Plan Review Details - Permit 20100980
Plan Review Stops For Permit 20100980
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By lcrespo Date 2020-12-03 Time 09:18 Rev Time 0.00
Received By lcrespo Date 2020-12-03 Time 09:18 Sent To  
Notes
2020-12-03 09:20:4612/03/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 12:27 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 10:31 Sent To  
Notes
2020-11-02 12:29:471ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100980
 11/2/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE GAS RISER TO INCLUDE THE 22 KW GAS
 GENERATOR WHICH IS CURRENTLY BEING REVIEWED FOR PERMIT
 ISSUANCE UNDER APPLICATION #20090018. THE SUBMITTED
 SPECS FOR THE GENERATOR INDICATE A FULL LOAD CAPACITY
 OF 327,000 BTUH- SECTION G2412.3 & G2412.4 FBC RES.
  
 2) SHOW ALL PIPE SIZES INCLUDING THE MAIN PIPE FROM THE
 METER TO THE TEE, THE MAIN RUN, AND THE BRANCHES TO THE
 APPLIANCES- SECTION G2413.1 FBC RES.
  
 3) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS
 AND THE OUTPUT PRESSURES AT EACH APPLIANCE- SECTION
 G2421.1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE
 SELECTED MODEL, INPUT AND OUTPUT PRESSURES AND PIPE
 SIZES, AND ORIFICE SIZES.
  
 4) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATORS- SECTION
 G2421.2(7).
  
 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS COMPLETE SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025. PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING
 THAT INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE
 NUMBER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-03 Cont ID  
Sent By lcrespo Date 2020-12-03 Time 09:18 Rev Time 0.00
Received By lcrespo Date 2020-12-02 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-11-02 Time   Rev Time 0.00
Received By cpuell Date 2020-10-27 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-12-03 Cont ID  
Sent By lcrespo Date 2020-12-03 Time 09:18 Rev Time 0.00
Received By lcrespo Date 2020-12-03 Time 09:18 Sent To  
Notes
2020-12-03 09:21:13THE PLUMBING FOR THE NEW TANKLESS WATER HEATER IS UNDER
 PERMIT- 20100981.

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 12:31 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 11:19 Sent To  
Notes
2020-11-02 12:32:30THE PLUMBING FOR THE NEW TANKLESS WATER HEATER IS UNDER
 PERMIT- 20100981.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By lcrespo Date 2020-12-03 Time 09:18 Rev Time 0.00
Received By lcrespo Date 2020-12-03 Time 09:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 12:33 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 10:31 Sent To  
Notes
2020-11-02 12:34:43SIGNATURE REVIEW
 11/2/2020
  
 THE CONTRACTOR OR QUALIFIER WHO PREPARED THE RISER
 DRAWING SHALL PROVIDE HIS COMPLETE SIGNATURE ON IT-
 SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H)
 & 471.025. PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING
 THAT INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE
 NUMBER.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved