2020-10-07 15:39:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100019 |
| 10/7/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 235 EDMOR |
| SHOWS A 400,000 BTUH POOL HEATER ISSUED UNDER |
| PERMIT-12020716. PLEASE PROVIDE A COMPLETE RISER |
| DRAWING THAT INCLUDES THE BRANCH LINE TO THE POOL |
| HEATER, AND THE BRANCH LINE TO THE INTERIOR APPLIANCES. |
| SHOW THE TOTAL LENGTHS OF THE BRANCHES, AND THE TOTAL |
| DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO THE |
| MOST REMOTE OUTLET. YOU ARE INDICATING THE EXISTING |
| LOAD AT 900,000 BTUH. SHOW ON THE RISER THE INDIVIDUAL |
| APPLIANCE LOCATIONS AND THEIR INDIVIDUAL LOADS- REFER |
| TO SECTIONS G2412.3, G2412.4, G2413.1, & G2413.2 FBC |
| RES. FUEL GAS. |
| |
| A) SHOW THE DELIVERY PRESSURE AT THE OUTLET OF THE NEW |
| REGULATOR, AND THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF |
| EITHER SIDE OF THE REGULATOR- SECTIONS G2421.1 & |
| G2421.2(7). |
| |
| B) INDICATE THE MAKE AND MODEL OF THE REGULATOR ON THE |
| RISER AND MARK OR HIGHLIGHT THE SPECS TO SHOW THE |
| SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| PRESSURES, AND ORIFICE SIZE. |
| |
| 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING THAT |
| INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |