Plan Review Details - Permit 20091245
Plan Review Stops For Permit 20091245
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-22 Cont ID  
Sent By pvalenti Date 2020-10-22 Time 13:39 Rev Time 0.00
Received By pvalenti Date 2020-10-22 Time 10:58 Sent To  
Notes
2020-10-22 13:42:25PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 AT TIME OF INSPECTION SHUTTERS MUST BE IN PLACE AS NEW
 WINDOWS ARE NOT IMPACT RESISTANT.
 ALL WORK IS SUBJECT TO FIELD INSPECTOR'S APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-13 Cont ID  
Sent By pvalenti Date 2020-10-13 Time 16:24 Rev Time 0.00
Received By pvalenti Date 2020-10-13 Time 16:24 Sent To  
Notes
2020-10-13 16:30:23PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND BUILDING REVIOEW DENIED:
  
 FBC B 107.2.1, THE SUBMITTED DOCUMENTATION STILL IS NOT
 CLEAR AS THE UPLOADED INFORMATION APPEARS TO INDICATE
 THAT NON-IMPACTED WINDOWS ARE TO BE INSTALLED. IF THE
 INTENTION IS TO INSTALL NON-IMPACT WINDOWS, PLEASE
 PROVIDE ADDITIONAL INFORMATION FOR SHUTTERS OR OTHER
 OPENING PROTECTIVE DEVICES.
  
 A SUBMITTED RESPONSE SHEET ANSWERING THESE COMMENTS
 WILL BE VERY HELPFUL FOR THE NEXT REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-06 Cont ID  
Sent By pvalenti Date 2020-10-06 Time 15:05 Rev Time 0.00
Received By pvalenti Date 2020-10-06 Time 14:33 Sent To  
Notes
2020-10-06 15:12:39PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE SUBMITTED INFORMATION SHEET IS NOT
 CLEAR AS TO WHICH TYPE OF WINDOW IS TO BE USED. THE
 PRODUCT IDENTIFIED IS WIN 8800 AND THE PRODUCT APPROVAL
 IDENTIFIED IS # 15819.1. PRODUCT APPROVAL # 15819 IS
 FOR PRODUCT WIN 8400 (NON-IMPACT) NOT WIN 8800.
 PLEASE REVIEW ALL DOCUMENTS AND RESUBMIT WITH THE
 DESIRED PRODUCTS IDENTIFIED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-22 Cont ID  
Sent By pvalenti Date 2020-10-22 Time 13:42 Rev Time 0.00
Received By pvalenti Date 2020-10-14 Time 16:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-13 Cont ID  
Sent By pvalenti Date 2020-10-13 Time 16:30 Rev Time 0.00
Received By pvalenti Date 2020-10-07 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-06 Cont ID  
Sent By pvalenti Date 2020-10-06 Time 15:13 Rev Time 0.00
Received By pvalenti Date 2020-10-01 Time 07:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-10-06 Cont ID  
Sent By pvalenti Date 2020-10-06 Time 15:13 Rev Time 0.00
Received By pvalenti Date 2020-10-06 Time 14:33 Sent To  
Notes
***NONE***