Plan Review Details - Permit 20100610
Plan Review Stops For Permit 20100610
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-20 Cont ID  
Sent By rmcphers Date 2020-11-20 Time 11:14 Rev Time 0.00
Received By rmcphers Date 2020-11-20 Time 11:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 12:54 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 12:54 Sent To  
Notes
2020-11-19 12:56:54FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) THE PROVIDED FLOOR PLAN NEEDS TO INDICATE THE
 LOCATION OF THE FLOORING AND TYPE OF FLOORING TO BE
 INSTALLED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rmcphers Date 2020-10-27 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2020-10-27 Time 14:40 Sent To  
Notes
2020-10-27 14:48:19FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE TYPE OF
 FLOORING TO BE INSTALLED AND THE LOCATION OF THE
 FLOORING TO BE INSTALLED.
  
 2) THE FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 3). PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ([email protected])
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2020-11-12 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-27 Cont ID  
Sent By rmcphers Date 2020-10-27 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2020-10-14 Time 10:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-10-27 Cont ID  
Sent By rmcphers Date 2020-10-27 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2020-10-27 Time 14:48 Sent To  
Notes
***NONE***