Plan Review Details - Permit 20100709
Plan Review Stops For Permit 20100709
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By cpuell Date 2022-10-06 Time 16:31 Rev Time 0.00
Received By cpuell Date 2022-10-06 Time 16:31 Sent To  
Notes
2022-10-06 16:31:28SITE PLAN INDICATES THAT YOU ARE DOING WORK ON TWO
 SEPARATE PARCELS, 74434328090080250 (WHICH HAS THE
 ADDRESS OF 1220 OKEECHOBEE RD) AND 74434328090080230
 (WHICH HAS THE ADDRESS OF 1216 OKEECHOBEE RD) IT
 APPEARS THAT THE TWO PARCELS ARE NOT OWNED BY THE SAME
 OWNER. FOR THE WORK DONE ON 1216 OKEECHOBEE RD A
 SEPARATE PERMIT WOULD BE REQUIRED. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By rmcphers Date 2022-10-04 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-10-04 Time 10:33 Sent To  
Notes
2022-10-04 10:34:23PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By rmcphers Date 2021-10-20 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2021-10-19 Time 16:32 Sent To  
Notes
2021-10-20 10:06:33PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By rmcphers Date 2022-10-04 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-10-04 Time 10:34 Sent To  
Notes
2022-10-04 11:10:15RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING S004 SHOWS THE DESIGN WIND SPEED AT 169 MPH
 - RISK CATEGORY II DESIGN WIND SPEED NEEDS TO BE 170
 MPH - FBC WBP SECTION 120
  
 2) PLEASE SHOW IF TERMITE PREVENTION IS REQUIRED FOR
 THE SOIL BELOW THE SLAB REPAIR - FBC 1816.1.2
  
 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE EXTERIOR DOORS AND WINDOWS -
 ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC WPB 107.3.4
  
 4) ACCESSIBLE RESTROOMS = PLEASE SHOW THE TOILET PAPER
 DISPENSER LOCATION FROM THE FRONT OF THE TOILET TO THE
 CENTER OF THE DISPENSER - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 5) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE PARKING TO
 THE ACCESSIBLE ENTRY - FBC A 206.4.1 PUBLIC ENTRANCES.
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404. FBC A 206.2.1 SITE ARRIVAL
 POINTS. AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED
 WITHIN THE SITE FROM ACCESSIBLE PARKING SPACES AND
 ACCESSIBLE PASSENGER LOADING ZONES; PUBLIC STREETS AND
 SIDEWALKS; AND PUBLIC TRANSPORTATION STOPS TO THE
 ACCESSIBLE BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 6) FBC A 208.3.1 PARKING SPACES COMPLYING WITH 502 THAT
 SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING
 TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES MUST BE
 LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST 44
 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT
 COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES
 EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 7) A SEPARATE PERMIT IS REQUIRED FOR THE PARKING LOT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By rmcphers Date 2021-10-20 Time 10:08 Rev Time 0.00
Received By rmcphers Date 2021-10-19 Time 16:31 Sent To  
Notes
2021-10-20 10:08:57EXTERIOR COOLER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) CODE IN EFFECT HAS CHANGED ON 1/1/21 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE CODE IN EFFECT (2020 FBC USING
 ASCE 7-16)
 2) PLEASE SHOW THE TERMITE PREVENTION REQUIRED FOR THE
 NEW STRUCTURE - FBC 1816
 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE DESIGNER OF RECORD FBC WPB 107.3.4
 4) DRAWING S004 SHOULD SHOW THE RISK CATEGORY USED FOR
 WIND DESIGN FBC 1603.1.4 - SHOW THE CORRECT WIND SPEED
 USED FOR THE WIND DESIGN BASED ON THE RISK CATEGORY PER
 FBC WPB SECTION 120.
 5) PLEASE PROVIDE THE COOLER WALL AND ROOF PANEL
 DETAILS - DESCRIPTION OF WALL PANELS, ATTACHMENTS TO
 FOUNDATION, ATTACHMENTS OF PANEL TO PANEL ETC. TO
 COMPLY WITH THE WIND LOADS SHOWN ON DRAWING S004.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By jleahy Date 2022-10-19 Time 15:38 Rev Time 0.00
Received By jleahy Date 2022-10-18 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-18 Cont ID  
Sent By jleahy Date 2021-10-18 Time 12:03 Rev Time 0.00
Received By jleahy Date 2021-10-18 Time 11:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By parking Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By   Date 2022-09-21 Time   Rev Time 0.00
Received By bdolan Date 2022-09-21 Time 12:18 Sent To  
Notes
2022-09-21 12:18:54ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-09-20 Cont ID  
Sent By   Date 2021-09-20 Time   Rev Time 0.00
Received By bdolan Date 2021-09-20 Time 12:35 Sent To  
Notes
2021-09-20 12:42:11PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 INSTALL EMERGENCY LIGHTING WITH EXIT SIGN IN COOLER
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By ccole Date 2022-10-04 Time 17:02 Rev Time 0.00
Received By ccole Date 2022-10-04 Time 11:56 Sent To  
Notes
2022-10-04 17:04:111ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 20100709
 10/4/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-201: PROVIDE A COMPLETE GAS RISER DRAWING
 THAT INCLUDES THE PIPING TO THE NEW GAS WATER HEATER
 SHOWN ON P-002, AND ALL OTHER GAS-FIRED APPLIANCES AND
 EQUIPMENT- SEC. 107.3.5.1.3 WPB. THE REVISED RISER
 SHALL SHOW INCLUDE THE FOLLOWING INFORMATION-
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING SUPPLYING THE OVENS AND
 WATER HEATER.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 G) OUTLET PRESSURES AT REGULATORS.
 H) LOCATIONS AND TYPES OF PIPE SLEEVES.
 I) PIPE SIZING TABLES.
  
 2) P-201: PROVIDE COMBUSTION AIR AND VENTING PLANS FOR
 THE OVENS AND WATER HEATER- SECS. 304.1 & 503.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By ccole Date 2021-10-06 Time 09:43 Rev Time 0.00
Received By ccole Date 2021-10-05 Time 14:56 Sent To  
Notes
2021-10-06 09:46:071ST REVIEW FBC-2020 PLUMBING
 PERMIT-20100709
 10/5/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1-P-110: THE PLAN SHOWS NEW GAS PIPING IN THE
 BAKERY AREA. PLEASE INDICATE WHICH APPLIANCES OR
 EQUIPMENT ARE BEING SUPPLIED BY THE PIPING- SECTION
 107.2.1 WPB AND SECTION 402.1 FBC P.
  
 2) 1-P-110: PROVIDE EQUIPMENT SCHEDULES AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR ALL NEW APPLIANCES
 AND EQUIPMENT- SECTIONS 305.1 AND 601.1 FBC FG.
  
 3) 1-P-110: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL
 NEW GAS-FIRED APPLIANCES AND EQUIPMENT AND INDICATE HOW
 THE AIR WILL BE SUPPLIED- SECTION 304.1 FBC FG.
  
 4) 1-P110: 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT
 INCLUDES ALL NEW AND EXISTING GAS PIPING AND APPLIANCES
 AT THE BAKERY- SECTIONS 401.3 & 401.4 FBC FG. REFER TO
 FBC CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-19 Cont ID  
Sent By jleahy Date 2022-10-19 Time 15:38 Rev Time 0.00
Received By jleahy Date 2022-09-16 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-20 Cont ID  
Sent By rmcphers Date 2021-10-20 Time 10:11 Rev Time 0.00
Received By rmcphers Date 2021-09-03 Time 05:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 06:55 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 06:55 Sent To  
Notes
2022-10-04 06:55:362ND REVIEW FMC
 PERMIT: 20100709
  
 CODES IN EFFECT: 2020
  
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
  
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE SCOPE OF THIS PROJECT HAS CHANGED, THERE IS NO
 LONGER AN EXTERIOR FREEZER. THE SCOPE OF WORK FOR THE
 MECHANICAL NOW APPEARS TO BE AN ADDITION AND NEW
 MECHANICAL DESIGN IN EXISTING STRUCTURE.
  
 1) PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS STATING
 THAT ALL HOODS AND REFRIGERATION WILL REQUIRE SEPARATE
 PERMIT APPLICATIONS AND SEPARATE PLAN REVIEWS AND
 NEITHER WILL BE REVIEWED UNDER THIS PERMIT APPLICATION.
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FMC 312.1
  
 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE. PLEASE USE THE OCCUPANCY CLASSIFICATIONS
 PRESENTED IN FMC TABLE 403.3.1.1 THAT MOST CLOSELY
 RESEMBLES THE USE OF EACH SPACE. FMC 403.3.1.1
  
 4) SHEET M-111; PROVIDE THE DUCT SIZES FOR EACH DUCT IN
 THE SYSTEMS. FBC 107.3.5
  
 5) SHEET M-111; PLEASE SHOW THE RETURN AIR PATH FROM
 THE RETAIL SALES AREA BACK TO X-OAU-2. FBC 107.3.5
  
 6) SHEET M-111: THERE ARE 2 NOTES INDICATING -SEE UPPER
 FLOOR PLAN FOR CONTINUATION- SHEET M-112 SHOWS ONLY ONE
 BUT DOES NOT SHOW THE AREA IT SERVES. PLEASE SHOW BOTH
 SUPPLY DUCTS ON THE UPPER FLOOR PLAN AND CONTINUE THEM
 TO THE AREAS THEY SERVE. ALSO SHOW THE RETURN AIR PATH
 FROM THE UPPER FLOOR BACK TO OAU-3. FBC 107.3.5
  
 7) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF MEETS THE
 GUARD PROTECTION REQUIREMENTS IN FMC 304.11
  
 8) PLEASE SHOW THE MECHANICAL EQUIPMENT ON THE ROOF
 WILL MEET THE ACCESS REQUIREMENTS IN FMC 306.5
  
 9) PLEASE SHOW THE CONDENSATE PIPE MATERIAL AND
 TERMINATION LOCATION. FMC 307.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By medwards Date 2021-09-24 Time 14:36 Rev Time 0.00
Received By medwards Date 2021-09-24 Time 14:36 Sent To  
Notes
2021-09-24 15:06:031) PLEASE PROVIDE MECHANICAL DRAWINGS FOR THE
 MECHANICAL WORK FOR THE NEW FREEZER.
 2) PLEASE PROVIDE INFORMATION SHOWING THAT THE FACTORY
 BUILT FREEZER IS LISTED AND LABELED. FBC M 1101.2
 3) PLEASE PROVIDE THE SYSTEM REQUIREMENTS PER FBC M
 1102
 4) PROVIDE EQUIPMENT TIE DOWN INFORMATION FOR THE
 CONDENSING UNIT.
 5) PLEASE SHOW THE CONDENSATE PIPING AND TERMINATION
 LOCATION. FBC M 307
 6) PLEASE SHOW PROTECTION FROM VEHICULAR TRAFFIC FOR
 THE EXTERIOR OF THE FREEZER. FBC M 1101.3
 7) PLEASE PROVIDE INFORMATION SHOWING THAT THE NEW
 FREEZER MEETS THE ENERGY EFFICIENCY CODE. FBC EC
 C403.2.14
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By ccole Date 2022-10-04 Time 16:46 Rev Time 0.00
Received By ccole Date 2022-10-04 Time 11:56 Sent To  
Notes
2022-10-04 16:46:202ND REVIEW FBC-2020 PLUMBING
 PERMIT-20100709
 10/4/24
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AE410 DETAILS A1 & B1: SHOW THE DEPTH AND
 WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACES AT THE
 ACCESSIBLE WATER CLOSETS, LAVATORIES, AND URINAL- SECS.
 604.3, 606.2 & 605.3 FBC ACC.
  
 2) AE410- A1: THE COMPARTMENT DOOR SHALL NOT SWING INTO
 THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY- SEC.
 603.2.3 FBC ACC.
  
 3) AE410- D2: THE TILE BACKER AT THE MOP SINK SHALL
 EXTEND 4FT. ABOVE THE SINK- SEC. 1210.2.2 FBC B.
  
 4) P-111 & P-201: A GREASE INTERCEPTOR IS REQUIRED TO
 RECEIVE THE GREASE LADEN DRAINAGE FROM THE
 3-COMPARTMENT SINK, THE MOP SINK, DISHWASHER, AND ANY
 OTHER SINKS, FLOOR DRAINS ETC. DISCHARGING GREASE LADEN
 WASTE- SEC. 1003.3.1 FBC P. REVISE THE PLANS TO SHOW
 THE LOCATION OF THE INTERCEPTOR AND PLUMBING PIPING
 DETAILS- SEC. 107.2.1 WPB.
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE INTERCEPTOR AND DUE TO A RECENT
 CHANGE IN PROCESS, THE INTERCEPTOR PERMIT IS REQUIRED
 TO BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY
 PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 5) P-200: AN ACCESSIBLE SHOWER (SH-1) IS SHOWN IN THE
 FIXTURE SCHEDULE HOWEVER THE LOCATION OF THE FIXTURE
 AND PIPING DETAILS ARE NOT SHOWN IN THE PLANS- SEC.
 1`07.2.1 WPB.
  
 6) P-111 & P-201: SHOW HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE PUBLIC LAVATORIES- SEC. 419.5 FBC P.
  
 7) P-111 & P-201: THE HW RECIRCULATION LOOP IS NOT
 DESIGNED IN COMPLIANCE WITH SEC. C404.5.1 FBC EC. THE
 1/2-INCH HW PIPES TO THE LAVATORIES ARE EXCEEDING THE
 MAXIMUM ALLOWABLE 2 FT. LENGTHS FROM THE HOT WATER
 SOURCE (RECIRCULATION LINE)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-05 Cont ID  
Sent By ccole Date 2021-10-05 Time 14:55 Rev Time 0.00
Received By ccole Date 2021-10-05 Time 13:25 Sent To  
Notes
2021-10-05 14:56:021ST REVIEW FBC-2020 PLUMBING
 PERMIT-20100709
 10/5/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1-G1003: THE PLUMBING FIXTURE CALCULATIONS
 SHALL BE BASED ON THE FBC- 2020 7TH EDITION PLUMBING
 CODE. PLEASE CORRECT THE OUTDATED CODE REFERENCE AND
 REFER TO TABLE 403.1- DRINKING FOUNTAINS AND SERVICE
 SINKS ARE REQUIRED PLUMBING FIXTURES. PLEASE SHOW THE
 LOCATIONS OF THE FIXTURES ON THE DRAWINGS.
  
 2) SHEETS 1-PD110 & 1-P-110: THE PLANS DO NOT SHOW ANY
 CHANGES TO THE PLUMBING SYSTEMS EXCEPT FOR THE
 CONDENSATE PIPING HOWEVER THE APPLICATION INDICATES
 IMPROVEMENTS TO THE OFFICE/BAKERY AREAS. PLEASE CLARIFY
 IF ANY ALTERATIONS TO THE PLUMBING SYSTEMS ARE PROPOSED
 BASED ON THOSE ALTERATIONS- SECTION 107.2.1 WPB.
  
 3) 1-PD110: SHOW THE TYPES AND SIZES OF THE CONDENSATE
 PIPING- SECTION 314.2.2. FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-03 Time 14:34 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 14:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 06:59 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 06:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-24 Cont ID  
Sent By medwards Date 2021-09-24 Time 15:09 Rev Time 0.00
Received By medwards Date 2021-09-24 Time 15:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-09-30 Cont ID  
Sent By llouie Date 2022-09-30 Time   Rev Time 0.00
Received By llouie Date 2022-09-30 Time   Sent To  
Notes
2022-09-30 12:00:26** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY OF THE PROPERTY IS REQUIRED.
  
 [9/30/2021 REPEAT COMMENT: NOT ADDRESSED. NO SURVEY
 PROVIDED WITH THE LATEST RESUBMITTAL.]
  
  
 2.) SITE PLAN SHOWING AREA CALCULATIONS, PARKING
 LAYOUT, TOTAL BUILDING SQUARE FOOTAGE IS REQUIRED.
 PLEASE NOTE THAT THERE IS A MAXIMUM LOT COVERAGE,
 F.A.R. AND MINIMUM LANDSCAPE REQUIREMENTS PER SEC.
 94-174(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).
  
 [9/30/2021 REPEAT COMMENT: NOT ADDRESSED. SITE AREA
 CALCULATIONS ARE ALSO MISSING FROM THE PERMIT
 RESUBMITTAL AND SHOULD BE INCLUDED IN THE SITE PLAN.]
  
  
 3.) THE PROPOSED EXPANSION CANNOT ELIMINATE ANY PARKING
 ON SITE IF THE SITE IS CURRENTLY SHORT ON PARKING FOR
 THE USE.
  
 [9/30/2021 REPEAT COMMENT: NOT ADDRESSED. THE REQUIRED
 UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY WAS
 NOT PROVIDED, SO THE SCOPE OF WORK IS UNCLEAR AT THIS
 TIME.]
  
  
 4.) SHOW SETBACK DISTANCE OF THE PROPOSED COOLER TO THE
 PROPERTY LINE(S).
  
 [9/30/2021 REPEAT COMMENT: NOT ADDRESSED. NO SETBACK
 DIMENSIONS HAVE BEEN PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH THE ZLDRS.]
  
  
 5.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S
 OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY.
  
 [9/30/2021 REPEAT COMMENT. NOT ADDRESSED. NO SEPARATE
 AND ACTIVE LANDSCAPE PERMIT WAS FOUND IN THE SYSTEM FOR
 THIS ADDRESS. A LANDSCAPE PERMIT MUST BE SUBMITTED FOR
 ZONING TO SIGN-OFF ON THE PERMIT.]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: I
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By llouie Date 2021-09-30 Time   Rev Time  
Received By llouie Date 2021-09-30 Time   Sent To  
Notes
2021-09-30 08:16:45** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY OF THE PROPERTY IS REQUIRED.
  
 2.) SITE PLAN SHOWING AREA CALCULATIONS, PARKING
 LAYOUT, TOTAL BUILDING SQUARE FOOTAGE IS REQUIRED.
 PLEASE NOTE THAT THERE IS A MAXIMUM LOT COVERAGE,
 F.A.R. AND MINIMUM LANDSCAPE REQUIREMENTS PER SEC.
 94-174(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).
  
 3.) THE PROPOSED EXPANSION CANNOT ELIMINATE ANY PARKING
 ON SITE IF THE SITE IS CURRENTLY SHORT ON PARKING FOR
 THE USE.
  
 4.) SHOW SETBACK DISTANCE OF THE PROPOSED COOLER TO THE
 PROPERTY LINE(S).
  
 5.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE?S
 VALUE ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S
 OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT AND IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING
 MATERIAL TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: I
  
  
  
  
  
  
  