Plan Review Details - Permit 20100549
Plan Review Stops For Permit 20100549
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-17 Cont ID  
Sent By mcphers Date 2020-12-17 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-11-24 Cont ID  
Sent By rmcphers Date 2020-11-24 Time 15:43 Rev Time 0.00
Received By rmcphers Date 2020-11-24 Time 15:43 Sent To  
Notes
2020-11-24 15:46:52GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A SLAB DETAIL DRAWING WITHOUT THE
 CITY APPROVAL STAMP ALREADY ATTACHED FROM A DIFFERENT
 PERMIT.
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 09:52 Sent To  
Notes
2020-10-29 10:18:04GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW GENERATOR EXHAUST TO BE 10' FROM
 BUILDING OPENINGS TO COMPLY WITH FBC R303.5.1
 2) GAS TANK DOCUMENTS IN PROJECTDOX = PLEASE PROVIDE A
 LOCATION FOR THE TANK ON THE SURVEY - PLEASE PROVIDE
 SIGNED AND SEALED TIEDOWN DRAWINGS FROM AN ARCHITECT OR
 ENGINEER TO COMPLY WITH THE WIND LOADS FBC R301.1
 3) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 16:34 Rev Time 0.00
Received By jleahy Date 2020-12-04 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By equinone Date 2020-10-30 Time 16:38 Rev Time 0.00
Received By equinone Date 2020-10-30 Time 16:38 Sent To  
Notes
2020-10-30 16:50:50CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 1) PLEASE SPECIFY SIZE OF BREAKER AT GENERATOR.
 2) ARE ALL THE CONDUCTORS FROM GENERATOR TO TRANSFER
 SWITCH WITHIN THE SAME 1 1/4" CONDUIT? PLEASE CLARIFY
 AND SHOW ON DRAWINGS IF SEPARATED.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-11-23 Cont ID  
Sent By ccole Date 2020-11-23 Time 13:30 Rev Time 0.00
Received By ccole Date 2020-11-23 Time 12:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By ccole Date 2020-10-27 Time 14:12 Rev Time 0.00
Received By ccole Date 2020-10-27 Time 13:06 Sent To  
Notes
2020-10-27 14:15:401ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100549
 10/27/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) LP GAS TANK AND INSTALLATION SPECS HAVE BEEN
 INCORRECTLY SUBMITTED. PLEASE PROVIDE A NATURAL GAS
 SUBMITTAL PACKAGE THAT INCLUDES THE GENERATOR FLEX
 CONNECTOR, REGULATOR, AND PIPE SIZING TABLES- SECTION
 107.2.1 WPB.
  
 2) GAS RISER DRAWING: PLEASE INCLUDE THE 22,000 BTUH
 DRYER IN THE EXISTING APPLIANCE LIST, AND CORRECT THE
 BTUH LOAD TOTAL TO INDICATE 869,000 BTUH. THE DRYER WAS
 INCLUDED WITH THE APPROVED PLANS UNDER PERMIT-
 99100191- SECTIONS G2412.3, G2412.4 & G2413.2 FBC RES.
  
 A) INDICATE THE RISER PIPE SIZES AT THE METER- SECTION
 G2413.1 FBC RES. PLEASE NOTE THE PIPE SIZING TABLE
 402.4(3) FBC FG YOU SHOW ON THE RISER INDICATES A
 MINIMUM 1-1/4 IN. MAIN SUPPLY PIPE IS REQUIRED FOR A
 869,000 BTUH SYSTEM AT A TOTAL DEVELOPED LENGTH OF 110
 FT.
  
 B) A REGULATOR AT THE GENERATOR IS REQUIRED TO DROP THE
 PRESSURE TO 3.5- 7 IN. W.C PER THE GENERATOR SPECS-
 SECTION 2421.1 FBC RES. SHOW THE REGULATOR ON THE RISER
 AND THE REQUIRED PIPE UNIONS PER SECTION 2421.2(7) FBC
 RES. SUBMIT MANUFACTURER?S SPECIFICATIONS MARKED UP OR
 HIGHLIGHTED TO SHOW THE SELECTED MODEL, INPUT AND
 OUTPUT PIPE SIZE AND PRESSURE, AND ORIFICE SIZE.
  
 2) CORRECT THE SURVEY DRAWING TO INDICATE A 10 FT.
 CLEARANCE FOR THE GENERATOR TO MECHANICAL AND GRAVITY
 AIR INTAKES (OPERABLE WINDOWS AND DOORS) INTO THE
 RESIDENCE- SECTION R303.5.1 FBC RES.
  
 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2020-12-11 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 16:39 Rev Time 0.00
Received By jleahy Date 2020-11-20 Time 14:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-30 Cont ID  
Sent By equinone Date 2020-10-30 Time 16:42 Rev Time 0.00
Received By equinone Date 2020-10-16 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-23 Cont ID  
Sent By ccole Date 2020-11-23 Time 13:30 Rev Time 0.00
Received By ccole Date 2020-11-23 Time 12:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-27 Cont ID  
Sent By ccole Date 2020-10-27 Time 14:15 Rev Time 0.00
Received By ccole Date 2020-10-27 Time 13:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-17 Cont ID  
Sent By rmcphers Date 2020-12-17 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-24 Cont ID  
Sent By rmcphers Date 2020-11-24 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2020-11-24 Time 15:47 Sent To  
Notes
2020-11-24 15:47:32SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 10:18 Sent To  
Notes
2020-10-29 10:19:10SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By rthermid Date 2020-12-03 Time   Rev Time 0.00
Received By rthermid Date 2020-12-03 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rthermid Date 2020-10-27 Time   Rev Time  
Received By rthermid Date 2020-10-27 Time   Sent To I
Notes
2020-10-27 10:28:23ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10/27/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE THE SETBACKS OF THE GENERATOR TO THE
 SIDE PROPERTY LINE. MECHANICAL EQUIPMENT CANNOT
 ENCROACH MORE THAN 4 FEET INTO A REQUIRED SETBACK. THE
 REQUIRED SETBACK IS 8 FEET, THIS MEANS THE GENERATOR
 MUST BE SETBACK A MINIMUM OF 4 FEET FROM THE SIDE
 PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved