Plan Review Details - Permit 20100800
Plan Review Stops For Permit 20100800
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-18 Cont ID  
Sent By fgiaquin Date 2020-11-18 Time 20:09 Rev Time 0.00
Received By fgiaquin Date 2020-11-18 Time 19:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-17 Cont ID  
Sent By fgiaquin Date 2020-11-17 Time 22:23 Rev Time 0.00
Received By fgiaquin Date 2020-11-17 Time 20:43 Sent To  
Notes
2020-11-17 21:55:06PLEASE EMAIL ME DIRECTLY WITH RESUBMITTAL AND I CAN
 UPLOAD TO PROJECTDOX AND PERFORM ANOTHER REVIEW ASAP. I
 AM AWARE OF YOUR APPT WITH FPL NEXT WEEK.
  
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 PREVIOUS COMMENTS:
  
 1. SATISFIED
  
 2. PANEL "T " CURRENT NOW SHOWN AS 53.36A. OCP IN PANEL
 ON SECONDARY SIDE OF XFMR MUST BE NO LESS THAN 125% OF
 THE SECONDARY CURRENT OF THE XFMR. 53.36A X 1.25 =
 66.7A, NEXT SIZE OCP PERMITTED 70A. NEC 408.36,
 215.3(A),
  
 3. SATISFIED
  
 4. SATISFIED
  
 5. SATISFIED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-09 Cont ID  
Sent By fgiaquin Date 2020-11-09 Time 20:27 Rev Time 0.00
Received By fgiaquin Date 2020-11-07 Time 21:09 Sent To  
Notes
2020-11-09 20:27:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SERVICE CONDUCTORS ARE SHOWN WITH AN EGC. EGC
 ORIGINATES AFTER SERVICE DISCONNECTING MEAN'S OCP.
 PLEASE REMOVE EGC FROM SERVICE ENTRANCE CONDUCTORS. NEC
 250.24B
  
 2. XFMR FEEDING PANEL T MUST HAVE NO LESS THAN 125% OF
 THE SECONDARY CURRENT OF THE XFMR AT PANEL T FOR OCP.
 286A X 1.25= 357.5A. NEXT STANDARD SIZE OCP IS 400AMPS.
 NEC 408.36 450.3(B) 215.3(A)
  
 3.VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE SIGNED
 CONTRACT BY BOTH OWNER AND CONTRACTOR WITH AN ACCURATE
 VALUE. IF AN ACCURATE VALUE CANNOT BE ESTABLISHED VALUE
 MAY BE SET BY BUILDING OFFICAL. FBC 109.3
  
 4. A FIRE PUMP IS SHOWN ON THE RISER DIAGRAM. WILL PART
 OF THIS SERVICE REMAIN AND BE THE PERMANENT SERVICE FOR
 THE BUILDING? FBC 107.2.1
  
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-17 Cont ID  
Sent By fgiaquin Date 2020-11-17 Time 22:24 Rev Time 0.00
Received By fgiaquin Date 2020-11-17 Time 13:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-09 Cont ID  
Sent By fgiaquin Date 2020-11-09 Time 20:27 Rev Time 0.00
Received By fgiaquin Date 2020-10-27 Time 16:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-17 Cont ID  
Sent By fgiaquin Date 2020-11-17 Time 22:23 Rev Time 0.00
Received By fgiaquin Date 2020-11-17 Time 22:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-09 Cont ID  
Sent By fgiaquin Date 2020-11-09 Time 20:27 Rev Time 0.00
Received By fgiaquin Date 2020-11-09 Time 20:27 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved