Plan Review Details - Permit 20100430
Plan Review Stops For Permit 20100430
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-19 Cont ID  
Sent By rmcphers Date 2021-02-19 Time 13:44 Rev Time 0.00
Received By rmcphers Date 2021-02-19 Time 13:44 Sent To  
Notes
2021-02-19 13:55:31PROVISO: TO PROVIDE A PRODUCT APPROVAL FOR THE OVERHEAD
 GARAGE DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-06 Cont ID  
Sent By rmcphers Date 2021-01-06 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2021-01-06 Time 14:18 Sent To  
Notes
2021-01-06 14:40:59REPLACE ROOF FRAMING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO
 COMPLY WITH FBC R807
 2) WILL THE ROOM BESIDE THE GARAGE CONTINUE TO BE USED
 AS STORAGE AS SHOWN ON THE PALM BEACH COUNTY PROPERTY
 APPRAISER. PLEASE WRITE ON THE DRAWING THE USE FOR THE
 ROOM NEXT TO THE GARAGE. DRAWING A02 SHOWS OCCUPANCY
 CLASSIFICATION AS "R3" THIS IS INCORRECT PLEASE REMOVE
 THIS FROM THE DRAWING.
 3) TRUSS LAYOUT AND ENGINEERING NEED TO BE SIGNED AND
 SEALED BY THE TRUSS DESIGNER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 08:19 Sent To  
Notes
2020-10-29 09:09:25REPLACE ROOF FRAMING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS (FRONT PAGES AND THE INSTALLATION INSTRUCTIONS).
 2) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER.
 3) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO
 COMPLY WITH FBC R807
 4) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING TILE (FRONT PAGES AND
 THE INSTALLATION INSTRUCTIONS).
 5) PLEASE SHOW THE CONTINUED USE OF THE ROOM BESIDE THE
 GARAGE AS STORAGE AS SHOWN ON THE PALM BEACH COUNTY
 PROPERTY APPRAISER.
 6) TRUSS LAYOUT AND ENGINEERING NEED TO BE SIGNED AND
 SEALED BY THE TRUSS DESIGNER.
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW- OR - IF
 YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC
 OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-01-27 Cont ID  
Sent By fmittner Date 2021-01-27 Time 08:40 Rev Time 0.00
Received By fmittner Date 2021-01-27 Time 08:40 Sent To  
Notes
2021-01-27 08:41:09APPROVED BY HPB 1/26/21

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By fmittner Date 2020-11-17 Time 12:39 Rev Time 0.00
Received By fmittner Date 2020-11-17 Time 12:39 Sent To  
Notes
2020-11-17 12:40:11MODIFICATION OF ROOF LINE REQUIRES HPB APPROVAL.
 SENDING CONTRACTOR COA APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-19 Cont ID  
Sent By rmcphers Date 2021-02-19 Time 13:49 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-27 Cont ID  
Sent By lmarchan Date 2021-01-27 Time 15:49 Rev Time 0.00
Received By lmarchan Date 2020-12-31 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By jleahy Date 2020-11-20 Time 09:19 Rev Time 0.00
Received By jleahy Date 2020-10-22 Time 14:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-02-19 Cont ID  
Sent By rmcphers Date 2021-02-19 Time 13:45 Rev Time 0.00
Received By rmcphers Date 2021-02-19 Time 13:45 Sent To  
Notes
2021-02-19 13:48:55BUILDING PERMIT APPLICATION MARKED ROOFING IS REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-06 Cont ID  
Sent By rmcphers Date 2021-01-06 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2021-01-06 Time 14:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By rmcphers Date 2020-10-29 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2020-10-29 Time 09:09 Sent To  
Notes
2020-10-29 09:10:33SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.