Plan Review Details - Permit 20100289
Plan Review Stops For Permit 20100289
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2021-02-19 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2021-02-19 Time 12:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-01-27 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2021-01-27 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By jwitmer Date 2020-12-16 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2020-12-16 Time 08:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-28 Cont ID  
Sent By jwitmer Date 2020-10-28 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2020-10-28 Time 15:16 Sent To  
Notes
2020-10-28 15:19:19IN REVIEW. JW 10/18/2020

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-02-16 Cont ID  
Sent By jleahy Date 2021-02-16 Time 16:52 Rev Time 0.00
Received By jleahy Date 2021-02-16 Time 16:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 09:15 Rev Time 0.00
Received By jleahy Date 2021-02-08 Time 09:12 Sent To  
Notes
2021-02-08 09:17:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ON THE PROPOSED OR DETAILED PLAN PLEASE ADD THE
 ELECTRICAL OUTLETS, AND LIGHTING FIXTURES TO THE PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 09:24 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 09:22 Sent To  
Notes
2020-12-16 09:25:23ELECTRICAL WORK WAS TAKEN OFF PLAN IN VERSION 2 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-04 Cont ID  
Sent By jleahy Date 2020-11-04 Time 10:14 Rev Time 0.00
Received By jleahy Date 2020-11-04 Time 10:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 10:59 Sent To  
Notes
2021-02-22 11:00:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-01-27 Cont ID  
Sent By pleduc Date 2021-01-27 Time   Rev Time 0.00
Received By pleduc Date 2021-01-27 Time 13:04 Sent To  
Notes
2021-01-27 13:07:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-10 Cont ID  
Sent By pleduc Date 2020-12-10 Time   Rev Time 0.00
Received By pleduc Date 2020-12-10 Time 16:09 Sent To  
Notes
2020-12-10 16:15:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-23 Cont ID  
Sent By pleduc Date 2020-10-23 Time   Rev Time 0.00
Received By pleduc Date 2020-10-23 Time 12:05 Sent To  
Notes
2020-10-23 13:48:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING AREA
 MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE FIRE
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY A
 CERTIFIED FIRE SPRINKLER CONTRACTOR.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY A CERTIFIED
 FIRE SPRINKLER CONTRACTOR.
  
 3) THE FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-02-24 Time   Rev Time 0.00
Received By shill Date 2021-02-16 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 09:17 Rev Time 0.00
Received By jleahy Date 2021-01-26 Time 17:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-12-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-12-09 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2020-11-04 Cont ID  
Sent By jleahy Date 2020-11-04 Time 10:15 Rev Time 0.00
Received By jleahy Date 2020-10-22 Time 06:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 11:31 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-01-26 Cont ID  
Sent By ccole Date 2021-01-26 Time 17:12 Rev Time 0.00
Received By ccole Date 2021-01-26 Time 17:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-12-18 Cont ID  
Sent By ccole Date 2020-12-18 Time 07:53 Rev Time 0.00
Received By ccole Date 2020-12-18 Time 06:43 Sent To  
Notes
2020-12-18 07:53:29 
 2ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20100289
 12/18/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 FAIR HOUSING ACT DESIGN MANUAL COMPLIANCE.
  
 1) SHEET 1: THE REVISED PLAN IS INDICATING A
 SPECIFICATION TYPE B DESIGN FOR THE MASTER BATH,
 HOWEVER THE REQUIRED 30X48 IN. CLEAR FLOOR SPACE
 DIAGRAM AT THE BATHTUB AND THE REQUIRED 30X48 IN. CLEAR
 FLOOR SPACE OUTSIDE THE SWING OF THE DOOR ARE NOT
 SHOWN. ALSO REQUIRED ARE THE GRAB BAR BACKING
 REINFORCEMENTS LOCATION DIASGRAMS AT THE BATHTUB FOR
 GRAB BARS- REFER TO LAYOUTS ON PAGES 7.37 & 7.40.
 PLEASE NOTE IN SPECIFICATION B ONLY ONE OF THE TWO
 BATHING FIXTURES MUST BE PROVIDED WITH THE REQUIRED
 CLEAR FLOOR SPACE- PAGE 7.56. BASED ON THE REVISED PLAN
 AND THE CLEAR FLOOR SPACE DIAGRAMS FOR SHOWERS ON PAGES
 7.56- 7.58 THE CLEAR FLOOR SPACE SHOWN AT THE SHOWER
 DOES NOT MEET COMPLIANCE. PLEASE REVISE THE PLAN TO
 SHOW THE BATHTUB MEETS COMPLIANCE.
  
 AS PREVIOUSLY NOTED IN THE FIRST REVIEW, AS AN
 ALTERNATIVE TO MEETING THE GUIDELINES FOR THE BATH
 ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR THE
 PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 2) 2ND REQUEST TO SUBMIT A PLUMBING SUB-PERMIT
 APPLICATION- SECTION 105.1 WPB. PLEASE NOTE THE
 APPLICATION MAY BE SUBMITTED AFTER THE MAIN PERMIT IS
 ISSUED, HOWEVER NO PLUMBING WORK SHALL COMMENCE UNTIL
 THE SUB- PERMIT IS ISSUED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By ccole Date 2020-10-29 Time 15:00 Rev Time 0.00
Received By ccole Date 2020-10-29 Time 12:17 Sent To  
Notes
2020-10-29 15:01:041ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20100289
 10/29/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1: REFER TO SECTION 1002.1: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
  
 2) SHEET 1: SHOW THE REQUIRED 1/4 IN. PER FT. SHOWER
 LINER SLOPE TO THE DRAIN- SECTION 417.5.2 FBC P.
  
 3) FAIR HOUSING ACT GUIDELINES: BECAUSE THE BUILDING
 WAS CONSTRUCTED IN ACCORDANCE WITH THE ACCESSIBILITY
 REQUIREMENTS OF THE FAIR HOUSING ACT DESIGN MANUAL FOR
 USABLE BATHROOMS IN DWELLING UNITS UNDER PERMIT
 01101288, THE PROPOSED ALTERATION BATHROOM ALTERATION
 SHALL ALSO BE IN COMPLIANCE WITH THE FAIR HOUSING ACT.
 REFER TO PAGES 7.39- 7.57 AND INDICATE ON THE PLAN IF
 THE ORIGINAL BATHROOM WAS DESIGNED AS EITHER A
 SPECIFICATION TYPE A OR B. IN TYPE A BATHROOMS BOTH THE
 BATHTUB AND THE SHOWER MUST BE PROVIDED WITH THE 30 X
 48 IN. CLEAR FLOOR SPACE POSITIONED FOR PARALLEL
 APPROACH. IN TYPE B ONLY ONE BATHING FIXTURE MUST BE
 PROVIDED WITH THE CLEAR FLOOR SPACE. IN THIS CASE IT
 APPEARS THE BATHTUB WOULD BE IN COMPLIANCE. PLEASE
 REVISE THE PLAN TO INDICATE THE SPECIFICATION TYPE, AND
 SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS.
 PLEASE NOTE THAT THE CLEAR FLOOR SPACE FOR THE SHOWER
 MUST BE FLUSH WITH THE CONTROL WALL- PAGE 7.56. FOR
 TYPE B BATHROOMS, REINFORCEMENTS FOR FUTURE GRAB BARS
 MUST BE INSTALLED IN ACCORDANCE WITH FAIR HOUSING
 ACCESSIBILITY GUIDELINES AND FIGURE 5 FBC ACC. PROVIDE
 DIMENSIONED BACK AND SIZED ELEVATION VIEWS OF THE
 SHOWER WALLS TO SHOW THE LOCATIONS, LENGTHS AND WIDTHS
 OF THE BACKINGS.
  
 PLEASE NOTE AS AN ALTERNATIVE TO MEETING THE GUIDELINES
 FOR THE BATH ALTERATIONS, THE OWNER AND DESIGNER OF
 RECORD FOR THE PROPOSED PROJECT MAY PROVIDE A SIGNED
 AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 SO REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 4) SUBMIT A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-02-16 Cont ID  
Sent By jleahy Date 2021-02-16 Time 16:52 Rev Time 0.00
Received By jleahy Date 2021-02-16 Time 16:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-26 Cont ID  
Sent By ccole Date 2021-01-26 Time 17:12 Rev Time 0.00
Received By ccole Date 2021-01-26 Time 17:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By jwitmer Date 2020-12-16 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2020-12-16 Time 08:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-28 Cont ID  
Sent By jwitmer Date 2020-10-28 Time 15:49 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-10-28 15:49:12SIGNATURE REVIEW: DENIED
 IT APPEARS THE PLANS ARE NOT SIGNED NOR SEALED.
 61G15-23.002 ENGINEER SEAL SIGNATURE AND DATE SHALL BE
 AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE
 LICENSEE?S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) AND AFFIX THE LICENSEE?S SEAL.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  