Plan Review Details - Permit 20100815
Plan Review Stops For Permit 20100815
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-12-15 Cont ID  
Sent By ccole Date 2020-12-15 Time 12:20 Rev Time 0.00
Received By ccole Date 2020-12-15 Time 11:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-11-23 Cont ID  
Sent By ccole Date 2020-11-23 Time 09:02 Rev Time 0.00
Received By ccole Date 2020-11-23 Time 09:02 Sent To  
Notes
2020-11-23 09:10:032ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100815
 11/23/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017FBC B-
 FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS #1A & 2 FROM THE 1ST REVIEW PRINTED BELOW
 STILL EXIST.
  
 1A) THE 1-1/2 IN. PE SUPPLYING THE POOL HEATER AND
 GENERATOR IS UNDERSIZED BASED ON THE PIPE SIZING TABLE
 YOU ARE SHOWING- TABLE 402.4(21) FBC FG. ACCORDING TO
 THE TABLE A 1-1/2 IN. PE WILL SUPPLY A MAXIMUM 485,000
 BTU'S AT 125 FT. LENGTH. TABLE 402.4(21) HAS BEEN
 REMOVED FROM THE DRAWING HOWEVER THE PIPE IS STILL
 UNDERSIZED BASED ON ALL LOW PRESSURE PE PIPE SIZNG
 TABLES IN THE FBC- 17 FUEL GAS.
  
 2) THE SURVEY DRAWING IS INCORRECTLY INDICATING A 5 FT.
 CLEARANCE FROM THE GENERATOR TO WINDOW AND DOOR
 OPENINGS INTO THE BUILDING, HOWEVER A 10 FT. CLEARANCE
 IS REQUIRED- SECTION R303.5.1 FBC RES. PLEASE CORRECT
 THE DRAWING TO INDICATE THE REQUIRED 10 FT. CLEARANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By cthroop Date 2020-10-20 Time 08:08 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 07:07 Sent To  
Notes
2020-10-20 08:08:211ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100815
 10/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: THE MAIN 1 IN. GALVANIZED SUPPLY
 PIPE FROM THE METER TO THE TEE IS UNDERSIZED BASED ON A
 12 IN. W.C. SYSTEM AND THE PIPE SIZING YOU ARE SHOWING-
 TABLE 402.4(3) FBC FG. ACCORDING TO THE TABLE A 1 IN.
 PIPE WILL PROVIDE A MAXIMUM 456,000 BTU'S AT 125 FT.
 LENGTH WHICH IS THE LENGTH OF THE UNDERGROUND RUN TO
 THE POOL HEATER AND GENERATOR. THE ACTUAL DEVELOPED
 LENGTH OF THE SYSTEM HAS NOT BEEN PROVIDED, PLEASE
 PROVIDE IT- SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 PLEASE NOTE THE ORIGINAL APPROVED RISER DRAWING UNDER
 PERMIT- 20061518 SHOWED A 2 PSI SYSTEM.
  
 A) THE 1-1/2 IN. PE SUPPLYING THE POOL HEATER AND
 GENERATOR IS UNDERSIZED BASED ON THE PIPE SIZING TABLE
 YOU ARE SHOWING- TABLE 402.4(21) FBC FG. ACCORDING TO
 THE TABLE A 1-1/2 IN. PE WILL SUPPLY A MAXIMUM 485,000
 BTU'S AT 125 FT. LENGTH.
  
 2) THE SURVEY DRAWING IS INCORRECTLY INDICATING A 5 FT.
 CLEARANCE FROM THE GENERATOR TO WINDOW AND DOOR
 OPENINGS INTO THE BUILDING, HOWEVER A 10 FT. CLEARANCE
 IS REQUIRED- SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-22 Cont ID  
Sent By ccarvaja Date 2020-12-17 Time 09:28 Rev Time 0.00
Received By ccarvaja Date 2020-12-14 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 10:16 Rev Time 0.00
Received By jleahy Date 2020-11-20 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 16:37 Rev Time 0.00
Received By jleahy Date 2020-10-16 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-12-15 Cont ID  
Sent By ccole Date 2020-12-15 Time 12:20 Rev Time 0.00
Received By ccole Date 2020-12-15 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-23 Cont ID  
Sent By ccole Date 2020-11-23 Time 09:10 Rev Time 0.00
Received By ccole Date 2020-11-23 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-20 Cont ID  
Sent By ccole Date 2020-10-20 Time 08:09 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 07:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-15 Cont ID  
Sent By ccole Date 2020-12-15 Time 12:20 Rev Time 0.00
Received By ccole Date 2020-12-15 Time 11:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-20 Cont ID  
Sent By ccole Date 2020-10-20 Time 08:11 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 07:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-12-17 Cont ID  
Sent By rthermid Date 2020-12-17 Time   Rev Time 0.00
Received By rthermid Date 2020-12-17 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By rthermid Date 2020-12-03 Time   Rev Time 0.00
Received By rthermid Date 2020-12-03 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By rthermid Date 2020-10-27 Time   Rev Time  
Received By rthermid Date 2020-10-27 Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved