Plan Review Details - Permit 20091114
Plan Review Stops For Permit 20091114
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By cpuell Date 2021-04-20 Time 16:07 Rev Time 0.00
Received By cpuell Date 2021-04-20 Time 16:07 Sent To  
Notes
2021-04-20 16:12:27ADDRESS OF 8130 N JOG RD TO REMAIN, PBSO WILL BE
 READDRESSING THE PARCEL.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By cpuell Date 2021-03-12 Time 12:41 Rev Time 0.00
Received By cpuell Date 2021-03-12 Time 12:41 Sent To  
Notes
2021-03-12 12:42:16PLEASE REACH OUT TO [email protected] TO DISCUSS
 ADDRESSING OPTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-19 Cont ID  
Sent By jwitmer Date 2023-04-19 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2023-04-17 Time 13:30 Sent To  
Notes
2023-04-19 08:04:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091114 / APPLICATION DATE 09/24/2020
 UNDER THE 2017 FBC-BUILDING
 ADD: 8130 N. JOG RD.
 CONT: THE WEITZ COMPANY
 TEL: 561-585-5511
 E-MAIL: LAUREN@[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. APRIL 19TH/ 2023
 ACTION: DENIED
 MONDAY APRIL 17TH, I SPOKE WITH JOE COLOME OF COLOME &
 ASSOCIATES ABOUT THIS PROJECT. WITHOUT STATE APPROVED
 PLANS SHOWING THE MODULAR BUILDING WAS DESIGNED AS
 SHOWN ON SHEET A-1, THAT NO REMODELING WAS OR IS GOING
 TO TAKE PLACE TO THIS MODULAR BUILDING. OTHERWISE THE
 STRUCTURE LOSES ITS STATE APPROVAL, THE INSIGNIA IS
 REMOVED AND RETURNED TO THE STATE. A COMPLETE SET OF
 PLANS WOULD BE REQUIRED FOR THE STRUCTURE FOR ALL
 TRADES INCLUDING THE ENERGY CODE, PRODUCT APPROVAL
 WINDOWS, DOORS AND ROOFING, WIND DESIGN MATE LINE
 FASTENING SCHEDULE, ANCHORING SCHEDULE AND MONOLITHIC
 SLAB IF PART OF THIS PERMIT. MR. COLOME WAS GOING TO
 GET IN TOUCH WITH THE CONTRACTOR THE WEITZ CO. IN
 REGARDS WITH THIS MATTER TO DATE THERE HAS BEEN NO
 FURTHER RESPONSE FROM THE DESIGNER OF RECORD NOR
 CONTRACTOR.
  
 1) THE LIFE SAFETY SHEET:
 1A) TO BE REVIEWED UNDER THE 2020 FBC-BUILDING CODE.
 THIS REVIEW WILL NOT HAPPEN UNTIL EITHER STATE APPROVED
 MODULAR BUILDING PLANS ARE SUBMITTED WITH NO INTERIOR
 CHANGES, OR IT IS STATED IN THE PLANS THAT THE STATE
 APPROVED MODULAR BUILDINGS INTERIOR IS BEING REMODELED
 WHERE THE MODULAR BUILDING LOSES ITS STATE APPROVAL AND
 THEN THE DESIGNER OF RECORD HAS TO PROVIDE ALL OF THE
 PLANS, PRODUCT APPROVALS, ENERGY CALCULATIONS TIE DOWN
 AND PERMANENT FOUNDATIONS AND BRACING AND MATE LINE
 CONNECTIONS. WITH THAT BEING SAID IT MAY ALSO REQUIRE
 ADDITIONAL SITE INSPECTIONS THAT WOULD NORMALLY HAVE
 BEEN COMPLETED AT THE FACTORY. NEVER WOULD
 MANUFACTURERED BUILDING PLAN BE CONSIDERED A DEFERRED
 SUBMITTAL.
  
 F. S. 553 PART IV
  
 FS 428.5.1 ON SITE MODIFICATIONS. ON-SITE MODIFICATION
 TO MANUFACTURED BUILDINGS MUST BE INSPECTED BY EITHER A
 THIRD PARTY AGENCY
 OR BY THE AUTHORITY HAVING JURISDICTION AND MUST COMPLY
 WITH THE FLORIDA BUILDING CODE . THE AUTHORITY HAVING
 JURISDICTION HAS SUPERSEDING AUTHORITY OVER ANY ONSITE
 MODIFICATIONS TO A MANUFACTURED BUILDING OR MAY
 DELEGATE THIS AUTHORITY TO THE DEPARTMENT IN WRITING ON
 A CASE-BYCASE BASIS. UPON ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE MODIFIED MANUFACTURED BUILDING, THE
 OLD INSIGNIA SHALL BE REMOVED AND RETURNED TO THE
 DEPARTMENT.
  
 THIS REVIEW CAN NOT CONTINUE UNTIL THE STATE CERTIFIED
 PLANS ARE SUBMITTED.
  
 1B) PLEASE NOTE THE SUBMITTED LIFE SAFETY SHEET ALSO
 REFERENCES RENOVATIONS TO P B C FIRE-RESCUE STATION #
 21 PLEASE UPDATE PLANS FOR THIS PROJECT, FIRE-RESCUE #
 17. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE HEADING OF OCCUPANT LOADS THERE IS A
 COUNT OF OCCUPANTS BUT THE SQUARE FEET FOR EACH
 OCCUPANCY NOR THE OCCUPANT LOAD FACTOR IS GIVEN. 2017
 FBC-B TABLE 1004.1.2.
  
 1D) THE FLOOR PLAN INDICATES THE (2) END WALLS REQUIRE
 A 1 HOUR RATING OF THE EXTERIOR WALL, THERE ARE NO
 SECTIONS THROUGH THE PLAN INDICATING HOW THIS WILL BE
 ACHIEVED, AND COMPLIANCE WITH TABLE 602 OF THE 2017
 FBC-BUILDING CODE. THE LEFT-HAND SIDE OF THE SHEET
 THERE IS NO ASSUMED PROPERTY LINE ESTABLISHED LIKE
 THERE IS ON THE RIGHT SIDE.
  
 2) SHEET A-6 DETAILS 1, 2, 6 & 7 ALL SHOW THE BOTTOM
 CABINETS AT A HEIGHT OF 36 INCHES TOP OF COUNTERTOP AND
 SOME WITH EITHER SINKS AND OR LAVATORIES.
 2017 FBC-ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET S-3:
 3A) SHOWS FOUNDATION INFORMATION, ONE THING THIS SHEET
 DOES NOT PROVIDE IS TO WHAT WIND SPEED WAS THIS
 FOUNDATION (MANUFACTURED BUILDING) DESIGNED FOR. 2017
 TABLE 2604.5 RISK CATEGORY OF BUILDINGS AND OTHER
 STRUCTURES? RISK FACTOR IV FIRE, RESCUE AMBULANCE AND
 POLICE STATIONS AND EMERGENCY VEHICLE GARAGES.
  
 3B) THE PLAN INDICATES TE-2 INDICATES A THICKENED EDGE
 12 X 12 THICKENED SLAB, WHAT THE PLAN DOES NOT INDICATE
 WHERE IS FINISHED GRADE IN RELATIONSHIP TO THE TOP OF
 THE THICKENED SLAB, HOW MUCH OF THE FOUNDATION IS
 BENEATH THE GRADE AND IN COMPLIANCE WITH THE 2017 FBC-B
 1809.4 THE MINIMUM DEPTH OF FOOTINGS BELOW THE
 UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
  
 4) WITHIN THIS SET OF PLANS THERE IS NO INFORMATION ON
 THE PRE-ENGINEERED PRECAST CONCRETE, RAMPS, LANDINGS,
 STEPS & LANDING. WHO IS IN-CHARGE OF THE INSPECTIONS
 WHEN THESE COMPONENTS ARE BEING ASSEMBLED, IS PART OF
 THE MANUFACTURED BUILDING PROGRAM? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-B LIVE LOADS TABLE 1607.1.
  
 5) THERE WAS NO INFORMATION SUBMITTED FOR THE
 GUARDRAILS NOR HANDRAIL SYSTEMS AND HOW THEY ARE TO BE
 INSTALLED/ ANCHORED. 2017 FBC-B HANDRAILS SECTION 1014.
 GUARDS SECTION 1015, 1607.8.1 HANDRAILS AND GUARDS.
  
 6) FOR MANUFACTURED BUILDINGS UNDER THE FLORIDA MODULAR
 BUILDING PROGRAM THEY ARE APPROVED UNDER THE STATE BUT
 YOU STILL HAVE TO SUPPLY THE STATE APPROVED PLANS, THEY
 WILL NOT BE SIGNED AND SEALED BUT THEY WILL HAVE THE
 MANUFACTURER AND THE 3RD PARTY INSPECTION ENTITY AND
 PLAN REVIEW NUMBER SO WE CAN VERIFY THAT NO REMODELING
 OR CHANGES TO THE INTERIOR OF THE APPROVED STATE PLANS,
 OTHERWISE IT VOIDS THE STATE APPROVAL.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-24 Cont ID  
Sent By jwitmer Date 2021-08-24 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2021-08-24 Time 11:28 Sent To  
Notes
2021-08-24 13:26:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091114 / APPLICATION DATE 09/24/2020
 UNDER THE 2017 FBC-BUILDING
 ADD: 8130 N. JOG RD.
 CONT: THE WEITZ COMPANY
 TEL: 561-585-5511
 E-MAIL: LAUREN@[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY AUGUST 24TH / 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET:
  
 1A) TO BE REVIEWED UNDER THE 2020 FBC-BUILDING CODE.
 THIS REVIEW WILL NOT HAPPEN UNTIL EITHER STATE APPROVED
 MODULAR BUILDING PLANS ARE SUBMITTED WITH NO INTERIOR
 CHANGES, OR IT IS STATED IN THE PLANS THAT THE STATE
 APPROVED MODULAR BUILDINGS INTERIOR IS BEING REMODELED
 WHERE THE MODULAR BUILDING LOSES ITS STATE APPROVAL AND
 THEN THE DESIGNER OF RECORD HAS TO PROVIDE ALL OF THE
 PLANS, PRODUCT APPROVALS, ENERGY CALCULATIONS TIE DOWN
 AND PERMANENT FOUNDATIONS AND BRACING AND MATE LINE
 CONNECTIONS. WITH THAT BEING SAID IT MAY ALSO REQUIRE
 ADDITIONAL SITE INSPECTIONS THAT WOULD NORMALLY HAVE
 BEEN COMPLETED AT THE FACTORY. NEVER WOULD
 MANUFACTURERED BUILDING PLAN BE CONSIDERED A DEFERRED
 SUBMITTAL.
  
 F. S. 553 PART IV
  
 FS 428.5.1 ON SITE MODIFICATIONS. ON-SITE MODIFICATION
 TO MANUFACTURED BUILDINGS MUST BE INSPECTED BY EITHER A
 THIRD PARTY AGENCY
 OR BY THE AUTHORITY HAVING JURISDICTION AND MUST COMPLY
 WITH THE FLORIDA BUILDING CODE . THE AUTHORITY HAVING
 JURISDICTION HAS SUPERSEDING AUTHORITY OVER ANY ONSITE
 MODIFICATIONS TO A MANUFACTURED BUILDING OR MAY
 DELEGATE THIS AUTHORITY TO THE DEPARTMENT IN WRITING ON
 A CASE-BYCASE BASIS. UPON ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE MODIFIED MANUFACTURED BUILDING, THE
 OLD INSIGNIA SHALL BE REMOVED AND RETURNED TO THE
 DEPARTMENT.
  
 THIS REVIEW CAN NOT CONTINUE UNTIL THE STATE CERTIFIED
 PLANS ARE SUBMITTED.
  
 1B) PLEASE NOTE THE SUBMITTED LIFE SAFETY SHEET ALSO
 REFERENCES RENOVATIONS TO P B C FIRE-RESCUE STATION #
 21 PLEASE UPDATE PLANS FOR THIS PROJECT, FIRE-RESCUE #
 17. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE HEADING OF OCCUPANT LOADS THERE IS A
 COUNT OF OCCUPANTS BUT THE SQUARE FEET FOR EACH
 OCCUPANCY NOR THE OCCUPANT LOAD FACTOR IS GIVEN. 2017
 FBC-B TABLE 1004.1.2.
  
 1D) THE FLOOR PLAN INDICATES THE (2) END WALLS REQUIRE
 A 1 HOUR RATING OF THE EXTERIOR WALL, THERE ARE NO
 SECTIONS THROUGH THE PLAN INDICATING HOW THIS WILL BE
 ACHIEVED, AND COMPLIANCE WITH TABLE 602 OF THE 2017
 FBC-BUILDING CODE. THE LEFT-HAND SIDE OF THE SHEET
 THERE IS NO ASSUMED PROPERTY LINE ESTABLISHED LIKE
 THERE IS ON THE RIGHT SIDE.
  
 2) SHEET A-6 DETAILS 1, 2, 6 & 7 ALL SHOW THE BOTTOM
 CABINETS AT A HEIGHT OF 36 INCHES TOP OF COUNTERTOP AND
 SOME WITH EITHER SINKS AND OR LAVATORIES.
 2017 FBC-ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET S-3:
 3A) SHOWS FOUNDATION INFORMATION, ONE THING THIS SHEET
 DOES NOT PROVIDE IS TO WHAT WIND SPEED WAS THIS
 FOUNDATION (MANUFACTURED BUILDING) DESIGNED FOR. 2017
 TABLE 2604.5 RISK CATEGORY OF BUILDINGS AND OTHER
 STRUCTURES? RISK FACTOR IV FIRE, RESCUE AMBULANCE AND
 POLICE STATIONS AND EMERGENCY VEHICLE GARAGES.
  
 3B) THE PLAN INDICATES TE-2 INDICATES A THICKENED EDGE
 12 X 12 THICKENED SLAB, WHAT THE PLAN DOES NOT INDICATE
 WHERE IS FINISHED GRADE IN RELATIONSHIP TO THE TOP OF
 THE THICKENED SLAB, HOW MUCH OF THE FOUNDATION IS
 BENEATH THE GRADE AND IN COMPLIANCE WITH THE 2017 FBC-B
 1809.4 THE MINIMUM DEPTH OF FOOTINGS BELOW THE
 UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
  
 4) WITHIN THIS SET OF PLANS THERE IS NO INFORMATION ON
 THE PRE-ENGINEERED PRECAST CONCRETE, RAMPS, LANDINGS,
 STEPS & LANDING. WHO IS IN-CHARGE OF THE INSPECTIONS
 WHEN THESE COMPONENTS ARE BEING ASSEMBLED, IS PART OF
 THE MANUFACTURED BUILDING PROGRAM? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-B LIVE LOADS TABLE 1607.1.
  
 5) THERE WAS NO INFORMATION SUBMITTED FOR THE
 GUARDRAILS NOR HANDRAIL SYSTEMS AND HOW THEY ARE TO BE
 INSTALLED/ ANCHORED. 2017 FBC-B HANDRAILS SECTION 1014.
 GUARDS SECTION 1015, 1607.8.1 HANDRAILS AND GUARDS.
  
 6) FOR MANUFACTURED BUILDINGS UNDER THE FLORIDA MODULAR
 BUILDING PROGRAM THEY ARE APPROVED UNDER THE STATE BUT
 YOU STILL HAVE TO SUPPLY THE STATE APPROVED PLANS, THEY
 WILL NOT BE SIGNED AND SEALED BUT THEY WILL HAVE THE
 MANUFACTURER AND THE 3RD PARTY INSPECTION ENTITY AND
 PLAN REVIEW NUMBER SO WE CAN VERIFY THAT NO REMODELING
 OR CHANGES TO THE INTERIOR OF THE APPROVED STATE PLANS,
 OTHERWISE IT VOIDS THE STATE APPROVAL.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
 THIS REVIEW CAN NOT CONTINUE UNTIL THE STATE CERTIFIED
 PLANS ARE SUBMITTED.
  
 1B) PLEASE NOTE THE SUBMITTED LIFE SAFETY SHEET ALSO
 REFERENCES RENOVATIONS TO P B C FIRE-RESCUE STATION #
 21 PLEASE UPDATE PLANS FOR THIS PROJECT, FIRE-RESCUE #
 17. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE HEADING OF OCCUPANT LOADS THERE IS A
 COUNT OF OCCUPANTS BUT THE SQUARE FEET FOR EACH
 OCCUPANCY NOR THE OCCUPANT LOAD FACTOR IS GIVEN. 2017
 FBC-B TABLE 1004.1.2.
  
 1D) THE FLOOR PLAN INDICATES THE (2) END WALLS REQUIRE
 A 1 HOUR RATING OF THE EXTERIOR WALL, THERE ARE NO
 SECTIONS THROUGH THE PLAN INDICATING HOW THIS WILL BE
 ACHIEVED, AND COMPLIANCE WITH TABLE 602 OF THE 2017
 FBC-BUILDING CODE. THE LEFT-HAND SIDE OF THE SHEET
 THERE IS NO ASSUMED PROPERTY LINE ESTABLISHED LIKE
 THERE IS ON THE RIGHT SIDE.
  
 2) SHEET A-6 DETAILS 1, 2, 6 & 7 ALL SHOW THE BOTTOM
 CABINETS AT A HEIGHT OF 36 INCHES TOP OF COUNTERTOP AND
 SOME WITH EITHER SINKS AND OR LAVATORIES.
 2017 FBC-ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET S-3:
 3A) SHOWS FOUNDATION INFORMATION, ONE THING THIS SHEET
 DOES NOT PROVIDE IS TO WHAT WIND SPEED WAS THIS
 FOUNDATION (MANUFACTURED BUILDING) DESIGNED FOR. 2017
 TABLE 2604.5 RISK CATEGORY OF BUILDINGS AND OTHER
 STRUCTURES? RISK FACTOR IV FIRE, RESCUE AMBULANCE AND
 POLICE STATIONS AND EMERGENCY VEHICLE GARAGES.
  
 3B) THE PLAN INDICATES TE-2 INDICATES A THICKENED EDGE
 12 X 12 THICKENED SLAB, WHAT THE PLAN DOES NOT INDICATE
 WHERE IS FINISHED GRADE IN RELATIONSHIP TO THE TOP OF
 THE THICKENED SLAB, HOW MUCH OF THE FOUNDATION IS
 BENEATH THE GRADE AND IN COMPLIANCE WITH THE 2017 FBC-B
 1809.4 THE MINIMUM DEPTH OF FOOTINGS BELOW THE
 UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
  
 4) WITHIN THIS SET OF PLANS THERE IS NO INFORMATION ON
 THE PRE-ENGINEERED PRECAST CONCRETE, RAMPS, LANDINGS,
 STEPS & LANDING. WHO IS IN-CHARGE OF THE INSPECTIONS
 WHEN THESE COMPONENTS ARE BEING ASSEMBLED, IS PART OF
 THE MANUFACTURED BUILDING PROGRAM? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-B LIVE LOADS TABLE 1607.1.
  
 5) THERE WAS NO INFORMATION SUBMITTED FOR THE
 GUARDRAILS NOR HANDRAIL SYSTEMS AND HOW THEY ARE TO BE
 INSTALLED/ ANCHORED. 2017 FBC-B HANDRAILS SECTION 1014.
 GUARDS SECTION 1015, 1607.8.1 HANDRAILS AND GUARDS.
  
 6) FOR MANUFACTURED BUILDINGS UNDER THE FLORIDA MODULAR
 BUILDING PROGRAM THEY ARE APPROVED UNDER THE STATE BUT
 YOU STILL HAVE TO SUPPLY THE STATE APPROVED PLANS, THEY
 WILL NOT BE SIGNED AND SEALED BUT THEY WILL HAVE THE
 MANUFACTURER AND THE 3RD PARTY INSPECTION ENTITY AND
 PLAN REVIEW NUMBER SO WE CAN VERIFY THAT NO REMODELING
 OR CHANGES TO THE INTERIOR OF THE APPROVED STATE PLANS,
 OTHERWISE IT VOIDS THE STATE APPROVAL.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-04-05 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2021-04-05 Time 14:27 Sent To  
Notes
2021-04-05 16:52:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091114 / APPLICATION DATE 09/24/2020
 UNDER THE 2017 FBC-BUILDING
 ADD: 8130 N. JOG RD.
 CONT: THE WEITZ COMPANY
 TEL: 561-585-5511
 E-MAIL: LAUREN@[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 05/ 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET:
 1A) THE PERMIT APPLICATION CAME IN FOR THIS PROJECT
 SEPT. 24TH/ 2020. APPLICANT WAS INVITED TO UPLOAD PLANS
 AND PAY FEES. LESS THAN 6 MONTHS WENT BY WITH NO
 ACTIVITY ON 3/11/2021 FEES WERE PAID AND PLANS WERE
 UPLOADED KEEPING THE PERMIT APPLICATION LIVE UNDER THE
 6TH EDITION OR 2017 FBC-BUILDING CODE. THE PLANS
 UPLOADED REFER TO THE 2020 FBC-B 7TH EDITION PLEASE
 CORRECT ALL REFERENCES TO THE 2020 FLORIDA BUILDING
 CODE- BUILDING.
  
 1B) PLEASE NOTE THE SUBMITTED LIFE SAFETY SHEET ALSO
 REFERENCES RENOVATIONS TO P B C FIRE-RESCUE STATION #
 21 PLEASE UPDATE PLANS FOR THIS PROJECT, FIRE-RESCUE #
 17. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE HEADING OF OCCUPANT LOADS THERE IS A
 COUNT OF OCCUPANTS BUT THE SQUARE FEET FOR EACH
 OCCUPANCY NOR THE OCCUPANT LOAD FACTOR IS GIVEN. 2017
 FBC-B TABLE 1004.1.2.
  
 1D) THE FLOOR PLAN INDICATES THE (2) END WALLS REQUIRE
 A 1 HOUR RATING OF THE EXTERIOR WALL, THERE ARE NO
 SECTIONS THROUGH THE PLAN INDICATING HOW THIS WILL BE
 ACHIEVED, AND COMPLIANCE WITH TABLE 602 OF THE 2017
 FBC-BUILDING CODE. THE LEFT-HAND SIDE OF THE SHEET
 THERE IS NO ASSUMED PROPERTY LINE ESTABLISHED LIKE
 THERE IS ON THE RIGHT SIDE.
  
 2) SHEET A-6 DETAILS 1, 2, 6 & 7 ALL SHOW THE BOTTOM
 CABINETS AT A HEIGHT OF 36 INCHES TOP OF COUNTERTOP AND
 SOME WITH EITHER SINKS AND OR LAVATORIES.
 2017 FBC-ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET S-3:
 3A) SHOWS FOUNDATION INFORMATION, ONE THING THIS SHEET
 DOES NOT PROVIDE IS TO WHAT WIND SPEED WAS THIS
 FOUNDATION (MANUFACTURED BUILDING) DESIGNED FOR. 2017
 TABLE 2604.5 RISK CATEGORY OF BUILDINGS AND OTHER
 STRUCTURES? RISK FACTOR IV FIRE, RESCUE AMBULANCE AND
 POLICE STATIONS AND EMERGENCY VEHICLE GARAGES.
  
 3B) THE PLAN INDICATES TE-2 INDICATES A THICKENED EDGE
 12 X 12 THICKENED SLAB, WHAT THE PLAN DOES NOT INDICATE
 WHERE IS FINISHED GRADE IN RELATIONSHIP TO THE TOP OF
 THE THICKENED SLAB, HOW MUCH OF THE FOUNDATION IS
 BENEATH THE GRADE AND IN COMPLIANCE WITH THE 2017 FBC-B
 1809.4 THE MINIMUM DEPTH OF FOOTINGS BELOW THE
 UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
  
 4) WITHIN THIS SET OF PLANS THERE IS NO INFORMATION ON
 THE PRE-ENGINEERED PRECAST CONCRETE, RAMPS, LANDINGS,
 STEPS & LANDING. WHO IS IN-CHARGE OF THE INSPECTIONS
 WHEN THESE COMPONENTS ARE BEING ASSEMBLED, IS PART OF
 THE MANUFACTURED BUILDING PROGRAM? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-B LIVE LOADS TABLE 1607.1.
  
 5) THERE WAS NO INFORMATION SUBMITTED FOR THE
 GUARDRAILS NOR HANDRAIL SYSTEMS AND HOW THEY ARE TO BE
 INSTALLED/ ANCHORED. 2017 FBC-B HANDRAILS SECTION 1014.
 GUARDS SECTION 1015, 1607.8.1 HANDRAILS AND GUARDS.
  
 6) FOR MANUFACTURED BUILDINGS UNDER THE FLORIDA MODULAR
 BUILDING PROGRAM THEY ARE APPROVED UNDER THE STATE BUT
 YOU STILL HAVE TO SUPPLY THE STATE APPROVED PLANS, THEY
 WILL NOT BE SIGNED AND SEALED BUT THEY WILL HAVE THE
 MANUFACTURER AND THE 3RD PARTY INSPECTION ENTITY AND
 PLAN REVIEW NUMBER SO WE CAN VERIFY THAT NO REMODELING
 OR CHANGES TO THE INTERIOR OF THE APPROVED STATE PLANS,
 OTHERWISE IT VOIDS THE STATE APPROVAL.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By jleahy Date 2021-09-24 Time 09:38 Rev Time 0.00
Received By jleahy Date 2021-09-23 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By equinone Date 2021-04-05 Time 12:11 Rev Time 0.00
Received By equinone Date 2021-04-05 Time 12:11 Sent To  
Notes
2021-04-05 12:11:39CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) COVER SHEET (INDEX OF DRAWINGS) AND E-1 BOTH
 MENTIONS AN E-3 DRAWING (ELECTRICAL FLOOR PLAN -
 DEMOLITION PLAN) THAT HAS NOT BEEN UPLOADED/SUBMITTED.
 PLEASE UPLOAD THIS DRAWING. FBC 107
  
  
 2) SHEET E-7 NEW ONE-LINE DIAGRAM SHOWS TWO PANELS "P1"
 WHILE E-9 SHOWS ONE PANEL P1 AND ONE PANEL P2 BOTH
 EXISTING. PLEASE CORRECT NEW ONE-LINE DIAGRAM TO
 INDICATE WHICH ONE IS P1 AND WHICH ONE IS P2. FBC 107
  
 3) PLEASE SHOW LOCATIONS OF PANELS P-1 AND P-2 - FBC
 107
  
 5) DRAWINGS SPECIFY THAT THIS IS A NEW SINGLE STORY
 PRE-MANUFACTURED BUILDING AND SHEETS E-4 AND E-5
 INDICATES THAT LIGHTING AND POWER CIRCUITS IN THE NEW
 BUILDING ARE COMING FROM PANEL P-1.
 IF THIS IS A NEW BUILDING HOW IS IT THAT ALL CIRCUITS
 ARE COMING FROM AN EXISTING PANEL P-1. PLEASE CLARIFY.
 FBC 107
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
 THE RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS:
 PHONE: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2023-04-21 Cont ID  
Sent By lquinone Date 2023-04-21 Time 15:29 Rev Time 0.00
Received By lquinone Date 2023-04-21 Time 15:29 Sent To  
Notes
2023-04-21 15:29:59REPEATED COMMENT:
  
 A FORMAL ENGINEERING SUBMITTAL IS REQUIRED.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By rrossano Date 2021-08-31 Time   Rev Time 0.00
Received By rrossano Date 2021-08-31 Time   Sent To  
Notes
2021-08-31 13:58:08A FORMAL ENGINEERING SUBMITTAL IS REQUIRED.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 [email protected] WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-03-31 Cont ID  
Sent By rrossano Date 2021-03-31 Time   Rev Time  
Received By rrossano Date 2021-03-31 Time   Sent To  
Notes
2021-03-31 10:53:38PLEASE ADDRESS ZONING DEPT. COMMENST.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-13 Cont ID  
Sent By pleduc Date 2021-08-13 Time   Rev Time 0.00
Received By pleduc Date 2021-08-13 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By pleduc Date 2021-03-16 Time   Rev Time 0.00
Received By pleduc Date 2021-03-15 Time 16:15 Sent To  
Notes
2021-03-16 12:19:09THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS & MECHANICAL - THEE ARE NO INDICATIONS OF A
 HOOD NOR A FIRE SUPPRESSION SYSTEM OVER THE COOKING
 EQUIPMENT.
  
 PER NFPA 1
  
 50.2 GENERAL REQUIREMENTS.
 50.2.1 GENERAL.
 50.2.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST
 SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE
 REQUIREMENTS OF THIS CHAPTER.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC CODE
 REFRERNCES AND NARRATIVE STATING WHY IT IS NOT
 REQUIRED.
  
  
 2) THERE ARE INDICATIONS OF FIRE LINE UNDERGROUND DEMO
 AND NEW LINE.
  
 ALL FIRE LINE WORK SHALL COMPLY WITH NFPA 24, BE
 INSTALLED BY A CERTIFIED UNDERGROUND CONTRACTOR AND BE
 SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) SHEET LS & A1 - THERE IS AN INDICATION OF A THE
 FRONT BATHROOM, WOMAN 111, DOOR THAT OPENS OUT INTO THE
 EXIT CORRIDOR AND ENCROACHES ON THE REQUIRED EGRESS
 PATH WIDTH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND CORRECT, SWING THE DOOR IN OR PROVIDE
 SPECIFIC DIMENSIONS MEETING THE REQUIREMENTS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-09-09 Cont ID  
Sent By ccole Date 2021-09-09 Time 14:36 Rev Time 0.00
Received By ccole Date 2021-09-09 Time 11:38 Sent To  
Notes
2021-09-09 14:39:17PERMIT NOT REQUIRED FOR PORTABLE LP GAS GRILL.
 PERMANENT INSTALLATION OF THE GRILL WILL REQUIRE A
 SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-13 Cont ID  
Sent By ccole Date 2021-04-13 Time 16:38 Rev Time 0.00
Received By ccole Date 2021-04-13 Time 16:18 Sent To  
Notes
2021-04-13 16:38:261ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 20091114
 4/13/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS PIPING RISER DRAWING FOR THE RELOCATED
 TANK AND GRILL- SECTION 107.3.5.1.5 WPB.
  
 2) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE
 REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL
 SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH
 THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW
 HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND
 WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58.
  
 3) CLARIFY IF THE BBQ GRILL WILL BE PORTABLE OR
 PERMANENTLY INSTALLED- SECTION 107.2.1 WPB. PROVIDE
 CONSTRUCTION DETAILS FOR PERMANENT INSTALLATION IF
 APPLICABLE INCLUDING HOW THE APPLIANCE WILL BE ANCHORED
 TO RESIST WIND PRESSURES- SECTION 301.10 FBC FG.
  
 4) PROVIDE GRILL CLEARANCES TO COMBUSTIBLES, AND TO AIR
 INTAKES AND OPENINGS INTO THE BUILDING- SECTION 623.1
 FBC FG.
  
 5) CLARIFY IF ANY NEW INTERIOR GAS APPLIANCES WILL BE
 INSTALLED AND PROVIDE COMPLETE RISER DRAWINGS,
 COMBUSTION AIR CALCULATIONS, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 305.1 FBC FG AND SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-05-01 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-12 Time 18:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-24 Cont ID  
Sent By jleahy Date 2021-09-24 Time 09:50 Rev Time 0.00
Received By jleahy Date 2021-08-12 Time 10:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-13 Time   Rev Time 0.00
Received By ccarvaja Date 2021-03-11 Time 16:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By jwitmer Date 2021-04-05 Time 16:47 Rev Time 0.00
Received By jwitmer Date 2021-04-05 Time 14:27 Sent To  
Notes
2021-04-05 16:48:58NO IMPACT FEES, GOVERNMENT INTENTY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-27 Cont ID  
Sent By medwards Date 2021-08-27 Time 17:12 Rev Time 0.00
Received By medwards Date 2021-08-27 Time 17:12 Sent To  
Notes
2021-08-27 17:13:53 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 09:12 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 08:26 Sent To  
Notes
2021-04-08 09:13:121ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20091114
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ATTACH A NOTE TO THE MECHANICAL DRAWINGS
 STATING THAT THE KITCHEN HOOD AND RELATED GREASE DUCT
 AND MAKEUP AIR WILL BE SUBMITTED UNDER A SEPARATE
 PERMIT AND PLAN REVIEW.
  
 2) PLEASE REMOVE THE KITCHEN HOOD AND GREASE DUCT PLANS
 FROM THIS SUBMITTAL AND PLEASE SUBMIT THE REQUIRED
 STATE APPROVED PLANS FOR THIS MODULAR BUILDING. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-04-24 Cont ID  
Sent By ccole Date 2023-04-24 Time 10:20 Rev Time 0.00
Received By ccole Date 2023-04-24 Time 08:28 Sent To  
Notes
2023-04-24 10:21:243RD REVIEW FBC-2020 PLUMBING
 PERMIT- 20091114
 4/24/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVIEW THE BUILDING REVIEW COMMENTS AND NOTE
 FINAL APPROVAL OF THE PLUMBING PLANS CANNOT BE
 ACCOMPLISHED UNTIL THOSE ISSUES CONCERNING STATE
 APPROVED PLANS AND SITE MODIFICATIONS ARE RESOLVED.
  
 2) SHEETS P-1, P-2, & P-3: BASED ON SEC. 1003.3.2 FBC P
 THE FOOD WASTE DISPOSER UNDER THE KITCHEN SINK SHALL
 NOT DISCHARGE TO THE GREASE INTERCEPTOR. PROVIDE A
 SOLIDS INTERCEPTOR OR REMOVE THE DISPOSER. THE SINKS
 (S1 & S2 AND THE RELOCATED 3-COMPARTMENT SINK ON THE
 EXTERIOR) ARE ALSO REQUIRE TO HAVE INDIRECT WASTE
 RECEPTORS IF USED FOR FOOD HANDLING OR DISHWASHING-
 SEC. 802.1 FBC P.
  
 3) DUE TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR
 PERMIT APPLICATION IS REQUIRED TO BE SUBMITTED PRIOR TO
 FINAL APPROVAL OF THE PLUMBING PLAN REVIEW. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected] . YOU
 WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS.
 YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT
 THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-09-09 Cont ID  
Sent By ccole Date 2021-09-09 Time 14:23 Rev Time 0.00
Received By ccole Date 2021-09-09 Time 11:38 Sent To  
Notes
2021-09-09 14:24:072ND REVIEW FBC-2020 PLUMBING
 PERMIT- 20091114
 9/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP-1: SHOW THE ACCESSIBLE ROUTE TO THE NEW
 DRINKING FOUNTAIN- SECTION 206.2.2 & 402.1 FBC ACC.
  
 2) A1, A5, A6: A CLEAR FLOOR SPACE DESIGNED FOR FORWARD
 APPROACH IS SHOWN AT SINK S-1 IN THE KITCHEN HOWEVER
 THE PLUMBING PLANS INDICATE THAT INDIRECT WASTE IS
 BEING PROVIDED. PLEASE PROVIDE A DETAIL SHOWING THE
 REQUIRED KNEE AND TOE CLEARANCES AT THE SINK- SEE
 FIGURES 306.2 & 306.3 FBC ACC.
  
 3) A1: THE WATER CLOSET 54-INCH CLEAR FLOOR SPACE
 DIMENSIONS MEASURED PERPENDICULAR FROM THE REAR WALLS
 IS INCORRECT- 56 INCHES MINIMUM REQUIRED- SECTION
 604.3.1 FBC ACC.
  
 4) A5: MISSING OR INCORRECT ACCESSIBILITY COMPLIANCE
 DETAILS PER FBC ACC.
  
 A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 NOT PROVIDED- SECTION 604.2.
  
 B) THE REAR WATER CLOSET GRAB SHALL BE POSITIONED SO
 THE BAR WILL EXTEND A MINIMUM OF 12 INCHES FROM THE
 CENTERLINE OF THE WATER CLOSET TO THE ADJACENT WALL-
 SEE FIGURE 604.5.2. PLEASE CORRECT THE DETAIL.
  
 F) PROVIDE A DETAIL SHOWING THE KNEE AND TOE CLEARANCES
 FOR THE LAVATORIES- SECTION 606.2 AND FIGURES 306.2 &
 306.3.
  
 G) MEASUREMENTS HAVE NOT BEEN PROVIDED TO SHOW THE
 LOCATIONS OF SHOWER CONTROLS, FAUCETS, AND SPRAYERS-
 SECTION 608.5.2.
  
 I) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 PLEASE ADD THE SHOWER SPRAY SPECIFICATIONS TO THE
 FIXTURE SCHEDULE- SECTION 608.6.
  
 5) A6: SHOW THE REQUIRED 1/4 INCH PER FT SLOPE FOR THE
 SHOWER PAN LINER- SECTION 417.5.2 FBC P.
  
 6) P1, P2, & P3: THE WASHING MACHINE IS REQUIRED TO
 DISCHARGE THROUGH AN INTERCEPTOR IN ACCORDANCE WITH
 SECTION 1003.6. PLEASE SHOW THE INTERCEPTOR ON THE
 DRAWINGS AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 7) P-3: THE HOT WATER RETURN CONNECTION TO THE
 THERMOSTATIC MIXING VALVE IS NOT SHOWN IN THE DETAIL-
 SECTION 607.2.2 FBC P.
  
 8) P-2, P-3: TEMPERED WATER IS REQUIRED AT THE LAVATORY
 SINKS IN ACCORDANCE WITH SECTION 419.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-13 Cont ID  
Sent By ccole Date 2021-04-13 Time 16:09 Rev Time 0.00
Received By ccole Date 2021-04-13 Time 13:26 Sent To  
Notes
2021-04-13 16:10:021ST REVIEW FBC-2020 PLUMBING
 PERMIT- 20091114
 4/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2 & P3: PROVIDE GREASE INTERCEPTOR SIZING
 CALCULATIONS, AN ENLARGED PLUMBING PIPING DETAIL, AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTIONS 1003.3.5
 FBC P. A) THE SAMPLING PORT DETAIL SHOWING A SANITARY
 CROSS WITH SUMP WHICH IS NOT ACCEPTABLE. PLEASE PROVIDE
 A SAMPLING PORT DETAIL IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS.
  
 2) P1: PLEASE PROVIDE A NOTE REQUIRING A FL. LICENSED
 PLUMBING CONTRACTOR TO OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 3) P1, P2, & P3: PROVIDE AN EQUIPMENT SCHEDULE AND
 PLUMBING PIPING DETAILS FOR THE NEW DRINKING FOUNTAINS-
 SECTIONS 107.2.1 & 107.3.5.3.1 WPB.
  
 4) P1, P2, P3: SHOW THE LOCATION OF THE REQUIRED
 SERVICE SINK AND PROVIDE AN EQUIPMENT SCHEDULE AND
 PIPING DETAILS- TABLE 403.1 FBC P.
  
 5) P2 & P3: PROVIDE THE SANITARY DRAIN AND VENT
 CONNECTIONS, AND PIPING DETAILS FOR THE RELOCATED
 3-COMPARTMENT SINK- SECTIONS 107.2.1 & 107.3.5.3.1 WPB.
 PLEASE CLARIFY THE USE OF THE SINK AND PROVIDE AN
 INDIRECT WASTE DETAIL- SECTION 802.1.1 FBC P.
  
 6) P-3: SHOW BACKFLOW PREVENTER LOCATIONS AT THE WATER
 SUPPLY LINES TO THE INTERIOR AND EXTERIOR ICE MAKERS-
 SECTION 608.3 FBC P.
  
 7) P1: THE REQUIRED ENERGY COMPLIANCE REPORT HAS NOT
 BEEN SUBMITTED. PROVIDE THE EFFICIENCY RATING OF THE
 NEW WATER HEATER IN THE EQUIPMENT SCHEDULE, AND ENTER
 THE DATA IN THE ENERGY COMPLIANCE REPORT- SEE SECTION
 C101.5.1 & TABLE C404.2 FBC EC.
  
 8) P0: PLEASE INCLUDE THE HOSE BIB IN THE PLUMBING
 FIXTURE SCHEDULE- SECTION 608.16.4.2 FBC P.
  
 9) A5 REQUIRED ACCESSIBILITY COMPLIANCE DETAILS- FBC
 ACC:
  
 A) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS-
 SECTION 604.2.
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
 C) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 G) LOCATIONS OF SHOWER CONTROLS, FAUCETS, AND SPRAYERS-
 SECTION 608.5.2.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2.
 I) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 PLEASE ADD THE SHOWER SPRAY SPECIFICATIONS TO THE
 FIXTURE SCHEDULE- SECTION 608.6.
  
 10) P3: PROVIDE A SHOWER PAN DETAIL- SECTION 421.5 FBC
 P.
  
 11) P2 & P3: MODIFY THE WATER HEATER DETAIL TO SHOW THE
 REQUIRED DRAIN PAN, PAN DRAIN RUN AND TERMINATION
 LOCATION- 504.7 FBC P.
  
 12) P2: RELOCATE THE LOCATIONS OF THE WATER SHUT OFF
 VALVES FROM BEHIND THE STACKABLE WASHER/DRYER TO A
 LOCATION WITH ACCESS- SECTION 606.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2023-04-19 Cont ID  
Sent By jwitmer Date 2023-04-19 Time 08:05 Rev Time 0.00
Received By jwitmer Date 2023-04-17 Time 13:30 Sent To  
Notes
2023-04-19 08:04:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091114 / APPLICATION DATE 09/24/2020
 UNDER THE 2017 FBC-BUILDING
 ADD: 8130 N. JOG RD.
 CONT: THE WEITZ COMPANY
 TEL: 561-585-5511
 E-MAIL: LAUREN@[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. APRIL 19TH/ 2023
 ACTION: DENIED
 MONDAY APRIL 17TH, I SPOKE WITH JOE COLOME OF COLOME &
 ASSOCIATES ABOUT THIS PROJECT. WITHOUT STATE APPROVED
 PLANS SHOWING THE MODULAR BUILDING WAS DESIGNED AS
 SHOWN ON SHEET A-1, THAT NO REMODELING WAS OR IS GOING
 TO TAKE PLACE TO THIS MODULAR BUILDING. OTHERWISE THE
 STRUCTURE LOSES ITS STATE APPROVAL, THE INSIGNIA IS
 REMOVED AND RETURNED TO THE STATE. A COMPLETE SET OF
 PLANS WOULD BE REQUIRED FOR THE STRUCTURE FOR ALL
 TRADES INCLUDING THE ENERGY CODE, PRODUCT APPROVAL
 WINDOWS, DOORS AND ROOFING, WIND DESIGN MATE LINE
 FASTENING SCHEDULE, ANCHORING SCHEDULE AND MONOLITHIC
 SLAB IF PART OF THIS PERMIT. MR. COLOME WAS GOING TO
 GET IN TOUCH WITH THE CONTRACTOR THE WEITZ CO. IN
 REGARDS WITH THIS MATTER TO DATE THERE HAS BEEN NO
 FURTHER RESPONSE FROM THE DESIGNER OF RECORD NOR
 CONTRACTOR.
  
 1) THE LIFE SAFETY SHEET:
 1A) TO BE REVIEWED UNDER THE 2020 FBC-BUILDING CODE.
 THIS REVIEW WILL NOT HAPPEN UNTIL EITHER STATE APPROVED
 MODULAR BUILDING PLANS ARE SUBMITTED WITH NO INTERIOR
 CHANGES, OR IT IS STATED IN THE PLANS THAT THE STATE
 APPROVED MODULAR BUILDINGS INTERIOR IS BEING REMODELED
 WHERE THE MODULAR BUILDING LOSES ITS STATE APPROVAL AND
 THEN THE DESIGNER OF RECORD HAS TO PROVIDE ALL OF THE
 PLANS, PRODUCT APPROVALS, ENERGY CALCULATIONS TIE DOWN
 AND PERMANENT FOUNDATIONS AND BRACING AND MATE LINE
 CONNECTIONS. WITH THAT BEING SAID IT MAY ALSO REQUIRE
 ADDITIONAL SITE INSPECTIONS THAT WOULD NORMALLY HAVE
 BEEN COMPLETED AT THE FACTORY. NEVER WOULD
 MANUFACTURERED BUILDING PLAN BE CONSIDERED A DEFERRED
 SUBMITTAL.
  
 F. S. 553 PART IV
  
 FS 428.5.1 ON SITE MODIFICATIONS. ON-SITE MODIFICATION
 TO MANUFACTURED BUILDINGS MUST BE INSPECTED BY EITHER A
 THIRD PARTY AGENCY
 OR BY THE AUTHORITY HAVING JURISDICTION AND MUST COMPLY
 WITH THE FLORIDA BUILDING CODE . THE AUTHORITY HAVING
 JURISDICTION HAS SUPERSEDING AUTHORITY OVER ANY ONSITE
 MODIFICATIONS TO A MANUFACTURED BUILDING OR MAY
 DELEGATE THIS AUTHORITY TO THE DEPARTMENT IN WRITING ON
 A CASE-BYCASE BASIS. UPON ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE MODIFIED MANUFACTURED BUILDING, THE
 OLD INSIGNIA SHALL BE REMOVED AND RETURNED TO THE
 DEPARTMENT.
  
 THIS REVIEW CAN NOT CONTINUE UNTIL THE STATE CERTIFIED
 PLANS ARE SUBMITTED.
  
 1B) PLEASE NOTE THE SUBMITTED LIFE SAFETY SHEET ALSO
 REFERENCES RENOVATIONS TO P B C FIRE-RESCUE STATION #
 21 PLEASE UPDATE PLANS FOR THIS PROJECT, FIRE-RESCUE #
 17. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE HEADING OF OCCUPANT LOADS THERE IS A
 COUNT OF OCCUPANTS BUT THE SQUARE FEET FOR EACH
 OCCUPANCY NOR THE OCCUPANT LOAD FACTOR IS GIVEN. 2017
 FBC-B TABLE 1004.1.2.
  
 1D) THE FLOOR PLAN INDICATES THE (2) END WALLS REQUIRE
 A 1 HOUR RATING OF THE EXTERIOR WALL, THERE ARE NO
 SECTIONS THROUGH THE PLAN INDICATING HOW THIS WILL BE
 ACHIEVED, AND COMPLIANCE WITH TABLE 602 OF THE 2017
 FBC-BUILDING CODE. THE LEFT-HAND SIDE OF THE SHEET
 THERE IS NO ASSUMED PROPERTY LINE ESTABLISHED LIKE
 THERE IS ON THE RIGHT SIDE.
  
 2) SHEET A-6 DETAILS 1, 2, 6 & 7 ALL SHOW THE BOTTOM
 CABINETS AT A HEIGHT OF 36 INCHES TOP OF COUNTERTOP AND
 SOME WITH EITHER SINKS AND OR LAVATORIES.
 2017 FBC-ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET S-3:
 3A) SHOWS FOUNDATION INFORMATION, ONE THING THIS SHEET
 DOES NOT PROVIDE IS TO WHAT WIND SPEED WAS THIS
 FOUNDATION (MANUFACTURED BUILDING) DESIGNED FOR. 2017
 TABLE 2604.5 RISK CATEGORY OF BUILDINGS AND OTHER
 STRUCTURES? RISK FACTOR IV FIRE, RESCUE AMBULANCE AND
 POLICE STATIONS AND EMERGENCY VEHICLE GARAGES.
  
 3B) THE PLAN INDICATES TE-2 INDICATES A THICKENED EDGE
 12 X 12 THICKENED SLAB, WHAT THE PLAN DOES NOT INDICATE
 WHERE IS FINISHED GRADE IN RELATIONSHIP TO THE TOP OF
 THE THICKENED SLAB, HOW MUCH OF THE FOUNDATION IS
 BENEATH THE GRADE AND IN COMPLIANCE WITH THE 2017 FBC-B
 1809.4 THE MINIMUM DEPTH OF FOOTINGS BELOW THE
 UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES.
  
 4) WITHIN THIS SET OF PLANS THERE IS NO INFORMATION ON
 THE PRE-ENGINEERED PRECAST CONCRETE, RAMPS, LANDINGS,
 STEPS & LANDING. WHO IS IN-CHARGE OF THE INSPECTIONS
 WHEN THESE COMPONENTS ARE BEING ASSEMBLED, IS PART OF
 THE MANUFACTURED BUILDING PROGRAM? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
 2017 FBC-B LIVE LOADS TABLE 1607.1.
  
 5) THERE WAS NO INFORMATION SUBMITTED FOR THE
 GUARDRAILS NOR HANDRAIL SYSTEMS AND HOW THEY ARE TO BE
 INSTALLED/ ANCHORED. 2017 FBC-B HANDRAILS SECTION 1014.
 GUARDS SECTION 1015, 1607.8.1 HANDRAILS AND GUARDS.
  
 6) FOR MANUFACTURED BUILDINGS UNDER THE FLORIDA MODULAR
 BUILDING PROGRAM THEY ARE APPROVED UNDER THE STATE BUT
 YOU STILL HAVE TO SUPPLY THE STATE APPROVED PLANS, THEY
 WILL NOT BE SIGNED AND SEALED BUT THEY WILL HAVE THE
 MANUFACTURER AND THE 3RD PARTY INSPECTION ENTITY AND
 PLAN REVIEW NUMBER SO WE CAN VERIFY THAT NO REMODELING
 OR CHANGES TO THE INTERIOR OF THE APPROVED STATE PLANS,
 OTHERWISE IT VOIDS THE STATE APPROVAL.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-08-24 Cont ID  
Sent By jwitmer Date 2021-08-24 Time 13:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-24 13:27:21SEE BUILDING REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By jwitmer Date 2021-04-05 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2021-04-05 Time 14:27 Sent To  
Notes
2021-04-05 16:50:59SUPPOSE TO BE A STATE OF FLORIDA MANUFACTURED MODULAR
 BUILDING WITH STATE APPROVAL, THIS REVIEW NO SUCH PLANS
 WERE SUBMITTED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-01 Cont ID  
Sent By ccole Date 2023-05-01 Time 09:24 Rev Time 0.00
Received By ccole Date 2023-05-01 Time 09:14 Sent To  
Notes
2023-04-24 09:09:33PLUMBING PLANS PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By jleahy Date 2021-09-24 Time 09:50 Rev Time 0.00
Received By jleahy Date 2021-09-24 Time 09:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-13 Cont ID  
Sent By ccole Date 2021-04-13 Time 17:09 Rev Time 0.00
Received By ccole Date 2021-04-13 Time 17:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-04-28 Cont ID  
Sent By llouie Date 2023-04-28 Time   Rev Time 0.00
Received By llouie Date 2023-04-28 Time   Sent To  
Notes
2023-04-28 15:59:16** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SITE PLAN (REFERENCE: ISPR 21-10) FOR THIS
 PROJECT HAD EXPIRED ON SEPTEMBER 22, 2022. A NEW SITE
 PLAN IS REQUIRED PRIOR TO PERMITTING.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * REFERENCE: ISPR 21-10
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-09-02 Cont ID  
Sent By llouie Date 2021-09-02 Time   Rev Time 0.00
Received By llouie Date 2021-09-02 Time   Sent To  
Notes
2021-09-02 15:20:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
  
 1.) AN APPLICATION FOR AN INFORMAL SITE PLAN REVIEW IS
 CURRENTLY PENDING WITH PLANNING STAFF. ZONING CANNOT
 PASS THE ZONING REVIEW UNTIL THE SITE PLAN APPROVAL HAS
 BEEN ISSUED. PLEASE CONTACT THE PROJECT MANAGER,
 RAFAELA THERMIDOR, ASSOCIATE PLANNER, AT (561) 822-1443
 FOR THE STATUS OF THE INFORMAL SITE PLAN APPLICATION.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CS
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-25 Cont ID  
Sent By llouie Date 2021-03-25 Time   Rev Time  
Received By llouie Date 2021-03-25 Time   Sent To  
Notes
2021-03-25 13:42:16** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SCOPE OF WORK IS FOR THE CONSTRUCTION OF A
 1,728 SQ. FT. PERMANENT MODULAR BUILDING AND A 168 SQ.
 FT. SHED ON THE PROPERTY. PER S.94-35 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, SITE PLAN REVIEW AND
 APPROVAL IS REQUIRED PRIOR TO BUILDING PERMIT. PLEASE
 CONTACT PLANNING STAFF FOR INFORMATION.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: CS
  