Plan Review Details - Permit 20091045
Plan Review Stops For Permit 20091045
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-13 Cont ID  
Sent By dbattles Date 2021-01-13 Time 16:26 Rev Time 0.00
Received By dbattles Date 2021-01-13 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-11 Cont ID  
Sent By rmcdouga Date 2020-12-11 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2020-12-11 Time 16:21 Sent To  
Notes
2020-12-11 16:32:54PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEERED CALCULATIONS FOR THE BEAM SPAN ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL THAT PREPARED THEM. FBC 107.1 & 107.2.1.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2020-10-14 Time 08:51 Sent To  
Notes
2020-10-14 10:27:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL FOR THE CONCRETE ROOF TILE IS
 EXPIRED. NOA NO. 14-0408.06 EXPIRED ON 5/20/2019.
 SUBMIT CURRENT PRODUCT APPROVAL.CITY AMENDMENTS FBC
 107.3.4
  
 2) SPECIFY THE SLOPE OF THE AWNING ROOF. THE MINIMUM
 SLOPE FOR TILE ROOFS IS 2:12. FBCR905.3.7
  
 3)THE PLANS SPECIFY THAT THE LEDGER AND WALL BRACKET
 ARE BOLTED TO THE EXISTING WOOD WALL FRAMING. SPECIFY
 THE BOLT TYPE ( LAG BOLT) AND THE REQUIRED EMBED DEPTH
 INTO THE EXISTING WOOD FRAMING. CITY AMENDMENTS FBC 107
  
 4) THE PLANS SPECIFY THAT THE ROOF SHEATHING IS A 1/2"
 TONGUE AND GROOVE SYSTEM. PLEASE CLARIFY WHAT THIS IS.
 TILE ROOFS REQUIRE MORE THAN 1/2" SHEATHING WITH 24" OC
 RAFTER SPACING. CITY AMENDMENTS FBC 107.2.1
 NOTE. THE ROOFING NAILS USED FOR THE 30 # UNDERLAYMENT
 WILL BE EXPOSED ON THE UNDERSIDE OF THE ROOF DECK IF
 1/2" ROOF SHEATHING IS USED. FBC-R905.3.6 FASTENERS.
 REQUIRES THE FASTENERS TO PENETRATE THROUGH OR A
 MINIMUM OF 3/4" INTO THE SHEATHING.
  
 5) THE SPAN BETWEEN THE SUPPORT BRACKETS FOR THE 4X8
 BEAM CARRYING THE TILE ROOF APPEARS TO BE EXCESSIVE.
 PROVIDE SIGNED AND SEALED CALCULATIONS TO SHOW THE
 ALLOWABLE SPAN FOR THE 4X8 BEAM, CITY AMENDMENTS FBC
 107.2.1.2
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By fmittner Date 2020-12-16 Time 15:08 Rev Time 0.00
Received By fmittner Date 2020-12-16 Time 15:08 Sent To  
Notes
2020-12-16 15:09:23PASSED FOR BORRAL HIGH S TILE NOA'S SUBMITTED SINC ENEW
 PENT ROOF

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-10-13 Cont ID  
Sent By fmittner Date 2020-10-13 Time 16:57 Rev Time 0.00
Received By fmittner Date 2020-10-13 Time 16:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-13 Cont ID  
Sent By dbattles Date 2021-01-13 Time 16:26 Rev Time 0.00
Received By dbattles Date 2020-11-23 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2020-10-02 Time 14:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-01-13 Cont ID  
Sent By dbattles Date 2021-01-13 Time 16:26 Rev Time 0.00
Received By dbattles Date 2021-01-13 Time 16:26 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2020-10-14 Time 08:51 Sent To  
Notes
2020-10-14 10:15:06THE PRODUCT APPROVAL FOR THE CONCRETE ROOF TILE IS
 EXPIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-12-11 Cont ID  
Sent By rmcdouga Date 2020-12-11 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2020-12-11 Time 16:21 Sent To  
Notes
2020-12-11 16:34:02THE BEAM CALCULATIONS ARE NOT SIGNED AND SEALED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-10-14 Cont ID  
Sent By rmcdouga Date 2020-10-14 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2020-10-14 Time 08:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By fmittner Date 2020-12-16 Time 15:08 Rev Time 0.00
Received By fmittner Date 2020-12-16 Time 15:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-13 Cont ID  
Sent By fmittner Date 2020-10-13 Time 16:57 Rev Time 0.00
Received By fmittner Date 2020-10-13 Time 16:57 Sent To  
Notes
***NONE***