Plan Review Details - Permit 20100167
Plan Review Stops For Permit 20100167
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By cthroop Date 2020-11-16 Time 14:13 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 14:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-24 Cont ID  
Sent By cthroop Date 2020-10-24 Time 09:29 Rev Time 0.00
Received By cthroop Date 2020-10-24 Time 09:07 Sent To  
Notes
2020-10-24 09:35:19PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. GENERATOR SPECIFICATIONS PROVIDED FOR REVIEW ARE FOR
 A 2017 MODEL GENERAC GENERATOR. PROVIDE CURRENT
 GENERATOR SPECIFICATIONS FOR REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. LOCATION OF GENERATOR ON SURVEY STATES IT WILL BE
 LOCATED 5 FEET OFF WINDOWS AND DOORS. GENERATOR SHALL
 BE LOCATED AT LEAST 10 FEET FROM BUILDING OPENINGS.
 R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-24 Cont ID  
Sent By cthroop Date 2020-10-24 Time 09:35 Rev Time 0.00
Received By cthroop Date 2020-10-24 Time 09:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-11-18 Cont ID  
Sent By ccole Date 2020-11-18 Time 13:07 Rev Time 0.00
Received By ccole Date 2020-11-18 Time 13:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 16:39 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 16:08 Sent To  
Notes
2020-11-13 16:39:472ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100167
 11/13/29
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT A GAS SUB-PERMIT APPLICATION THAT SHOWS THE
 CORRECT WORK DESCRIPTION FOR THE PROPOSED NATURAL GAS
 PIPING INSTALLATIONS. THE APPLICATION THAT WAS
 SUBMITTED INDICATES A 500-GALLON LP TANK INSTALLATION-
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-20 Cont ID  
Sent By ccole Date 2020-10-20 Time 10:30 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 09:25 Sent To  
Notes
2020-10-20 10:31:391ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100167
 10/20/29
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PROVIDE AN LP GAS RISER DRAWING
 SHOWING THE TYPES AND SIZES OF PIPING; TOTAL DEVELOPED
 LENGTH OF THE SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW
 AND EXISTING LP APPLIANCES OR EQUIPMENT; TOTAL BTUH
 LOAD OF THE SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES
 OR EQUIPMENT- SECTIONS G2412.3, G2412.4, G2413.2,
 G2413.4.1, G2413.4.2, G2412.3, G2412.4 FBC RES.
  
 A) SHOW THE LOCATIONS OF SHUTOFF VALVES, LOCATIONS AND
 MAKES AND MODELS OF REGULATORS INCLUDING INLET AND
 OUTLET PRESSURES, LOCATIONS OF UNIONS, RISERS AND FLEX
 CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES-
 SECTIONS G2420, G2421, & G2413.4(1)- G2413.4(21) FBC
 RES. PLEASE NOTE THE SUBMITTED PIPE SIZING TABLE IN THE
 GAS SUBMITTAL PACKAGE IS FOR NATURAL GAS. PLEASE SUBMIT
 LP PIPE SIZING TABLES.
  
 2) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE
 LOCATION OF THE NEW LP TANK AND REQUIRED 10 FT.
 CLEARANCES DISTANCES FROM THE TANK TO THE BUILDING, AND
 ADJACENT PROPERTY LINES- TABLE 6.3.1.1 NFPA 58. PLEASE
 SHOW THE PIPING RUN ON THE SURVEY FROM THE TANK TO THE
 GENERATOR- SECTION 107.2.1 WPB.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 4) PROVIDE LP TANK INSTALLATION AS REQUIRED BY NFPA 58:
  
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
  
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND
 HOW IT WILL BE TESTED- SECTION 6.17.1.
  
 5) THE SURVEY HAS BEEN INCORRECTLY MARKED UP TO SHOW A
 5 FT. CLEARANCE FOR THE GENERATOR TO WINDOWS AND DOORS,
 HOWEVER A 10 FT. CLEARANCE TO MECHANICAL AND GRAVITY
 AIR INTAKES IS REQUIRED PER SECTION R303.5.1 FBC RES-
 PLEASE CORRECT THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-11-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-11-17 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-17 Cont ID  
Sent By lmarchan Date 2020-11-17 Time 10:50 Rev Time 0.00
Received By lmarchan Date 2020-11-12 Time 14:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-06 Cont ID  
Sent By lmarchan Date 2020-11-06 Time 09:04 Rev Time 0.00
Received By lmarchan Date 2020-10-08 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-11-18 Cont ID  
Sent By ccole Date 2020-11-18 Time 13:06 Rev Time 0.00
Received By ccole Date 2020-11-18 Time 13:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-13 Cont ID  
Sent By ccole Date 2020-11-13 Time 16:31 Rev Time 0.00
Received By ccole Date 2020-11-13 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-20 Cont ID  
Sent By ccole Date 2020-10-20 Time 10:32 Rev Time 0.00
Received By ccole Date 2020-10-20 Time 09:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By cthroop Date 2020-11-16 Time 14:13 Rev Time 0.00
Received By cthroop Date 2020-11-16 Time 14:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-24 Cont ID  
Sent By cthroop Date 2020-10-24 Time 09:36 Rev Time 0.00
Received By cthroop Date 2020-10-24 Time 09:07 Sent To  
Notes
2020-10-24 09:38:17PLAN REVIEW GENERATOR / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD DESIGN
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-17 Cont ID  
Sent By kalexand Date 2020-11-17 Time 13:40 Rev Time 0.00
Received By kalexand Date 2020-11-17 Time 13:40 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-05 Cont ID  
Sent By kalexand Date 2020-11-05 Time 15:38 Rev Time 0.00
Received By kalexand Date 2020-11-05 Time 15:38 Sent To I
Notes
***NONE***