Plan Review Details - Permit 20100939
Plan Review Stops For Permit 20100939
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 10:29 Sent To  
Notes
2021-04-06 10:32:47GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE PROVIDED ENGINEERING FROM "ENGINEERING EXPRESS"
 IS FOR THE GENERATOR CABINET FRAMING AND DOES NOT
 INCLUDE GENERATOR TIE DOWNS. PLEASE PROVIDE SIGNED AND
 SEALED GENERATOR TIE DOWNS FROM AN ENGINEER OR
 ARCHITECT. UNABLE TO FIND GENERATOR TIEDOWNS ON THE NEW
 DRAWINGS. GENERATOR IS SUBJECT TO WIND LOADS PLEASE
 PROVIDE TIE DOWNS TO COMPLY WITH WIND LOADS FBC 1609
 AND SHOWING THE WIND DESIGN CRITERIA FBC 1603.1.4
  
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN SUBMIT THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 BUILDING DIVISION AT CITY HALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 08:10 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 07:58 Sent To  
Notes
2021-03-09 08:10:46GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) UNABLE TO FIND GENERATOR TIEDOWNS ON THE NEW
 DRAWINGS. GENERATOR IS SUBJECT TO WIND LOADS PLEASE
 PROVIDE TIE DOWNS TO COMPLY WITH WIND LOADS FBC 1609
 AND SHOWING THE WIND DESIGN CRITERIA FBC 1603.1.4
  
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN SUBMIT THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 BUILDING DIVISION AT CITY HALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By rmcphers Date 2020-12-03 Time 16:08 Rev Time 0.00
Received By rmcphers Date 2020-12-03 Time 14:35 Sent To  
Notes
2020-12-03 15:57:10GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CONCRETE SLAB DETAILS NEED TO BE SIGNED AND SEALED
 BY THE DESIGNER.
 2) PLEASE PROVIDE SIGNED AND SEALED SITE SPECIFIC
 GENERATOR TIE DOWN DETAILS FROM AN ARCHITECT OR
 ENGINEER TO COMPLY WITH WIND LOADS FBC 1609
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN SUBMIT THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 BUILDING DIVISION AT CITY HALL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-04-21 Cont ID  
Sent By fgiaquin Date 2021-04-21 Time 20:52 Rev Time 0.00
Received By fgiaquin Date 2021-04-21 Time 14:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-04-06 Cont ID  
Sent By fgiaquin Date 2021-04-06 Time 19:58 Rev Time 0.00
Received By fgiaquin Date 2021-04-06 Time 19:01 Sent To  
Notes
2021-04-06 19:58:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SUBMIT ELECTRICAL DRAWINGS AS PER PREVIOUS PLAN
 REVIEW COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-08 Cont ID  
Sent By fgiaquin Date 2021-03-08 Time 22:46 Rev Time 0.00
Received By fgiaquin Date 2021-03-08 Time 22:30 Sent To  
Notes
2021-03-08 22:45:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE WAS NOT ADDRESSED AND NO ELECTRICAL PLANS WERE
 SUBMITTED AS INSTRUCTED. PROVIDE ACCURATE VALUE FOR
 INSTALLATION OF GENERATOR TO INCLUDE ALLL LABOR AND
 MATERIALS (GENERATOR ALSO). PROVIDE SIGNED SEALED
 ELECTRICAL DRAWINGS BY PE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  
  
  
 VALUE WAS NOT ADDRESSED AND NO ELECTRICAL PLANS WERE
 SUBMITTED AS INSTRUCTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By fgiaquin Date 2020-12-07 Time 20:14 Rev Time 0.00
Received By fgiaquin Date 2020-12-07 Time 19:13 Sent To  
Notes
2020-12-07 20:14:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SIGNED SEALED ELECTRICAL DRAWING FOR REVIEW
 BY ENGINEER. FBC 107.2.1
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By pleduc Date 2021-03-09 Time   Rev Time 0.00
Received By pleduc Date 2021-03-09 Time 09:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By pleduc Date 2020-12-03 Time   Rev Time 0.00
Received By pleduc Date 2020-12-03 Time 15:52 Sent To  
Notes
2020-12-03 16:02:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE SPECIFIC INDICATIONS OF THE EXHAUST
 LOCATION.
  
 PLEASE PROVIDE DETAILS OF THE EXHAUST LOCATION WITH
 SPECIFIC INTEREST TO THE FUMES ENTERING LIVING SPACES.
  
 PER NFPA 110 & 37
  
 NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
 NFPA 37
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE DETAILS
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-12-08 Cont ID  
Sent By ccole Date 2020-12-08 Time 07:13 Rev Time 0.00
Received By ccole Date 2020-12-08 Time 07:04 Sent To  
Notes
2020-12-08 07:15:32DIESEL GENERATOR- GAS REVIEW NOT REQUIRED.
 CCOLE
 12/8/2020

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-21 Cont ID  
Sent By fgiaquin Date 2021-04-21 Time 20:52 Rev Time 0.00
Received By fgiaquin Date 2021-04-21 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-06 Cont ID  
Sent By fgiaquin Date 2021-04-06 Time 19:58 Rev Time 0.00
Received By fgiaquin Date 2021-03-31 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-15 Cont ID  
Sent By lmarchan Date 2021-03-15 Time 14:57 Rev Time 0.00
Received By lmarchan Date 2021-03-08 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-25 Cont ID  
Sent By lmarchan Date 2021-02-25 Time 10:21 Rev Time 0.00
Received By lmarchan Date 2020-11-20 Time 18:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 11:02 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By medwards Date 2021-03-09 Time 07:12 Rev Time 0.00
Received By medwards Date 2021-03-09 Time 06:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-08 Cont ID  
Sent By medwards Date 2020-12-08 Time 11:23 Rev Time 0.00
Received By medwards Date 2020-12-08 Time 10:08 Sent To  
Notes
2020-12-08 11:23:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100939
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SURVEY SHOWING THE DIESEL GENERATOR
 LOCATION AND HOW THE GENERATOR IS ACCESSED TO REFUEL.
 FBC 107.2.1
  
 2) PLEASE SHOW THE GENERATOR LOCATION IN REFERENCE TO
 THE PROPERTY LINES AND DISTANCE FROM AIR INTAKE AND
 OPENINGS INTO BUILDINGS. FBC M 501.3.1
  
 3) PLEASE SHOW THE LOCATION OF A DAY TANK IF ONE IS TO
 BE USED. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-08 Cont ID  
Sent By ccole Date 2020-12-08 Time 07:13 Rev Time 0.00
Received By ccole Date 2020-12-08 Time 07:03 Sent To  
Notes
2020-12-08 07:16:28DIESEL GENERATOR- PLUMBING REVIEW NOT REQUIRED.
 CCOLE
 12/8/2020

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 14:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-06 Cont ID  
Sent By rmcphers Date 2021-04-06 Time 10:36 Rev Time 0.00
Received By rmcphers Date 2021-04-06 Time 10:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 08:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By rmcphers Date 2020-12-03 Time 16:09 Rev Time 0.00
Received By rmcphers Date 2020-12-03 Time 16:09 Sent To  
Notes
2020-12-03 16:10:09SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL
 SIGNATURE - YOU CAN SUBMIT THE ORIGINAL SIGNED AND
 SEALED DRAWINGS/DOCUMENTS TO THE BUILDING DIVISION AT
 CITY HALL.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-15 Cont ID  
Sent By jroach Date 2021-03-15 Time 14:55 Rev Time 0.00
Received By jroach Date 2021-03-15 Time 14:45 Sent To  
Notes
2021-03-15 14:55:59ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03.15.2021
 PERMIT NO.: 20100939
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THIS PERMIT REVIEW IS LIMITED TO THE GENERATOR ONLY.
  
 2. THE GENERATOR SHALL BE ENTIRELY SCREENED FROM VIEW
 BY AN OPAQUE WALL OR FENCE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR
 COMPARABLY DURABLE WOOD AND STEEL. SHRUBS/HEDGES SHALL
 BE PLANTED AT 2-FOOT INTERVALS.
  
 3. THE CENTREPARK COMMERCIAL PLANNED DEVELOPMENT SHALL
 BE SUBJECT TO ALL DEVELOPMENT ORDER CONDITIONS, AS
 OUTLINED IN RESOLUTION NO. 16-21, APPROVED ON FEBRUARY
 8, 2021, AND AS MAY BE AMENDED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-25 Cont ID  
Sent By jroach Date 2021-02-25 Time 08:25 Rev Time 0.00
Received By jroach Date 2021-02-25 Time 08:25 Sent To  
Notes
2021-02-25 08:26:41GENERATOR IS SHOWN IN A CITY EASEMENT. EXECUTED
 DOCUMENTS SHALL BE PROVIDED TRANSFERING OWNERSHIP OF
 THE EASEMENT.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved