2020-10-07 12:47:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100263 |
| 10/7/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 944 |
| CHURCHILL RD. SHOW A GAS PERMIT #15040162 WAS ISSUED ON |
| 4/6/2015 FOR GAS LINE INSTALLATION TO A NEW TANKLESS |
| WATER HEATER AT 150,000 BTUH, AND A NEW DRYER AT 35,000 |
| BTUH. PLEASE REVISE THE GAS RISER TO SHOW A COMPLETE |
| PIPING SYSTEM THAT INCLUDES THE NEW GENERATOR AND THE |
| EXISTING APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC |
| RES. PLEASE INCLUDE THE TYPE, SIZE, AND LENGTH OF THE |
| MAIN SUPPLY PIPE FROM THE METER TO THE TEE. |
| |
| A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. PLEASE NOTE THE GENERATOR PERMIT- 20090421 SHOWS A |
| 22 KW GENERATOR AT 327.000 BTUH. |
| |
| B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| G2413.4.2 FBC RES. |
| |
| C) SHOW THE LOCATIONS OF SHUT OFF VALVES AND PIPE |
| UNIONS- SECTIONS G2420.5 & G2422.1.4. |
| |
| D) SHOW THE LOCATIONS OF NEW AND EXISTING REGULATORS. |
| INDICATE THE MAKES AND MODELS OF THE REGULATORS AND |
| THEIR INLET AND OUTLET PRESSURES- SECTION G2421.1 & |
| G2421.2. SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING |
| THE SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| PRESSURES, SPRING DATA, AND ORIFICE SIZE. IF CONNECTED |
| TO RIGID PIPING, PIPE UNIONS ARE REQUIRED WITH 1 FT. OF |
| EITHER SIDE OF THE REGULATOR- SECTION G2421.2(7). |
| |
| E) SHOW THE LOCATIONS OF DRIP LEGS- SECTION G2419.2. |
| |
| 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING THAT |
| INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |