Plan Review Details - Permit 20100518
Plan Review Stops For Permit 20100518
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By rmcdouga Date 2020-11-16 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2020-11-16 Time 07:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rmcdouga Date 2020-10-27 Time 10:06 Rev Time 0.00
Received By rmcdouga Date 2020-10-27 Time 10:06 Sent To  
Notes
2020-10-27 10:16:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE THE WIND LOAD DESIGN DATA ON THE PLANS. FBC
 1609
  
 2) SUBMIT SIGNED AND SEALED CALCULATIONS FOR SIGN
 ANCHORING REQUIREMENTS FROM A FLORIDA LICENSED
 ENGINEER. FBC 3107 & FS 471
  
 3) THE VALUE FOR THIS SIGN APPEARS TO BE TOO LOW.
 SUBMIT A COPY OF THE CONTRACT TO VERIFY THE COST OF THE
 SIGN, INSTALLATION, DESIGN, ENGINEERING, LABOR,
 MATERIAL, OVERHEAD AND PROFIT. FBC 109.3
  
 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-05 Cont ID  
Sent By fgiaquin Date 2020-11-05 Time 20:28 Rev Time 0.00
Received By fgiaquin Date 2020-11-05 Time 19:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-04 Cont ID  
Sent By fgiaquin Date 2020-11-04 Time 20:48 Rev Time 0.00
Received By fgiaquin Date 2020-11-04 Time 20:32 Sent To  
Notes
2020-11-04 20:48:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN APPEARS TO BE FOR 120V CIRCUIT, KW METER,
 TIMECLOCK, AND DISCONNECT. PLAN IS SIGNED BY A LICENSED
 CONTRACTOR BUT NEEDS TO BE SUBMITTED AS A SEPARATE
 ELECTRICAL PERMIT. FBC 105.1 FBC 107.2.1
  
 WORK SHOWN IS OUT OF SCOPE OF LICENSE FOR ES SIGN
 CONTRACTOR.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW OF SIGN, SHOWING
 WIRING DIAGRAM FOR XFMR AND SIGN. AS PER LAST PLAN
 REVIEW COMMENTS.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By fgiaquin Date 2020-10-27 Time 20:55 Rev Time 0.00
Received By fgiaquin Date 2020-10-27 Time 20:30 Sent To  
Notes
2020-10-27 20:55:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. . FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-16 Cont ID  
Sent By rmcdouga Date 2020-11-16 Time 07:22 Rev Time 0.00
Received By rmcdouga Date 2020-11-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-27 Cont ID  
Sent By fgiaquin Date 2020-10-27 Time 20:55 Rev Time 0.00
Received By fgiaquin Date 2020-10-09 Time 14:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-05 Cont ID  
Sent By fgiaquin Date 2020-11-05 Time 20:28 Rev Time 0.00
Received By fgiaquin Date 2020-11-05 Time 20:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rmcdouga Date 2020-10-27 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2020-10-27 Time 10:16 Sent To  
Notes
2020-10-27 10:16:59ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE PAPER VERSION OF DRAWINGS WITH
 THE ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-20 Cont ID  
Sent By rthermid Date 2020-10-20 Time   Rev Time  
Received By rthermid Date 2020-10-20 Time   Sent To I
Notes
***NONE***