIDE THE MISSING PIPING SYSTEM
 COMPLIANCE DATA- SECTION C101.5 FBC EC.
  
 21) PROVIDE A ROOF DRAINAGE PLAN INCLUDING ROOF FLOW
 RATE CALCULATIONS, AND SIZING OF THE HORIZONTAL ROOF
 GUTTER AND VERTICAL LEADER SIZES PER SECTIONS 1106.3,
 1106.6 AND TABLES 1106.3 & 1106.6 FBC P.
  
 22) SHEETS A10.01- A10.02 FAIR HOUSING ACT DESIGN
 MANUAL GUIDELINES:
  
 A) PROVIDE GRAB BAR REINFORCEMENT DETAILS FOR ALL BATH
 FIXTURES- PAGE 7.33 (REQUIREMENT 6). PLEASE NOTE
 SPECIFICATION TYPE B SHOWERS REQUIRE REINFORCEMENTS FOR
 FUTURE SEATS- PAGE 7.58.
  
 B) INDICATE WHICH DESIGN HAS BEEN SELECTED FOR THE
 RESIDENT ROOMS- SPECIFICATION TYPE A OR TYPE B- PAGE
 7.34.
  
 C) THE SHOWERS SHALL NOT BE INSTALLED ADJACENT TO THE
 TOILETS- PAGE 7.44. PLEASE RE-DESIGN THE LAYOUT TO BE
 IN COMPLIANCE.
  
 D) THE SHOWER CONTROLS SHALL BE INSTALLED ON THE
 OPPOSITE WALL OF WHERE THEY ARE SHOWN ON THE PLAN- PAGE
 7.56.
  
 E) SHOW THE REQUIRED MINIMUM 36 X 36 IN. SHOWER
 DIMENSIONS- PAGE 7.58.
  
 F) PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE TOILETS- PAGE 7.43- 7.46.
  
 G) A FRONT APPROACH TO THE LAVATORY SINKS IS SHOWN
 PROVIDE A DETAIL FOR INSTALLATION OF THE REMOVABLE
 LAVATORY CABINET OR BASE- PAGE 7.49.
  
 23) SHEET A10.0.3:
  
 A) PROVIDE THE CLEAR FLOOR SPACE DIMENSION FOR THE
 WATER CLOSET MEASURED PERPENDICULAR FROM THE REAR WALL-
 SECTION 604.3.1 FBC ACC.
  
 B) SHOW THE MOUNTING HEIGHTS OF FIXTURE GRAB BARS
 MEASURED FROM THE FINISH FLOORS TO THE TOPS OF THE
 GRIPPING SURFACES- SECTION 609.4
  
 C) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SECTION 604.6.
  
 D) THE LENGTHS OF THE SHOWER GRAB BARS AS SHOWN IN
 DETAILS 2, 9, & 10 ARE NOT IN COMPLIANCE WITH FIGURE
 608.3.1 FBC ACC.
  
 E) THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL
 BE LOCATED ON THE CONTROL WALL 15 INCHES MAXIMUM FROM
 THE CENTERLINE OF THE SEAT TOWARD THE SHOWER OPENING.
 PLEASE CORRECT THE INCORRECT DIMENSION SHOWN IN DETAIL
 9- SECTION 608.5.1.
  
 F) CORRECT THE 1/8 IN. SHOWER SLOPE SHOWN IN THE DETAIL
 TO INDICATE 1/4 IN. PER FT.- SECTION 417.5.2 FBC P.
 SHOW THE LINER TURNED UP NOT LESS THAN 2? ABOVE THE
 FINISHED THRESHOLD ON ALL SIDES. PLEASE NOTE THAT
 RECESSED SHOWERS SHALL BE DEPRESSED A MINIMUM OF 2 IN.
 BELOW THE FINISHED FLOOR.
  
 24) A10.04: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS AT THE KITCHEN SINKS- SECTION 606.2 FBC ACC.
  
 25) A10.05: SHOW THE REQUIRED CLEAR FLOOR SPACE
 PARALLEL APPROACHES FOR THE WASHERS AND DRYERS- SECTION
 611.2. A) SHOW THE MEASUREMENTS TO THE BOTTOM AND TOP
 OF THE WASHER AND DRYER DOOR OPENINGS MEASURED FROM THE
 FINISHED FLOOR- SECTION 611.4 FBC ACC. C) INDICATE THE
 WASHER AND DRYER CONTROLS ARE IN COMPLIANCE WITH
 SECTIONS 309.3, 309.4 & 611.3 FBC ACC.
  
 26) A10.06:
  
 A) SHOW THE MOUNTING HEIGHTS OF FIXTURE GRAB BARS
 MEASURED FROM THE FINISH FLOORS TO THE TOPS OF THE
 GRIPPING SURFACES- SECTION 609.4 FBC ACC.
  
 B) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SECTION 604.6.
  
 C) SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF THE
 LAVATORY SINKS- SECTION 306.3.
  
 D) THE TOILET PAPER DISPENSER SHALL BE INSTALLED WITH
 THE CENTERLINE OF THE DISPENSER LOCATED BETWEEN 7 AND 9
 IN. FROM THE FRONT OF THE WATER CLOSET- SECTION 604.7.
  
 E) SEE COMMENT #13 REGARDING THE MEDICATION SINK.
 PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE SINK IN DETAIL 1- SECTIONS 212.3 AND
 606.2.
 27) A10.0.7:
  
 A) SHOW THE REQUIRED 30 X 60 IN. DIMENSIONS OF THE
 SHOWERS- SECTION AND FIGURE 608.2.2 FBC ACC.
  
 B) SHOW THE REQUIRED 30 X 60 IN. CLEARANCE DIAGRAMS AND
 DIMENSIONS AT THE SHOWERS- SECTION 608.2.2.1.
  
 C) SHOW THE SHOWER GRAB BARS WILL BE INSTALLED A
 MAXIMUM OF 6 IN. FROM THE ADJACENT WALLS- SECTION AND
 FIGURE 608.3.2.
  
 D) SHOW THE HEIGHT OF THE SHOWER CONTROL MEASURED FROM
 THE FINISHED FLOOR OF THE SHOWER- SECTION 608.5.2.
  
 E) PROVIDE A ROLL-IN SHOWER PAN AND THRESHOLD DETAIL-
 SECTION 608.7 FBC P AND SECTION 417.5.2 FBC P.
  
 F) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH
 CONTROLS- SECTION 604.6 FBC ACC.
  
 G) SHOW THE KNEE CLEARANCE AT THE UNDERSIDE OF THE
 LAVATORY SINKS- SECTION 306.3.
  
 H) THE TOILET PAPER DISPENSER SHALL BE INSTALLED WITH
 THE CENTERLINE OF THE DISPENSER LOCATED BETWEEN 7 AND 9
 IN. FROM THE FRONT OF THE WATER CLOSET- SECTION 604.7.
  
 28) ACCESSIBLE DRINKING FOUNTAINS: PROVIDE DRAWINGS AND
 DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE
 DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B) KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS-
 SECTIONS 306, 307, & 602.2. C) COMPLIANCE WITH SECTION
 307.2 PROTRUSION LIMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 10:42 Rev Time 0.00
Received By ccole Date 2021-06-28 Time 10:42 Sent To  
Notes
2021-06-28 10:44:32GREASE INTERCEPTOR REVIEWED- A SEPARATE PERMIT AND
 PLANS ARE REQUIRED FOR INSTALLATION.

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 10:40 Rev Time 0.00
Received By ccole Date 2021-06-28 Time 10:40 Sent To  
Notes
2021-06-28 10:42:10SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE
 IRRIGATION SYSTEM.

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2020-11-20 Time   Rev Time 0.00
Received By   Date 2020-11-20 Time   Sent To  
Notes
2020-11-20 08:11:01NO OBJECTION TO THE PROPOSED ENCLOSURE DETAIL, SHEET
 SP-1.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2021-05-19 Cont ID  
Sent By rmcphers Date 2021-05-19 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2021-05-19 Time 09:45 Sent To  
Notes
2021-05-19 09:45:56DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-03-08 Cont ID  
Sent By rmcphers Date 2021-03-08 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2021-03-08 Time 10:13 Sent To  
Notes
2021-03-08 10:13:29DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By rmcphers Date 2020-12-02 Time 12:10 Rev Time 0.00
Received By rmcphers Date 2020-12-02 Time 12:10 Sent To  
Notes
2020-12-02 12:11:23SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-24 Cont ID  
Sent By medwards Date 2021-06-24 Time 14:23 Rev Time 0.00
Received By medwards Date 2021-06-24 Time 14:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-10 Cont ID  
Sent By medwards Date 2021-05-10 Time 09:17 Rev Time 0.00
Received By medwards Date 2021-05-10 Time 09:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-24 Cont ID  
Sent By medwards Date 2021-02-24 Time 13:43 Rev Time 0.00
Received By medwards Date 2021-02-24 Time 13:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-13 Cont ID  
Sent By medwards Date 2020-11-13 Time 14:33 Rev Time 0.00
Received By medwards Date 2020-11-13 Time 14:33 Sent To  
Notes
2020-11-13 14:36:151) SP-1 IS A PART OF THE DESIGN OF THIS PROJECT AND FS
 471 REQUIRES THE DESIGNER TO SIGN AND SEAL THE
 DRAWINGS. BECAUSE THIS IS A DIGITAL SUBMITTAL WE NEED
 THIS TO BE A DIGITAL SIGNATURE AND SEAL. FBC 481
 2) THE CIVIL SHEETS ARE DIGITALLY SIGNED AND SEALED BY
 THE ENGINEER HOWEVER 61G15-23.004 F.A.C.REQUIRES THE
 ENGINEER TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
 3) SHEET SP-0-3 DOES NOT HAVE A DITITAL SIGNATURE OR
 SEAL FROM THE ARCHITECT. IT DOES REQUIRE A DIGITAL
 SIGNATURE AND SEAL. FS 481.
 4) SHEET S-4- THE ENGINEER DID DIGITALLY SIGN AND SEAL
 THIS SHEET BUT 61G15-23.004 F.A.C. REQUIRES THE
 ENGINEER TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
 5) THE GEOTECH REPORT IS DIGITALLY SIGNED AND SEALED BY
 THE ENGINEER BUT 61G15-23.004 F.A.C. REQUIRES THE
 ENGINEER TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2021-06-24 Cont ID  
Sent By eschneid Date 2021-06-24 Time 15:34 Rev Time 0.25
Received By eschneid Date 2021-06-24 Time 15:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-28 Cont ID  
Sent By eschneid Date 2021-04-28 Time 09:29 Rev Time 0.50
Received By eschneid Date 2021-04-28 Time 08:56 Sent To  
Notes
2021-04-28 09:30:57SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. PARKING LOT STRIPPING
 B. BASKETBALL COURT AND HARDSCAPE
 C. LANDSCAPE
 D. IRRIGATION
 E. GAZEBO
 F. BICYCLE RACKS
 G. GENERATOR
 H. DUMPSTER ENCLOSURE
 I. FENCES
 J. SIGNS
 K. SITE LIGHTING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-03 Cont ID  
Sent By eschneid Date 2021-03-03 Time 14:37 Rev Time 0.75
Received By eschneid Date 2021-03-03 Time 13:50 Sent To  
Notes
2021-03-03 14:38:26SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. PARKING LOT STRIPPING
 B. BASKETBALL COURT AND HARDSCAPE
 C. LANDSCAPE
 D. IRRIGATION
 E. GAZEBO
 F. BICYCLE RACKS
 G. GENERATOR
 H. DUMPSTER ENCLOSURE
 I. FENCES
 J. SIGNS
 K. SITE LIGHTING
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By eschneid Date 2020-11-16 Time 17:04 Rev Time 1.00
Received By eschneid Date 2020-11-16 Time 17:04 Sent To  
Notes
2020-11-16 17:05:37FAILED
  
 1) PROVIDE THE SETBACK FROM THE PROPERTY LINE TO THE
 POSTS FOR THE ROOF ALONG THE NORTH SIDE OF THE
 BUILDING. THE OUTSIDE FACE OF THE POST NEEDS TO BE AT
 LEAST 25 FEET FROM THE NORTHERN PROPERTY LINE.
  
 2) THE SETBACK FOR THE BUILDING ON SHEET SP.0.1-1 FROM
 THE NORTH PROPERTY LINE DOES NOT MATCH THE APPROVED
 SITE PLAN. ALL PLANS MUST SHOW ACCURATE CONDITIONS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. PARKING LOT STRIPPING
 B. BASKETBALL COURT AND HARDSCAPE
 C. LANDSCAPE
 D. IRRIGATION
 E. GAZEBO
 F. BICYCLE RACKS
 G. GENERATOR
 H. DUMPSTER ENCLOSURE
 I. FENCES
 J. SIGNS
 K. SITE LIGHTING
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446