2020-11-02 16:42:47 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100957 |
| 11/2/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER |
| DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES AND |
| BRANCH PIPING INSTALLED UNDER PERMIT- 01030466 AND THE |
| GAS GENERATOR INSTALLED UNDER PERMIT- 06040973. PERMIT- |
| 0130466 INDICATES A TOTAL LOAD OF 675,000 BTUH, AND |
| PERMIT- 06040973 INDICATES A LOAD OF 550,000 BTUH FOR |
| THE GENERATOR- SECTION 107.2.1 WPB AND SECTIONS G2412.3 |
| & G2412.4 FBC RES. |
| |
| A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. |
| |
| B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| G2413.4.2 FBC RES. |
| |
| C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION |
| G2421.2(7) FBC RES. |
| |
| D) THE 1 IN. SCH 40 METALLIC PIPE IS UNDERSIZED FOR THE |
| 638,000 BTUH IS UNDERSIZED ACCORDING TO SIZING TABLE |
| 402.4(2) FBC FG THAT IS LISTED ON THE RISER. |
| |
| 2) THE SURVEY SHOWS A 5 FT. CLEARANCE FROM THE |
| GENERATOR EXHAUST TO OPENINGS INTO THE HOUSE HOWEVER A |
| MINIMUM 10 FT. CLEARANCE IS REQUIRED TO MECHANICAL AND |
| GRAVITY AIR INTAKES INTO THE BUILDING- SECTION-R303.5.1 |
| FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |