Plan Review Stops For Permit 20100049 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-12-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-03 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-03 |
Time |
11:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-28 |
Time |
07:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-28 |
Time |
07:33 |
Sent To |
|
|
Notes |
2020-10-28 07:47:46 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY | | OPENINGS INTO THE BUILDING. FBC M501.3 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-12-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-12-05 |
Time |
23:26 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-12-05 |
Time |
22:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-10-28 |
Time |
20:13 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-10-28 |
Time |
19:39 |
Sent To |
|
|
Notes |
2020-10-28 19:46:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. VALUE LOW FOR AMOUNT OF WORK SHOWN, RAISE VALUE OR | | VALUE WILL BE SET BY BUILDING OFFICIAL. FBC 109.3 | | | | 2. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTORS WHEN | | DWELLING IS BEING FED BY MORE THAN ONE PANEL. NEC | | 310.15(B)(7)(1) | | | | 3. CANNOT DE-RATE FEEDER CONDUCTORS WHEN DWELLING IS | | BEING FED BY MORE THAN ONE PANEL. NEC 310.15(B)(7)(2) | | | | 4. PERMIT APPLICATION SAYS 22KW GENERATOR ALONG WITH | | CUT SHEETS, BUT PLAN SHOWS 24KW GENERATOR.. PROVIDE | | CORRECTION. FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-21 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-21 |
Time |
08:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-01 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-01 |
Time |
12:35 |
Sent To |
|
|
Notes |
2020-12-01 12:52:18 | 2ND REVIEW FBC-2017 RES. | | PERMIT- 20100049 | | 12/1/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW WAS NOT | | ADDRESSED- PLEASE COMPLY. | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | THE NEW PIPING AND THE EXISTING PIPING AND APPLIANCES | | INSTALLED UNDER PERMIT 03051196- SECTION 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-10-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-10-20 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-10-20 |
Time |
16:20 |
Sent To |
|
|
Notes |
2020-10-20 16:50:42 | 1ST REVIEW FBC-2017 RES. | | PERMIT- 20100049 | | 10/20/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES | | THE EXISTING PIPING AND APPLIANCES INSTALLED UNDER | | PERMIT 03051196- SECTION 107.2.1 WPB. | | | | 2) PLEASE CORRECT THE NOTE ON THE SURVEY TO INDICATE | | THE 10 FT. REQUIRED CLEARANCE FROM THE GENERATOR TO | | WINDOW AND DOOR OPENINGS- SECTION R303.5.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-12-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-21 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-11 |
Time |
18:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-12-05 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-12-05 |
Time |
23:26 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-11-23 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2020-10-28 |
Time |
20:13 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2020-10-13 |
Time |
16:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2020-12-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-21 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-21 |
Time |
08:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-01 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-01 |
Time |
12:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-10-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-10-20 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-10-20 |
Time |
16:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-12-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-12-21 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-12-21 |
Time |
08:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-12-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-03 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-03 |
Time |
11:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-10-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-10-28 |
Time |
07:40 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-10-28 |
Time |
07:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-12-03 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-12-03 |
Time |
|
Rev Time |
0.00 |
Received By |
rthermid |
Date |
2020-12-03 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-10-27 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-10-27 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2020-10-27 |
Time |
|
Sent To |
I |
|
Notes |
2020-10-27 08:51:38 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 10/27/2020 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. MECHANICAL EQUIPMENT CANNOT ENCROACH MORE THAN 4 | | FEET INTO A REQUIRED SETBACK. THE GENERATOR MUST BE | | SETBACK A MINIMUM OF 3.5 FEET FROM THE SIDE PROPERTY | | LINE . | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | W: WPB.ORG | | |
|
|