Plan Review Details - Permit 20100435
Plan Review Stops For Permit 20100435
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 18:17 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 17:21 Sent To  
Notes
2020-12-17 17:57:27APPROVED WITH PROVISO.
 NOTE: PROVIDE INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
 1-PROVIDE PRODUCT APPROVAL FOR:
 A)FLAT ROOF AND, CLEARLY MARK APPROVED ASSEMBLY TO BE
 INSTALLED.
  
 B)EXTERIOR SWING DOOR. NOTE: PROVIDE THE FLORIDA
 PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 2-ENGINEER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By jgomez Date 2020-10-29 Time 14:54 Rev Time 0.00
Received By jgomez Date 2020-10-29 Time 10:31 Sent To  
Notes
2020-10-29 14:55:40RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- IMPORTANT: ALL DRAWINGS WERE UPLOADED TO PROJECTDOX
 AS A SINGLE PDF. DRAWINGS NEED TO BE UPLOADED
 INDIVIDUALLY. PLEASE UPLOAD EACH DRAWING INDIVIDUALLY
 AS REQUIRED BY THE CITY REQUIREMENTS FOR DIGITAL PLAN
 REVIEW. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 2-NEED TO PROVIDE LANDINGS ON THE EXTERIOR SIDE OF EACH
 PROPOSED EXTERIOR DOOR AS REQUIRED BY SEC. R311.3.2
 FBC-RESIDENTIAL.
 REVISE FOUNDATION PLAN, FLOOR PLAN, WALL SECTIONS AND
 STAIRS DETAILS AS REQUIRED.
  
 3-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)FLAT ROOF MODIFIED BITUMEN SPECIFIED ON SECTION A-A
 ON SHEET S02. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)BATHROOM EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES. OR PROVIDE COPY OF SIGNED CONTRACTS .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By equinone Date 2020-12-14 Time 13:30 Rev Time 0.00
Received By equinone Date 2020-12-14 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-30 Cont ID  
Sent By equinone Date 2020-10-30 Time 11:26 Rev Time 0.00
Received By equinone Date 2020-10-30 Time 11:26 Sent To  
Notes
2020-10-30 11:34:19CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PLEASE CLARIFY SCOPE OF ELECTRICAL WORK BEING DONE AND
 SHOW IT ON DRAWINGS. THE ELECTRICAL DRAWING SUBMITTED
 E-01 DOES NOT SHOW ANY ELECTRICAL MODIFICATIONS. FBC
 107.2
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By fmittner Date 2020-11-17 Time 12:46 Rev Time 0.00
Received By fmittner Date 2020-11-17 Time 12:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 18:17 Rev Time 0.00
Received By jgomez Date 2020-12-11 Time 06:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By jleahy Date 2020-11-20 Time 09:19 Rev Time 0.00
Received By jleahy Date 2020-10-23 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-12-14 Cont ID  
Sent By medwards Date 2020-12-14 Time 07:54 Rev Time 0.00
Received By medwards Date 2020-12-14 Time 07:51 Sent To  
Notes
2020-12-14 07:55:10NOTE ON SHEET A-2 " NOMECHANICAL WORK BEING DONE UNDER
 THIS PROJECT. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 07:31 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 07:19 Sent To  
Notes
2020-10-28 07:31:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100435
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL
 SYSTEM. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By lcrespo Date 2020-12-14 Time 14:27 Rev Time 0.00
Received By lcrespo Date 2020-12-14 Time 14:15 Sent To  
Notes
2020-12-14 14:27:4412/14/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By lcrespo Date 2020-10-28 Time 16:57 Rev Time 0.00
Received By lcrespo Date 2020-10-28 Time 16:57 Sent To  
Notes
2020-10-28 16:58:31010/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON SHEET P01 NOTE 1 PLEASE PROVIDE THE YEAR OF
 COMPLIANCE CODE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 4. PLEASE SHOW WHERE SANITARY IS GOING TO BE CONNECTED
 TO EXISTING PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PLEASE PROVIDE A NARRATIVE IN DETAIL OF THE SCOPE OF
 WORK BEING DONE PER THE WPB AMENDMENTS TO THE FBC SEC.
 101.2.
  
 6. PLEASE UPLOAD PAGES TO PROJECTDOX AS A SINGLE PDF.
 DRAWINGS NEED TO BE UPLOADED INDIVIDUALLY. PLEASE
 UPLOAD EACH DRAWING INDIVIDUALLY AS REQUIRED BY THE
 CITY REQUIREMENTS FOR THE DIGITAL PLAN REVIEW. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 7. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS.
  
 8. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER PER THE FLORIDA
 ADMINISTRATIVE CODE 61G10-11.010 SEALS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-12-17 Cont ID  
Sent By jgomez Date 2020-12-17 Time 17:54 Rev Time 0.00
Received By jgomez Date 2020-12-17 Time 17:53 Sent To  
Notes
2020-12-17 17:56:00APPROVED WITH PROVISO.
 NOTE: PROVIDE INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 A)FLAT ROOF MODIFIED BITUMEN SPECIFIED ON SECTION A-A
 ON SHEET S02. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By medwards Date 2020-12-14 Time 07:59 Rev Time 0.00
Received By medwards Date 2020-12-14 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 07:34 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 07:34 Sent To  
Notes
2020-10-28 07:35:19PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  