Plan Review Details - Permit 20100464
Plan Review Stops For Permit 20100464
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By cpuell Date 2020-11-17 Time 09:45 Rev Time 0.00
Received By cpuell Date 2020-11-17 Time 09:45 Sent To  
Notes
2020-11-17 09:45:43PLEASE EMAIL [email protected] TO DISCUSS ADDRESSING
 OPTIONS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-12-11 Cont ID  
Sent By rmcphers Date 2020-12-11 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2020-12-11 Time 14:30 Sent To  
Notes
2020-12-11 14:30:48PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By rmcphers Date 2020-10-26 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2020-10-26 Time 11:11 Sent To  
Notes
2020-10-26 11:12:21PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-15 Cont ID  
Sent By rmcphers Date 2020-12-15 Time 08:10 Rev Time 0.00
Received By rmcphers Date 2020-12-11 Time 14:06 Sent To  
Notes
2020-12-11 14:29:50BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) (I MISSED THIS THE FIRST REVIEW) DOOR AT ACCESSIBLE
 RESTROOM WIDTH 2/8 DOESN'T WORK FBC 404.2.3 CLEAR
 WIDTH. DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32
 INCHES (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES.
 2) ACCESSIBLE RESTROOM FBC ACCESSIBILITY = MIRROR
 HEIGHT SHOULD STATE TO THE "BOTTOM OF THE REFLECTION"
 603.3 - SHOW TOILET PAPER DISPENSER DISTANCE (7" TO 9"
 TO THE CENTER OF THE DISPENSER) FROM TOILET 604.7 -
 GRAB BAR HEIGHT SHOULD STATE MAX TO TOP OF THE GRAB BAR
 609.4 (DRAWING A2 ONE OF THE DETAILS SHOWS HEIGHT AT
 36" TO THE CENTER OF THE GRAB THIS DOES NOT COMPLY WITH
 THE MAX. HEIGHT TO THE TOP OF THE GRAB BAR) - DOOR
 CANNOT SWING INTO FIXTURE CLEAR FLOOR SPACE 603.2.3
 (EXCEPTION (2).WHERE THE TOILET ROOM OR BATHING ROOM IS
 FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE.(SHOW THIS CLEAR FLOOR SPACE).
 3) STOREFRONT DRAWINGS FROM THOMAS TWOMEY P.E. UNABLE
 TO DETERMINE IF SEALED BY THE ENGINEER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN DROP OFF THE ORIGINAL
 SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE FRONT DESK
 IN THE BUILDING DEPT. AT THE CITY HALL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By rmcphers Date 2020-10-26 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2020-10-26 Time 09:57 Sent To  
Notes
2020-10-26 11:10:16BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE HOURLY FIRE RATING FOR THE WALLS.
 2) PLEASE SHOW THE CEILING HEIGHT.
 3) PLEASE SHOW THE NEW SPACE SQUARE FOOTAGE.
 4) PLEASE SHOW THE OCCUPANT LOAD FBC 1004
 5) PLEASE SHOW THE OCCUPANCY CLASSIFICATION FBC CHAPTER
 3
 6) PLEASE SHOW THE USE FOR EACH ROOM.
 7) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE FBC
 CHAPTER 6
 8) THE ADDED EXTERIOR DOORS CANNOT SWING INTO THE
 PUBLIC RIGHT-OF-WAY FBC 3202.2 (PLEASE PROVIDE A SURVEY
 THAT SHOWS THAT THIS DOES NOT OCCUR).
 9) PLEASE PROVIDE THE FRONT PAGES FOR THE DOOR PRODUCT
 APPROVAL (FLORIDA STATE FRONT PAGES) FL18413.
 10) ACCESSIBLE RESTROOM FBC ACCESSIBILITY = MIRROR
 HEIGHT SHOULD STATE TO THE BOTTOM OF THE REFLECTION
 603.3 - SHOW TOILET PAPER DISPENSER DISTANCE FROM
 TOILET 604.7 - GRAB BAR HEIGHT SHOULD STATE MAX TO TOP
 OF GRAB BAR 609.4 - DOOR CANNOT SWING INTO FIXTURE
 CLEAR FLOOR SPACE 603.2.3 - SHOW THE REAR GRAB BAR TO
 COMPLY WITH 604.5.2 REAR WALL. THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES (915 MM) LONG MINIMUM AND EXTEND
 FROM THE CENTERLINE OF THE WATER CLOSET 12 INCHES (305
 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM
 ON THE OTHER SIDE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-10 Cont ID  
Sent By jleahy Date 2020-12-10 Time 14:57 Rev Time 0.00
Received By jleahy Date 2020-12-10 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-28 Cont ID  
Sent By jleahy Date 2020-10-28 Time 09:39 Rev Time 0.00
Received By jleahy Date 2020-10-28 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-08 Cont ID  
Sent By pleduc Date 2020-12-08 Time   Rev Time 0.00
Received By pleduc Date 2020-12-08 Time 15:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-09 Cont ID  
Sent By pleduc Date 2020-10-09 Time   Rev Time 0.00
Received By pleduc Date 2020-10-09 Time 11:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-12-22 Cont ID  
Sent By fmittner Date 2020-12-22 Time 15:42 Rev Time 0.00
Received By fmittner Date 2020-12-22 Time 15:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 11:41 Rev Time 0.00
Received By jleahy Date 2020-12-07 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-17 Cont ID  
Sent By cpuell Date 2020-11-17 Time 09:46 Rev Time 0.00
Received By cpuell Date 2020-10-08 Time 15:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-08 Cont ID  
Sent By medwards Date 2020-12-08 Time 09:24 Rev Time 0.00
Received By medwards Date 2020-12-08 Time 09:24 Sent To  
Notes
2020-12-08 09:24:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100464
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS THIS NEW TENANT SPACE HAS AN OFFICE AND A SHOW
 ROOM PLEASE USE THE CORRECT OCCUPANCY CLASSIFICATION
 BASED ON USE OF SPACE WITHIN THE NEW TENANT SPACE I.E.
 OFFICE AND SALES FOR THE SHOW ROOM AREA. FBC M TABLE
 403.3.1.1
  
 2) THE RECONFIGURING OF THE EXISTING TENANT SPACE?S
 MECHANICAL SYSTEM MUST BE PERMITTED AND REVIEWED. FBC
 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-14 Cont ID  
Sent By medwards Date 2020-10-14 Time 15:10 Rev Time 0.00
Received By medwards Date 2020-10-14 Time 15:10 Sent To  
Notes
2020-10-14 15:12:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100464
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OCCUPANCY CLASSIFICATION OF THE
 EXISTING SPACE AND THE OCCUPANCY CLASSIFICATION OF THE
 NEW TENANT SPACE. FBC 107.2.1
  
 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 MECHANICAL DUCT WORK FOR BOTH SPACES. FBC 107.2.1
  
 3) PLEASE SHOW HOW THE NEW TENANT SPACE WILL CONTROL
 THE TEMPERATURE IN THE NEW TENANT SPACE. FBC M 309
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By lcrespo Date 2020-12-09 Time 12:20 Rev Time 0.00
Received By lcrespo Date 2020-12-09 Time 12:20 Sent To  
Notes
2020-12-09 12:21:0212/09/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-19 Cont ID  
Sent By jesmith Date 2020-10-19 Time 14:59 Rev Time 0.00
Received By jesmith Date 2020-10-19 Time 12:32 Sent To  
Notes
2020-10-19 14:55:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 PLEASE NOTE THAT PLANS FOR CLOSED MASTER PERMIT
 19070494 LOCATED IN CITY OF WEST PALM BEACH'S FILENET
 WORKPLACE SHOWS THE EXISTING SPACE INCLUSIVE OF
 ELECTRICAL, PLUMBING AND MECHANICAL. IT APPEARS ALL
 EXISTING PLUMBING AND PLUMBING FIXTURES SHOWN ON NEW
 TENANT SPACE HAVE BEEN APPROVED ON PAST PERMITS.
  
 1.IS THERE A CHANGE OF OCCUPANCY? ORIGINAL OCCUPANCY
 FROM CLOSED MASTER PERMIT 19070494 INDICATES OCCUPANCY
 WAS B-BUSINESS. PER WPB FBC 107.2.1, PLEASE CLARIFY
 OCCUPANCY CLASSIFICATION OF THE EXISTING SPACE AND
 PROVIDE THE OCCUPANCY CLASSIFICATION OF THE NEW TENANT
 SPACE. PROVIDE OCCUPANT LOAD.
  
 2. ORIGINAL OCCUPANCY ON LIFE SAFETY PLANS FROM CLOSED
 MASTER PERMIT 19070494 INDICATES THERE IS A SERVICE
 SINK REQUIRED AND PROVIDED; THEY SHOW A JANITOR'S
 CLOSET BETWEEN THE ELECTRICAL ROOM AND THE MEN'S
 RESTROOM, BUT THEY DON'T SHOW THE FIXTURE. PER WPB FBC
 107.2.1, PLEASE CONFIRM AND SHOW EXISTING ON THE PLAN.
  
 3.PER WPB FBC 107.2.1, PLEASE PROVIDE PLUMBING DRAWINGS
 PLAN VIEW AND SIZED RISER DIAGRAM FOR WATER SUPPLY AND
 SANITARY SHOWING THE NEW PLUMBING WORK PLUMBING WORK.
  
 4.PER FBC PL 607.1, PROVIDE HOT WATER TO NEW LAVATORY
 AND BAR SINK. PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL, SCHEDULE AND DETAIL
 THE FOR WATER HEATING DEVICE.
  
 5.PER FBC PL 416.5 AND 607.1.2, TEMPERED WATER SHALL BE
 SUPPLIED TO THE LAVATORY THROUGH A WATER TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 AND SHALL
 LIMIT THE TEMPERED WATER TO A MAXIMUM OF 110 DEGREES F.
  
 6.REGARDING THE SANITARY RISER DIAGRAM ON PLAN SHEET
 A-1, THE BAR SINK SHALL CONNECT DOWNSTREAM OF THE
 LAVATORY AND WATER CLOSET PER FBC PL 912.1.
  
 7. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 8.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 CONNECTION SCHEDULE, PROVIDING WATER AND WASTE
 CONNECTION SIZES, MAXIMUM WATERFLOW/CONSUMPTION AND
 FIXTURE SPECIFICATIONS. SHOW COMPLIANCE WITH FBC PL
 TABLE 604.4 "'MAXIMUM FLOW RATES AND CONSUMPTION FOR
 PLUMBING FIXTURES AND FIXTURE FITTINGS"
  
 9. PROVIDE ALCOVE WALL FOR DRINKING FOUNTAIN TO COMPLY
 WITH PER FBC ACC 307.2 WHICH STATES OBJECTS WITH
 LEADING EDGES MORE THAN 27 INCHES (685 MM) AND NOT MORE
 THAN 80 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES (100 MM) MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 10.PER WPB FBC 107.2.1, IDENTIFY ALL NEW AND EXISTING
 ACCESSIBLE SPACES/ROOMS ON THE FLOOR PLAN INCLUDING THE
 LOUNGE AREA.
  
 11. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC
 ACC CHAPTERS 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE.
 I.LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 J.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 L.SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 OR
 304.3.2.
 M.DOOR TO TOILET ROOM SWINGS INTO LAVATORY CLEAR FLOOR
 SPACE. PER WPB FBC 107.2.1, CLARIFY THAT IT DOES NOT
 ENCROACH ON CLEAR FLOOR SPACE.
 N.DOORS SHALL BE PERMITTED TO SWING INTO TURNING SPACES
 PER FBC ACC 304.4.
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED OR DIGITALLY SIGNED
 AND SEALED BY THE DESIGNER IN ACCORDANCE WITH FAC AND
 FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20100464 1921 S DIXIE HWY
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-11 Cont ID  
Sent By rmcphers Date 2020-12-11 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2020-12-11 Time 14:37 Sent To  
Notes
2020-12-11 14:38:23SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN DROP OFF OR MAIL THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 15:46 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 15:45 Sent To  
Notes
2020-10-20 15:46:21ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  