Plan Review Details - Permit 20100876
Plan Review Stops For Permit 20100876
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-09 Cont ID  
Sent By ccole Date 2020-11-09 Time 08:09 Rev Time 0.00
Received By ccole Date 2020-11-06 Time 16:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 07:55 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 07:15 Sent To  
Notes
2020-11-02 07:56:022ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100876
 11/2/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW ARE MARKED
 AS PASSED OR FAILED. NOTES IN CAPS HAVE BEEN ADDED TO
 FAILED COMMENTS.
  
 1) PASSED. THE RISER INDICATES AN EXISTING METER
 HOWEVER I WAS NOT ABLE TO LOCATE PERMITS AND PLAN
 RECORDS OF EXISTING GAS PIPING AND EXISTING GAS-FIRED
 APPLIANCES. A THOROUGH REVIEW CANNOT BE COMPLETED
 WITHOUT A COMPLETE RISER DRAWING THAT INCLUDES THE
 EXISTING GAS PIPING AND EXISTING APPLIANCES- SECTIONS
 G2412.3 & G2412.4 FBC RES. PLEASE INDICATE THE DELIVERY
 GAS PRESSURE AT THE METER.
  
 A) PASSED. SHOW THE CORRECT TOTAL LOAD AND THE
 INDIVIDUAL LOADS OF THE SYSTEM- SECTIONS G2412.3,
 G2412.4, & G2413.2 FBC RES.
  
 B) PASSED. PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF
 THE PIPING FROM THE METER TO THE MOST REMOTE OUTLET,
 AND THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1
 AND G2413.4.2 FBC RES.
  
 C) FAILED. INDICATE THE INPUT GAS PRESSURE FOR THE
 GENERATOR PER MANUFACTURER'S SPECIFICATIONS AT THE
 OUTLET SIDE OF THE REGULATORS. PLEASE SUBMIT MARKED UP
 OR HIGHLIGHTED SPECS FOR THE REGULATORS SHOWING THE
 SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND
 PRESSURES, SPRING DATA, AND ORIFICE SIZE- SECTION
 G2421. SHOW THE LOCATIONS OF THE NEW REGULATORS AT THE
 NEW METER AND AT THE GENERATOR. SHOW THE INLET AND
 OUTLET PRESSURES, AND LOCATIONS OF SHUTOFF VALVES.
  
 D) FAILED. SHOW THE REQUIRED PIPE UNIONS FOR RIGID
 PIPING WITHIN 1 FT. OF EITHER SIDE THE REGULATOR-
 SECTION G2421.2(7). COMMENT NOT ADDRESSED.
  
 E) FAILED. PROVIDE THE PIPE SIZING TABLE- SEE TABLES
 G2413.4(1)- G2413.4(8). COMMENT NOT ADDRESSED.
  
 2) PASSED. THE SIGNATURE OF THE LICENSED CONTRACTOR OR
 QUALIFIER SHALL BE ON THE RISER DRAWING- SECTION
 107.2.1 & FL. STATUTES 471.003(2) (H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 17:27 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 16:56 Sent To  
Notes
2020-10-21 17:28:221ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100876
 10/21/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RISER INDICATES AN EXISTING METER HOWEVER I WAS
 NOT ABLE TO LOCATE PERMITS AND PLAN RECORDS OF EXISTING
 GAS PIPING AND EXISTING GAS-FIRED APPLIANCES. A
 THOROUGH REVIEW CANNOT BE COMPLETED WITHOUT A COMPLETE
 RISER DRAWING THAT INCLUDES THE EXISTING GAS PIPING AND
 EXISTING APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC
 RES. PLEASE INDICATE THE DELIVERY GAS PRESSURE AT THE
 METER.
  
 A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS
 OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR
 PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF
 THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED
 SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE
 MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 AND ORIFICE SIZE- SECTION G2421.
  
 D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATOR- SECTION
 G2421.2(7).
  
 E) PROVIDE THE PIPE SIZING TABLE- SEE TABLES
 G2413.4(1)- G2413.4(8).
  
 2) THE SIGNATURE OF THE LICENSED CONTRACTOR OR
 QUALIFIER SHALL BE ON THE RISER DRAWING- SECTION
 107.2.1 & FL. STATUTES 471.003(2) (H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-11-09 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-05 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 07:58 Rev Time 0.00
Received By ccole Date 2020-10-30 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-10-21 Time   Rev Time 0.00
Received By ccarvaja Date 2020-10-20 Time 12:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-11-06 Cont ID  
Sent By ccole Date 2020-11-06 Time 17:37 Rev Time 0.00
Received By ccole Date 2020-11-06 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 07:58 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 07:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 16:56 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 16:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-09 Cont ID  
Sent By ccole Date 2020-11-09 Time 08:09 Rev Time 0.00
Received By ccole Date 2020-11-06 Time 16:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-02 Cont ID  
Sent By ccole Date 2020-11-02 Time 07:58 Rev Time 0.00
Received By ccole Date 2020-11-02 Time 07:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-21 Cont ID  
Sent By ccole Date 2020-10-21 Time 17:48 Rev Time 0.00
Received By ccole Date 2020-10-21 Time 16:56 Sent To  
Notes
2020-10-21 17:49:25THE SIGNATURE OF THE LICENSED CONTRACTOR OR QUALIFIER
 SHALL BE ON THE RISER DRAWING- SECTION 107.2.1 & FL.
 STATUTES 471.003(2) (H) & 471.025.