Plan Review Details - Permit 20100178
Plan Review Stops For Permit 20100178
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-09 Cont ID  
Sent By fgiaquin Date 2020-12-09 Time 21:30 Rev Time 0.00
Received By fgiaquin Date 2020-12-09 Time 20:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-18 Cont ID  
Sent By fgiaquin Date 2020-11-18 Time 22:09 Rev Time 0.00
Received By fgiaquin Date 2020-11-18 Time 21:39 Sent To  
Notes
2020-11-18 22:09:18PROVIDE LOAD CALCULATION AS PER PREVIOUS PLAN REVIEW
 COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By fgiaquin Date 2020-11-03 Time 21:50 Rev Time 0.00
Received By fgiaquin Date 2020-11-03 Time 20:32 Sent To  
Notes
2020-11-03 21:49:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION SHOWING ALL LOADS.
 FBC 107.2.1 NEC 220.
  
 2. PLAN MUST BE SIGNED BY ELECTRICAL CONTRACTOR
 QUALIFIER. PROVIDE CORRECTION. FS 471.003(2)(H);
 471.025; WPB FBC 107.1
  
 3. ADDRESS MUST BE ON PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-18 Cont ID  
Sent By fgiaquin Date 2020-11-18 Time 22:09 Rev Time 0.00
Received By fgiaquin Date 2020-11-05 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-03 Cont ID  
Sent By fgiaquin Date 2020-11-03 Time 21:50 Rev Time 0.00
Received By fgiaquin Date 2020-10-21 Time 11:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-18 Cont ID  
Sent By fgiaquin Date 2020-11-18 Time 22:09 Rev Time 0.00
Received By fgiaquin Date 2020-11-18 Time 22:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-03 Cont ID  
Sent By fgiaquin Date 2020-11-03 Time 21:50 Rev Time 0.00
Received By fgiaquin Date 2020-11-03 Time 14:17 Sent To  
Notes
2020-11-03 21:50:38PLANS NOT SIGNED BY QUALIFIER