Plan Review Details - Permit 20100704
Plan Review Stops For Permit 20100704
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-12-11 Cont ID  
Sent By ccole Date 2020-12-11 Time 16:53 Rev Time 0.00
Received By ccole Date 2020-12-11 Time 15:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-12-04 Cont ID  
Sent By ccole Date 2020-12-04 Time 12:35 Rev Time 0.00
Received By ccole Date 2020-12-04 Time 09:19 Sent To  
Notes
2020-12-04 12:35:442ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 201000704
 12/4/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P103 GAS RISER:
  
 A) THE TOTAL GAS LOAD OF 1,178,000 BTUH AT A TOTAL
 DEVELOPED LENGTH OF 180 FT. WILL REQUIRE INSTALLATION
 OF A MINIMUM 1 IN. PE FROM THE METER TO THE FIRST
 BRANCH LINE TEE- TABLE 402.4(22) 2 PSI PRESSURE. THE
 RISER IS SHOWING A 3/4 IN. PIPE WHICH IS UNDERSIZED.
 B) THE 3/4 IN. SCHED. 40 GALVANIZED PIPE AT LOW
 PRESSURE OF 0.5 IN. W.C. SHOWN IMMEDIATELY AFTER REG. C
 IS UNDERSIZED TO SUPPLY THE TOTAL BRANCH LOAD OF
 478,000 BTUH AT 60 FT. TDL. ACCORDING TO TABLE 402.4(2)
 A MINIMUM 1-1/4 IN. PIPE IS REQUIRED.
 C) PLEASE CORRECT THE 6 FT. PIPE LENGTH UNDER REG. A
 SHOWN IN THE TABLE. THE RISER SHOWS A 50 FT. PIPE RUN
 TO THE COOKTOP. THE 1/2 IN. SCHEDULE 40 GALVANIZED PIPE
 AT THIS LOCATION IS UNDERSIZED- A 3/4 IN. PIPE IS
 REQUIRED PER TABLE 402.4(2). PLEASE NOTE A MINIMUM
 1-1/2 IN. SCHED. 40 PIPE IS REQUIRED AT REG. FOR A
 TOTAL BRANCH LOAD OF 550,000 BTUH LOAD AT 50 FT.- TABLE
 402.4(2). THE PIPE SIZE AT REG A IS NOT SPECIFIED
 HOWEVER AN UNDERSIZED 1/2 IN. PIPE IS SHOWN FOR THE
 400,000 BTUH POOL HEATER- A MINIMUM 1-1/4 IN. PIPE IS
 REQUIRED.
  
 2) THE ARCHITECT OF RECORD WHO PREPARED SHEET P103
 SHALL PROVIDE HIS/HER DIGITAL SEAL AND SIGNATURE ON THE
 PLAN- FLORIDA STATUTE 481.221 AND SECTION 61G1- 16.005
 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By ccole Date 2020-10-28 Time 16:00 Rev Time 0.00
Received By ccole Date 2020-10-28 Time 15:19 Sent To  
Notes
2020-10-28 16:00:341ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 201000704
 10/28/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COPIES OF PREVIOUSLY APPROVED PLAN SHEETS UNDER A
 SEPARATE PERMIT HAVE BEEN SUBMITTED WHICH ARE NOT
 ACCEPTABLE. PROVIDE ORIGINAL, UP TO DATE,
 ELECTRONICALLY SIGNED AND SEALED PLANS FOR GAS PERMIT
 REVIEW- SECTION 107.2.1 WPB, FL. STATUTE 471.025, AND
 SECTION 61G15-23.005. FAC. THE PLANS SHALL BE CORRECTED
 PER ITEMS A, B, & C PRINTED BELOW.
  
 A) SHEET P103: PROVIDE THE TOTAL LENGTH DEVELOPED
 LENGTH OF THE PIPING FROM THE METER TO THE MOST REMOTE
 OUTLET, AND THE INDIVIDUAL BRANCH LENGTHS- SECTIONS
 G2413.4.1 AND G2413.4.2 FBC RES.
  
 B) P103: SHOW THE LOCATIONS OF THE LOW PRESSURE
 REGULATOR FOR THE GRIDDLE RANGE- SECTIONS G2421.1 &
 G2421.2 FBC RES.
  
 C) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE THE REGULATORS- SECTION
 G2421.2(7).
  
 2) P103: PROVIDE THE 0.5 PSI PIPE SIZING TABLE- SECTION
 G2413.3 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE
 SELECTED MODEL, INPUT AND OUTPUT PRESSURES AND PIPE
 SIZES, AND ORIFICE SIZES- SECTION G2421.1 FBC RES.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED APPLIANCES OR PLACE A NOTE THAT THE SPECS
 WILL BE ONSITE AT TIME OF INSPECTION- SECTION 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-12-11 Time   Rev Time 0.00
Received By lmarchan Date 2020-12-09 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-12-04 Time   Rev Time 0.00
Received By lmarchan Date 2020-12-01 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-10-28 Time   Rev Time 0.00
Received By lmarchan Date 2020-10-22 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-12-11 Cont ID  
Sent By ccole Date 2020-12-11 Time 16:53 Rev Time 0.00
Received By ccole Date 2020-12-11 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-12-04 Cont ID  
Sent By ccole Date 2020-12-04 Time 12:35 Rev Time 0.00
Received By ccole Date 2020-12-04 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-28 Cont ID  
Sent By ccole Date 2020-10-28 Time 16:00 Rev Time 0.00
Received By ccole Date 2020-10-28 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-11 Cont ID  
Sent By ccole Date 2021-05-11 Time 16:55 Rev Time 0.00
Received By ccole Date 2020-12-11 Time 15:26 Sent To  
Notes
2020-12-11 17:02:23SIGNATURE REVIEW
 12/11/2020
  
 1) THE ARCHITECT OF RECORD WHO PREPARED SHEET P103
 SHALL PROVIDE HIS/HER DIGITAL SEAL AND SIGNATURE ON THE
 PLAN- FLORIDA STATUTE 481.221 AND SECTION 61G1- 16.005
 FLORIDA ADMINISTRATIVE CODE.
 IF THE AOR CANNOT PROVIDE A DIGITALLY SIGNED AND SEALED
 PLAN SHEET, A SIGNED AND SEALED PAPER PLAN SHEET CAN BE
 SUBMITTED TO THE WPB BUILDING DEPT FOR PERMIT ISSUANCE.
 PLEASE ATTACH A PLAN REVIEW REQUEST FORM WITH THE
 DESCRIPTION OF INFORMATION FILLED OUT TO CLARIFY THE
 PURPOSE OF THE SUBMITTAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-04 Cont ID  
Sent By ccole Date 2020-12-04 Time 09:59 Rev Time 0.00
Received By ccole Date 2020-12-04 Time 09:19 Sent To  
Notes
2020-12-04 09:59:51SIGNATURE REVIEW
 12/4/2020
  
 1) THE ARCHITECT OF RECORD WHO PREPARED SHEET P103
 SHALL PROVIDE HIS/HER DIGITAL SEAL AND SIGNATURE ON THE
 PLAN- FLORIDA STATUTE 481.221 AND SECTION 61G1- 16.005
 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By ccole Date 2020-10-28 Time 16:02 Rev Time 0.00
Received By ccole Date 2020-10-28 Time 15:19 Sent To  
Notes
2020-10-28 16:04:20SIGNATURE REVIEW
 PERMIT-20100704
 10/28/2020
  
 COPIES OF PREVIOUSLY APPROVED PLAN SHEETS UNDER A
 SEPARATE PERMIT HAVE BEEN SUBMITTED WHICH ARE NOT
 ACCEPTABLE. PROVIDE ORIGINAL, UP TO DATE,
 ELECTRONICALLY SIGNED AND SEALED PLANS FOR GAS PERMIT
 REVIEW- SECTION 107.2.1 WPB, FL. STATUTE 471.025, AND
 SECTION 61G15-23.005. FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved