Plan Review Details - Permit 20091213
Plan Review Stops For Permit 20091213
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-10-09 Cont ID  
Sent By jgomez Date 2020-10-09 Time 11:20 Rev Time 0.00
Received By jgomez Date 2020-10-09 Time 09:01 Sent To  
Notes
2020-10-09 11:27:17BUILDING REVIEW APPROVED WITH PROVISO:
 1-VERIFY HEADROOM CLEARANCE AT STAIR LANDING AREA AND
 SECOND FLOOR ABOVE. NEED 80 INCHES MIN. SEC. 1011.3
 FBC-BUILDING.
 2-VERIFY PLANTER HEIGHT TO COMPLY WITH THE BARRIER
 HEIGHT OF 27 INCHES AS REQUIRED BY SEC. 307.4
 FBC-ACCESSIBILITY FOR REQUIRED VERTICAL CLEARANCE BELOW
 STAIRWAY.
 3-) WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-10-06 Cont ID  
Sent By jleahy Date 2020-10-06 Time 12:02 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-10-08 Cont ID  
Sent By pleduc Date 2020-10-08 Time   Rev Time 0.00
Received By pleduc Date 2020-10-08 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-04 Cont ID  
Sent By lcrespo Date 2020-12-04 Time 14:37 Rev Time 0.00
Received By lcrespo Date 2020-12-02 Time 14:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 10:44 Rev Time 0.00
Received By equinone Date 2020-09-28 Time 18:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-09-29 Cont ID  
Sent By medwards Date 2020-09-29 Time 07:08 Rev Time 0.00
Received By medwards Date 2020-09-29 Time 06:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By lcrespo Date 2020-12-04 Time 14:37 Rev Time 0.00
Received By lcrespo Date 2020-12-04 Time 14:37 Sent To  
Notes
2020-12-04 14:38:3012/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-10-01 Cont ID  
Sent By lcrespo Date 2020-10-01 Time 15:28 Rev Time 0.00
Received By lcrespo Date 2020-10-01 Time 13:52 Sent To  
Notes
2020-10-01 15:29:16010/01/20 1ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB IRRIGATION PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE CALCULATIONS FOR STORM DRAIN SIZING
 INCLUDING THE EXISTING THAT THE NEW DRAIN IS TO CONNECT
 TO. INCLUDE THE IMPACT OF THE IRRIGATION SYSTEM ON THE
 DRAINAGE SYSTEM.
  
 3. PLEASE DETAIL OR PROVIDE SPECIFIC SPECIFICATION AND
 TESTING STANDARDS IF CORRUGATED PIPE AND FITTINGS WILL
 BE USED TO PECULATE WATER FROM PLANTER IN COMPLIANCE
 WITH FBC PL TABLES 702.1 AND 702.4.
  
 4. PLEASE PROVIVE WHERE ALL STORM DRAIN CONNECTIONS ARE
 SHOWN ON THE SITE/CIVIL DRAWINGS PER THE WPB FBC
 107.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By lcrespo Date 2020-12-04 Time 14:37 Rev Time 0.00
Received By lcrespo Date 2020-12-04 Time 14:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-20 Cont ID  
Sent By equinone Date 2020-10-20 Time 10:43 Rev Time 0.00
Received By equinone Date 2020-10-20 Time 10:43 Sent To  
Notes
2020-10-06 12:03:35ELECTRIC PAGE SIGNATURE IS GOOD TO GO JLEAHY

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-13 Cont ID  
Sent By eschneid Date 2020-10-13 Time 11:10 Rev Time 0.50
Received By eschneid Date 2020-10-13 Time 10:48 Sent To  
Notes
***NONE***