2020-10-02 13:40:59 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 2091028 |
| 10/2/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE ADDITIONAL INFORMATION ON THE GAS RISER |
| DRAWING: |
| |
| A) TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM FROM THE |
| METER TO THE MOST REMOTE OUTLET- SECTION G2413.1, AND |
| THE TOTAL BTUH LOAD- G2413.2 FBC RES. |
| |
| B) SHOW REQUIRED SHUTOFF VALVES AT EACH APPLIANCE- |
| SECTION G2420.5. |
| |
| C) LABEL THE LOW PRESSURE REGULATOR AND SHOW THE |
| SELECTED MAKE AND MODEL, THE OUTLET PRESSURE AND THE |
| REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE |
| REGULATOR- SECTION 2421.1 & 2421.2. PLEASE NOTE THAT |
| REGULATOR SPECS SHALL BE ONSITE AND BE HIGHLIGHTED TO |
| SHOW THE SELECTED MODEL, THE INLET AND OUTLET PIPE |
| SIZES AND PRESSURES, SPRING SELECTION, ORIFICE SIZE, |
| AND THAT THE MODEL IS SUITABLE FOR OUTDOOR USE. |
| |
| 3) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE |
| NEW RANGE AND PROVIDE COMBUSTION AIR CALCULATIONS- |
| SECTION G2407.1. PLEASE NOTE IF USING INDOOR AIR SEE |
| SECTION G2407.5. |
| |
| 4) INDICATE HOW THE NEW RANGE WILL BE VENTED. CLARIFY |
| IF THERE IS AN EXISTING RANGE HOOD OR IF A NEW HOOD AND |
| EXHAUST SYSTEM WILL BE INSTALLED- SECTION M1503 FBC |
| RES. AND SECTION 107.2.1 WPB. PLEASE NOTE THAT NEW |
| RANGE HOODS AND EXHAUST DUCTS WILL REQUIRE PLANS AND |
| SPECIFICATIONS TO BE SUBMITTED, AND A MECHANICAL SUB OR |
| PRIMARY PERMIT MUST BE OBTAINED- SECTION 105.1 WPB. |
| |
| 5) PROVIDE A DETAIL SHOWING THE LOCATION OF THE |
| TANKLESS WATER HEATER AND REQUIRED INSTALLATION AND |
| VENT CLEARANCES FROM GRADE, OVERHEAD CONSTRUCTION, AIR |
| INTAKES, AND OPERABLE OPENINGS INTO THE BUILDING- |
| SECTIONS G2427 & G2448.1 FBC RES. |
| |
| 6) THE SIGNATURE OF THE CONTRACTOR OF RECORD- KIRK |
| ANGELOCCI- SHALL BE ON THE DRAWINGS PER SECTION 107.2.1 |
| WPB AND FL. STATUTES 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |