2020-11-02 11:04:52 | 11/02/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE UPLOAD EVERY SHEET OF EACH PAGE SEPARATELY |
| INTO PROJECTDOX PER THE WPB AMENDMENT TO FBC SEC. |
| 107.2.1.3 QUALITY OF BUILDING PLANS. |
| |
| 2. A SUB ELECTRICAL PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 3. PLEASE PROVIDE IF THE APPLICABLE PAGES THAT ARE |
| STATED ON G001 AS FOLLOWS; P101, P102, P103, P104, |
| P105, AND P501 PER THE WPB AMENDMENT TO FBC SEC. |
| 107.2.1.3 QUALITY OF BUILDING PLANS. |
| |
| 4. PLEASE PROVIDE A SPECIFICATION FOR METER, SENSOR, |
| AND VALES PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. PLEASE PROVIDE THE SPECIFIC NARRATIVE TO THE UNIT OR |
| THE WORK AREA TO THE SCOPE OF WORK ON YOUR G001 PER THE |
| WPB AMENDMENTS TO THE FBC WPB A 101.2 |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |