Plan Review Stops For Permit 20100692 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2020-11-07 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-11-07 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-11-07 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2020-10-30 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-30 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-30 |
Time |
09:03 |
Sent To |
|
|
Notes |
2020-10-30 09:10:36 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | ASBESTOS REVIEW DENIED: | | | | ASBESTOS REQUIREMENTS: | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS?AND?SERVICE | | S/ENVIRONMENTAL?HEALTH/AIR?QUALITY/ASBESTOS?DEMOLITION? | | RENOVATION.HTML | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2020-10-22 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-22 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-22 |
Time |
11:03 |
Sent To |
|
|
Notes |
2020-10-22 15:39:22 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | ASBESTOS REVIEW DENIED: | | | | ASBESTOS REQUIREMENTS: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-11-07 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-11-07 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-11-07 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-10-30 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-30 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-30 |
Time |
09:02 |
Sent To |
|
|
Notes |
2020-10-30 09:20:15 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1) EXTERIOR WINDOW AND DOOR REMOVAL SHALL NOT TAKE | | PLACE UNDER THIS DEMO PERMIT. | | 2) NEW FLOORING IS NOT PART OF THIS PERMIT. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-22 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-22 |
Time |
15:44 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-22 |
Time |
11:03 |
Sent To |
|
|
Notes |
2020-10-22 15:49:15 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2.1, PLEASE PROVIDE PRODUCT APPROVALS FOR | | NEW EXTERIOR WINDOWS AND DOORS. | | | | 2) FBC B 107.2.1, PLEASE PROVIDE THE FOLLOWING | | INFORMATION FOR NEW FLOORING SYSTEM: | | (PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | OR UL 723. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-27 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-10-27 |
Time |
07:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-10-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2020-10-21 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2020-10-21 |
Time |
14:52 |
Sent To |
|
|
Notes |
2020-10-21 14:56:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL | | PERMIT APPLICATION TO [email protected] AND CC | | [email protected] SO I RECEIVE IT ALSO. WHEN THIS EMAIL | | IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN | | REVIEW. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2020-10-16 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-10-16 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-10-16 |
Time |
16:44 |
Sent To |
|
|
Notes |
2020-10-16 16:45:03 | FIRE PROVISO: | | | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-11-07 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-11-07 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-11-05 |
Time |
07:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-10-30 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-30 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-29 |
Time |
09:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-10-22 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-22 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-15 |
Time |
15:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2020-10-22 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-22 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-22 |
Time |
11:03 |
Sent To |
|
|
Notes |
2020-10-22 15:37:08 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | NFIP REVIEW: | | | | ELEVATION CERTIFICATE NOT REQUIRED. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-10-22 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-10-22 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-10-22 |
Time |
11:03 |
Sent To |
|
|
Notes |
|
|