2020-10-06 13:30:51 | 10/06/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB PLUMBING PERMIT FOR AUTOFILL PRESSURE VAUCCUM |
| BREAKER HAS TO BE A STAND-ALONE TYPE, THIS AUTO-FILL |
| ALSO REQUIRES TO HAVE A REDUCED PRESSURE ZONE VACUUM |
| BREAKER AT THE METER WHICH IT UNIT HAS TO BE CERTIFIED |
| BY THE CITY OF WEST PALM BEACH UNDER THE CROSS |
| CONNECTION PROGRAM AS THIS IS A CONTAINMENT BACKFLOW |
| DEVICE. THE PVB IS AN ISOLATION DEVICE THAT CAN BE |
| CERTIFIED BY THE PLUMBING CONTRACTOR BEFORE A FINAL |
| INSPECTION. PLEASE SUBMIT A SEPARATE APPLICATION WITH |
| THE MANUFACTURER?S SPECIFICATIONS FOR THE BACKFLOW |
| PREVENTERS. THE MAKE, MODEL, AND SIZE OF THE DEVICE |
| SHALL BE LISTED IN THE DESCRIPTION OF THE WORK SECTION |
| ON THE PERMIT APPLICATION. THESE DEVICES REQUIRE A |
| DOCUMENT THAT NEEDS TO SHOW THE DEVICE IS LEAD-FREE |
| WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD AND |
| APPROVED DEVICES LISTED AND PUBLISHED BY THE UNIVERSITY |
| OF SOUTHERN CALIFORNIA (USC). |
| |
| 2. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE P |
| CC 200 CARTRIDGE FILTER PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1, INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. A SOLAR COVER REQUIRED PER 2017 FBC RE 403.10.3. |
| |
| 4. PLEASE PROVIDE DOCUMENTATION THAT THE GAS AND SPA |
| HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82 % |
| FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16, 2013, |
| WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. |
| |
| 5. IDENTIFY AND SHOW ON THE PUMP CURVE WHICH CURVE KEY |
| IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. |
| THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM |
| THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 |
| SECS. 4.4.9, 4.4.9.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |