Plan Review Details - Permit 20100483
Plan Review Stops For Permit 20100483
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-10-14 Cont ID  
Sent By cpuell Date 2020-10-14 Time 13:10 Rev Time 0.00
Received By cpuell Date 2020-10-14 Time 13:09 Sent To  
Notes
2020-10-30 09:14:18ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW STATUS: DENIED.
  
 1) PLEASE PROVIDE ELECTRICAL DRAWINGS FOR THIS SPACE.
 INCLUDE FLOOR LAYOUT INDICATING THE LOCATION OF NEW AND
 EXISTING PANELS, LOCATION OF NEW EQUIPMENT,
 DISCONNECTING MEANS, HOME RUNS TO PANELBOARDS AND ANY
 OTHER NEW EQUIPMENT SUCH AS RECEPTACLES, AND LIGHTING
 FIXTURES.
  
 2) PLEASE PROVIDE A BASIC POWER RISER DIAGRAM
 INDICATING ALL THE PANELBOARDS SERVING THIS TENANT--
 EITHER INSTALLED NEW OR EXISTING. INCLUDE RATINGS OF
 PANELBOARDS, DISCONNECTING MEANS. INCLUDE THE SIZE AND
 TYPES OF THE FEEDERS TO THESE PANELBOARDS, INCLUDING
 SIZE AND TYPE OF CONDUITS, AND GROUND WIRES.
  
 3) PLEASE PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; FBC 107.3.5
  
 4) PLEASE PROVIDE LOAD CALCULATIONS FOR ALL PANELBOARDS
 AFFECTED BY THIS PROJECT. INCLUDE NEW AND EXISTING
 LOADS.
  
  
  
  
  
  
  
  
  
  
  
2020-10-14 13:10:39CHANGED FROM 1700 45TH ST # 1742 TO 1742 45TH ST

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By rmcphers Date 2020-12-04 Time 07:52 Rev Time 0.00
Received By rmcphers Date 2020-12-04 Time 07:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-02 Cont ID  
Sent By rmcphers Date 2020-11-02 Time 09:12 Rev Time 0.00
Received By rmcphers Date 2020-11-02 Time 09:12 Sent To  
Notes
2020-11-02 09:15:46ROOF TOP FANS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOF TOP FANS ARE SUBJECT TO WIND LOADS - PLEASE
 SHOW THE WIND DESIGN CRITERIA USED FOR THE WIND DESIGN
 PER FBC 1603.1.4
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 14:16 Rev Time 0.00
Received By equinone Date 2020-12-04 Time 14:16 Sent To  
Notes
2020-12-04 14:18:37CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 SAME COMMENTS AS FIRST REVIEW. NONE OF THEM HAVE BEEN
 ADDRESSED.
  
 1) PLEASE PROVIDE ELECTRICAL DRAWINGS SHOWING THE
 FOLLOWING COMPONENTS OF THE ELECTRICAL DISTRIBUTION
 SYSTEM AS THEY APPLY TO THIS PROJECT. FBC 107.2
  
 2) ELECTRICAL FLOOR PLAN SHOWING THE LOCATION OF ALL
 NEW ELECTRICAL EQUIPMENT, LIGHTING FIXTURES,
 RECEPTACLES, HOME RUNS TO THE PANELS, EXISTING AND NEW
 PANELBOARDS, SYMBOLS. FBC 107.2
 POWER RISER DIAGRAM (CAN BE PARTIAL), INCLUDING
 EXISTING AND NEW PANELBOARDS, FEEDER AND CONDUIT SIZES,
 GROUND CONDUCTORS, DISCONNECTING MEANS, TRANSFORMERS
 AFFECTED BY THIS WORK. FBC 107.2
 LOAD CALCULATIONS OF AFFECTED PANELBOARDS SHOWING
 EXISTING AND NEW LOADS (NEC 220, NEC 220.87)
 PANEL SCHEDULES OF ALL AFFECTED PANELBOARDS SHOWING NEW
 AND EXISTING CIRCUITS, OVERCURRENT DEVICES, CONDUCTOR
 SIZES, RATING OF PANELBOARDS. FBC 107.2
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By equinone Date 2020-10-30 Time 08:27 Rev Time 0.00
Received By equinone Date 2020-10-30 Time 08:27 Sent To  
Notes
2020-10-30 10:11:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PLEASE PROVIDE ELECTRICAL DRAWINGS SHOWING THE
 FOLLOWING COMPONENTS OF THE ELECTRICAL DISTRIBUTION
 SYSTEM AS THEY APPLY TO THIS PROJECT. FBC 107.2
  
 ELECTRICAL FLOOR PLAN SHOWING THE LOCATION OF ALL NEW
 ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, RECEPTACLES,
 HOME RUNS TO THE PANELS, EXISTING AND NEW PANELBOARDS,
 SYMBOLS. FBC 107.2
 POWER RISER DIAGRAM (CAN BE PARTIAL), INCLUDING
 EXISTING AND NEW PANELBOARDS, FEEDER AND CONDUIT SIZES,
 GROUND CONDUCTORS, DISCONNECTING MEANS, TRANSFORMERS
 AFFECTED BY THIS WORK. FBC 107.2
 LOAD CALCULATIONS OF AFFECTED PANELBOARDS SHOWING
 EXISTING AND NEW LOADS (NEC 220, NEC 220.87)
 PANEL SCHEDULES OF ALL AFFECTED PANELBOARDS SHOWING NEW
 AND EXISTING CIRCUITS, OVERCURRENT DEVICES, CONDUCTOR
 SIZES, RATING OF PANELBOARDS. FBC 107.2
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-20 Cont ID  
Sent By pleduc Date 2020-10-20 Time   Rev Time 0.00
Received By pleduc Date 2020-10-20 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 14:17 Rev Time 0.00
Received By equinone Date 2020-11-24 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-02 Cont ID  
Sent By rmcphers Date 2020-11-02 Time 09:20 Rev Time 0.00
Received By rmcphers Date 2020-10-15 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-01 Cont ID  
Sent By medwards Date 2020-12-01 Time 07:48 Rev Time 0.00
Received By medwards Date 2020-12-01 Time 07:48 Sent To  
Notes
2020-12-01 07:48:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100483
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE NEW HOOD WILL BE INSTALLED IN
 THE LOCATION OF THE CURRENT RTU RETURN DUCT. PLEASE
 PROVIDE A DRAWING WITH THE EXISTING DUCT WORK LAYOUT
 AND THE HOOD. THIS MAY REQUIRE A MECHANICAL PERMIT IF
 ANY DUCTWORK IS REMOVED OR MOVED TO ALLOW THE
 INSTALLATION OF THE NEW HOOD, GREASE DUCT AND MAKEUP
 AIR. FBC 107.2.1
  
 2) MECHANICAL HOOD DRAWINGS SHEET 1 OF 5 MENTIONS THAT
 THE BUILDING HVAC SYSTEM SHALL PROVIDE MORE THAN 414
 CFM TO INSURE OVERALL BUILDING BALANCE IS POSITIVE.
 PLEASE OBTAIN A MECHANICAL PERMIT FOR THE ABOVE WORK
 AND PROVIDE MECHANICAL SHEETS WITH THAT PERMIT SHOWING
 THE AIR BALANCE, INCLUDING THE BATH EXHAUST FANS. FBC M
 508.1.2
  
 3) PLEASE PROVIDE THE SPECIFICATIONS FOR THE MUA AND
 SHOW THAT THE MAKE UP AIR TEMPERATURE DIFFERENCE DOES
 NOT EXCEED 10 DEG.F FBC M508.1.1
  
 4) PLEASE PROVIDE THE SPECIFICATIONS FOR THE COOKING
 EQUIPMENT LOCATED UNDER THE HOOD. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By medwards Date 2020-10-27 Time 14:08 Rev Time 0.00
Received By medwards Date 2020-10-27 Time 14:08 Sent To  
Notes
2020-10-27 14:08:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100483
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION INDICATES THERE ARE 2 HOODS
 BEING INSTALLED. THE DRAWINGS AND SPEC SHEETS ONLY SHOW
 HOOD 1. PLEASE BE CONSISTENT, IS THERE ONLY 1 HOOD OR
 IS THERE 2? FBC 107.2
  
 2) PLEASE PROVIDE A COMPLETE CODE ANALYSIS FOR THIS
 TENANT SPACE. IS THIS A CHANGE OF USE? BFC 107.2
  
 3) PLEASE PROVIDE A COMPLETE FLOOR PLAN FOR THE TENANT
 SPACE. FBC 107.2
  
 4) IS THERE A MASTER PERMIT FOR THIS PROJECT?
  
 5) PLEASE SHOW THAT THE MAKE UP AIR FOR THE HOOD MEETS
 FBC M 508.1 FOR MAKE UP AIR AND FBC M 508.1.1 FOR MAKE
 UP AIR TEMPERATURE.
  
 6) PLEASE PROVIDE THE DESIGN SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE FOR THIS
 FACILITY. FBC M 508.1.2
  
 7) PLEASE PROVIDE A ROOF DRAWING SHOWING THE HOOD
 EXHAUST OUTLET MEETS FBC M 501.3.1
  
 8) PLEASE SHOW ON THE ROOF DRAWING THE LOCATION OF THE
 MAKEUP AIR UNIT AND THAT IT MEETS FBC M 401.4
  
 9) PLEASE SHOW THAT THE HOOD TERMINATION AND MAKE UP
 AIR UNITS WILL MEET FBC M 304.11
  
 10) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF HAS
 MEANS OF ACCESS. FBC M 306.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By rmcphers Date 2020-12-04 Time 07:53 Rev Time 0.00
Received By rmcphers Date 2020-12-04 Time 07:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-30 Cont ID  
Sent By equinone Date 2020-10-30 Time 08:17 Rev Time 0.00
Received By equinone Date 2020-10-30 Time 08:16 Sent To  
Notes
***NONE***