Plan Review Details - Permit 20100012
Plan Review Stops For Permit 20100012
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rmcphers Date 2020-10-27 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2020-10-27 Time 15:32 Sent To  
Notes
2020-10-27 15:46:45GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE SITE
 SPECIFIC WIND DESIGN PRESSURES OR PROVIDE SIGNED AND
 SEALED SITE SPECIFIC WIND DESIGN PRESSURES FROM AN
 ARCHITECT OR ENGINEER. (WIND DESIGN TO BE BASED ON
 150MPH, EXPOSURE"C") (SEE NOTE NUMBER 2 ON THE ENGINEER
 SLAB DRAWING).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-12 Cont ID  
Sent By fgiaquin Date 2020-11-12 Time 21:22 Rev Time 0.00
Received By fgiaquin Date 2020-11-12 Time 20:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-10-29 Cont ID  
Sent By fgiaquin Date 2020-10-29 Time 21:18 Rev Time 0.00
Received By fgiaquin Date 2020-10-29 Time 19:43 Sent To  
Notes
2020-10-29 21:18:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LOW FOR AMOUNT OF WORK SHOWN, RAISE VALUE OR
 VALUE WILL BE SET BY BUILDING OFFICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-12-02 Cont ID  
Sent By ccole Date 2020-12-02 Time 11:18 Rev Time 0.00
Received By ccole Date 2020-12-02 Time 10:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-12-01 Cont ID  
Sent By ccole Date 2020-12-01 Time 14:30 Rev Time 0.00
Received By ccole Date 2020-12-01 Time 14:30 Sent To  
Notes
2020-12-01 14:31:023RD REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100012
 12/1/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW ARE LISTED
 BELOW WITH ADDITIONAL NOTES.
  
 3) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. TANK SPECS NOT SUBMITTED.
 PLEASE PROVIDE THE TANK SPEC SHEET.
  
 4A) FAILED. PROVIDE LP TANK INSTALLATION DETAILS AS
 REQUIRED BY NFPA 58- ENGINEERING FOR ANCHORING THE TANK
 TO PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT-
 SECTION 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE
 ELEVATION VIEW THAT SHOWS THE BURIAL DEPTH, ANCHORING
 BASE MATERIAL, AND THE TYPES, SIZES, AND NUMBERS OF
 ANCHORS, CABLES OR STRAPS, AND THE TYPE OF PROTECTIVE
 SLEEVES FOR THE CABLES OR STRAPS. PLEASE PROVIDE
 ENGINEERING FOR INSTALLATION OF THE LP TANK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-11-18 Cont ID  
Sent By ccole Date 2020-11-18 Time 12:37 Rev Time 0.00
Received By ccole Date 2020-11-18 Time 11:57 Sent To  
Notes
2020-11-18 12:37:452ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100012
 11/18/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) FAILED. SURVEY: INDICATE THE REQUIRED 10 FT.
 CLEARANCE DISTANCE FOR THE UG TANK TO THE DRIVEWAY-
 SECTION 6.6.6.1(B) & (C) NFPA 58-14. TANKS INSTALLED
 WITH 10 FT. SHALL BE INSTALLED 18 IN. BELOW GRADE OR
 VEHICLE PROTECTION SHALL BE PROVIDED. THE CLEARANCE
 DISTANCE FROM THE UG TANK TO THE DRIVEWAY NOT SHOWN.
 INSTALLATION DETAILS FOR DOME AND COVER NOT PROVIDED.
  
 3) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. TANK SPECS NOT SUBMITTED.
  
 4) FAILED. PROVIDE LP TANK INSTALLATION DETAILS AS
 REQUIRED BY NFPA 58:
  
 A) FAILED. ENGINEERING FOR ANCHORING THE TANK TO
 PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT-
 SECTION 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE
 ELEVATION VIEW THAT SHOWS THE BURIAL DEPTH, ANCHORING
 BASE MATERIAL, AND THE TYPES, SIZES, AND NUMBERS OF
 ANCHORS, CABLES OR STRAPS, AND THE TYPE OF PROTECTIVE
 SLEEVES FOR THE CABLES OR STRAPS. PLEASE PROVIDE A
 COMPLETE DETAIL THAT INCLUDES THE ATTACHMENT OF THE
 DOME AND COVER.
  
 B) FAILED. SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1
 (1) NFPA 58. INDICATE THE TYPE OF PROTECTION AND HOW IT
 WILL BE TESTED- SECTION 6.17.1. DETAIL FOR ANODE BAG
 INSTALLATION NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-10-26 Cont ID  
Sent By ccole Date 2020-10-26 Time 14:06 Rev Time 0.00
Received By ccole Date 2020-10-26 Time 12:39 Sent To  
Notes
2020-10-26 14:06:411ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100012
 10/26/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SURVEY: INDICATE THE REQUIRED 10 FT. CLEARANCE
 DISTANCE FOR THE UG TANK TO THE DRIVEWAY- SECTION
 6.6.6.1(B) & (C) NFPA 58-14. TANKS INSTALLED WITH 10
 FT. SHALL BE INSTALLED 18 IN. BELOW GRADE OR VEHICLE
 PROTECTION SHALL BE PROVIDED.
  
 2) SURVEY: CORRECT THE 5 FT. GENERATOR EXHAUST
 CLEARANCE TO OPENINGS INTO THE BUILDING. A 10 FT.
 CLEARANCE IS REQUIRED TO MECHANICAL AND GRAVITY AIR
 INTAKES INTO THE BUILDING PER SECTION R303.5.1 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 4) PROVIDE LP TANK INSTALLATION DETAILS AS REQUIRED BY
 NFPA 58:
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1
 (1) NFPA 58. INDICATE THE TYPE OF PROTECTION AND HOW IT
 WILL BE TESTED- SECTION 6.17.1
  
 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 10:21 Rev Time 0.00
Received By jleahy Date 2020-11-24 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2020-11-13 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-29 Cont ID  
Sent By fgiaquin Date 2020-10-29 Time 21:18 Rev Time 0.00
Received By fgiaquin Date 2020-10-14 Time 10:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-12-02 Cont ID  
Sent By ccole Date 2020-12-02 Time 11:18 Rev Time 0.00
Received By ccole Date 2020-12-02 Time 10:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-11-18 Cont ID  
Sent By ccole Date 2020-11-18 Time 12:37 Rev Time 0.00
Received By ccole Date 2020-11-18 Time 11:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-10-26 Cont ID  
Sent By ccole Date 2020-10-26 Time 14:06 Rev Time 0.00
Received By ccole Date 2020-10-26 Time 12:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-03 Cont ID  
Sent By medwards Date 2020-12-03 Time 06:47 Rev Time 0.00
Received By medwards Date 2020-12-03 Time 06:47 Sent To  
Notes
2020-12-02 11:27:39A SIGNED AND SEALED HARD COPY OF THE LP TANK HOLD DOWN
 AND ANODE BAG INSTALLATION DETAIL SHEET SHALL BE
 DROPPED OFF AT THE WPB BUILDING DEPT. FOR PERMIT
 ISSUANCE.
 THE CONTRACTOR SHALL ATTACH A PLAN REVIEW REQUEST WITH
 THE SPEC SHEET TO EXPLAIN THE PURPOSE OF THE SUBMITTAL.
  
 CCOLE
 12/2/2020

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-11-19 Cont ID  
Sent By rmcphers Date 2020-11-19 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2020-11-19 Time 14:25 Sent To  
Notes
2020-11-19 14:26:39FOR THE PREFAB SLAB DRAWING = SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-10-27 Cont ID  
Sent By rmcphers Date 2020-10-27 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2020-10-27 Time 15:47 Sent To  
Notes
2020-10-27 15:48:16FOR THE PREFAB SLAB DRAWING = SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.--------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 ---------------------------------------------
2020-10-26 14:09:20THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
 CCOLE 10/26/2020.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By rthermid Date 2020-12-09 Time   Rev Time 0.00
Received By rthermid Date 2020-12-09 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-20 Cont ID  
Sent By rthermid Date 2020-10-20 Time   Rev Time  
Received By rthermid Date 2020-10-20 Time   Sent To I
Notes
***NONE***