Plan Review Details - Permit 20100816
Plan Review Stops For Permit 20100816
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-10 Cont ID  
Sent By rmcphers Date 2020-12-10 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2020-12-10 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 10:25 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 10:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 17:11 Rev Time 0.00
Received By equinone Date 2020-12-04 Time 17:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By equinone Date 2020-11-02 Time 08:44 Rev Time 0.00
Received By equinone Date 2020-11-02 Time 08:44 Sent To  
Notes
2020-11-02 08:44:39CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 1) PLEASE SPECIFY SIZE OF BREAKER AT GENERATOR.
 2) ARE ALL THE CONDUCTORS FROM GENERATOR TO TRANSFER
 SWITCH WITHIN THE SAME 1 1/4" CONDUIT? PLEASE CLARIFY
 AND SHOW ON DRAWINGS IF SEPARATED.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-12-11 Cont ID  
Sent By ccole Date 2020-12-11 Time 07:45 Rev Time 0.00
Received By ccole Date 2020-12-10 Time 16:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By ccole Date 2020-10-28 Time 13:07 Rev Time 0.00
Received By ccole Date 2020-10-28 Time 12:11 Sent To  
Notes
2020-10-28 13:07:471ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100816
 10/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PLEASE INCLUDE THE 55,000 BTUH
 BBQ GRILL IN THE EXISTING APPLIANCE LIST, AND CORRECT
 THE MAX BTUH LOAD TOTAL TO INDICATE 991,000 BTUH. THE
 GRILL WAS INCLUDED WITH THE APPROVED PLANS UNDER
 PERMIT- 15110671 - SECTIONS G2412.3, G2412.4 & G2413.2
 FBC RES.
  
 A) USING PIPE SIZING TABLE 402.4(3) FBC FG THAT YOU
 SHOW ON THE RISER, THE 1 IN. MAIN RISER PIPE IS
 UNDERSIZED FOR A 911,000 BTUH LOAD AT A TOTAL DEVELOPED
 LENGTH OF 110 FT. THE MINIMUM SIZE PER THE TABLE IS
 1-1/4 IN.
  
 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE RISER
 DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-12-11 Time   Rev Time 0.00
Received By lmarchan Date 2020-12-01 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By jleahy Date 2020-11-02 Time 11:22 Rev Time 0.00
Received By jleahy Date 2020-10-16 Time 13:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-12-11 Cont ID  
Sent By ccole Date 2020-12-11 Time 07:45 Rev Time 0.00
Received By ccole Date 2020-12-10 Time 16:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-28 Cont ID  
Sent By ccole Date 2020-10-28 Time 13:08 Rev Time 0.00
Received By ccole Date 2020-10-28 Time 12:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-10 Cont ID  
Sent By rmcphers Date 2020-12-10 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2020-12-10 Time 15:45 Sent To  
Notes
2020-12-10 15:46:02EMERGENCY RULE APPLIED 61G15ER20-4 --------------------
 -------------------------------------------------------
 ----------------------------------
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 10:25 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 10:25 Sent To  
Notes
2020-10-29 10:26:56EMERGENCY RULE APPLIED 61G15ER20-4 --------------------
 -------------------------------------------------------
 ----------------------------------
2020-10-28 13:10:51THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS RISER
 DRAWING SHALL PROVIDE HIS SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By rthermid Date 2020-10-27 Time   Rev Time  
Received By rthermid Date 2020-10-27 Time   Sent To I
Notes
***NONE***